11
delivery
water
temp.
°C
thermal
power
W
delivery
air temp.
°C
30
848
28,3
35
1274
32,5
40
1664
36,4
45
2138
41,0
delivery
water
temp.
°C
tot.
thermal
power
W
room
thermal
power W
delivery
air temp.
°C
power
required
by heat
pump
W
30
2164
811
28,1
983
35
2589
1235
32,3
1408
40
3021
1668
36,5
1840
45
3452
2099
40,8
2271
TECHINCAL DATA
Electric power
V/Ph/Hz
230/
1/50
Weight
kg
71
Total dehumidification capacity
(external environment 35 °C, 50% R.H.)
l/24h
44,9
W
1083
Useful dehumidification capacity
(referred to recirculation, room at 26 °C, 55% R.H.)
l/24h
25,9
W
625
Useful cooling capacity
(referred to recirculation, room at 26 °C, 55% R.H.)
W
1050
Electric power absorbed by the compressor
W
460
Water flow rate required
l/h
400
Water circuit loss of pressure
kPa
8
Power absorbed by the delivery fan (min - max)
W
15 -
70
Delivery fan flow rate (min - max)
m3/h
80 -
300
Delivery fan useful hydraulic head
Pa
120
Power absorbed by the ejection fan (min - max)
W
15 -
30
Ejection fan flow rate (min - max)
m3/h
80 -
160
Ejection fan useful hydraulic head
Pa
100
Energy recovery during winter operation
(20 °C - 50% internal r.h., -5 °C - 80% external r.h.)
flow rate 80
m3/h
95%
flow rate 160
m3/h
91%
Energy recovery during summer operation
(26 °C - 65% internal r.h., 35 °C - 50% external r.h.)
flow rate 80
m3/h
93%
flow rate 160
m3/h
86%
Sound pressure level
(in open field, distance 1m)
dB(A)
39
Quantity of R134a cooling gas
kg
0,56
Equiv. CO
2
(GWP = 1430)
t
0,80
Specific energy consumption (SEC)
-
Cold
-
Temperate
-
Warm
kWh/m
2
a
-76,13
-38,40
-4,16
SEC class
kWh/m
2
a
A
PERFORMANCE
WINTER, heating (total flow rate 300m3/h)
Recirculation
Ex Recirculation
(300m3/h 20 °C 40%RH)
(160m3/h -5 °C, 90%RH+ 140m3/h 20 °C, 40%RH)