KDVRAY500 MANUAL
Pag. 16 of 24
CONTROL UNIT - CONNECTIONS
The control unit has to be placed into an electric panel and fixed on a DIN rail. The occuped
space is 6 DIN modules.
COMMUNICATION WITH HANDLING MACHINE
Connectons between handling machine and control unit have to be made for energy supply
(24VDC) and serial bus communication. Use a 4-wire shelded cable, minimum cross-section
0.5 mmq.
OUTPUT RELAYS
-
C01-NO1: relay 250V AC – 5A, is activated when water circulation is needed, it can be
connected to a pump.
-
C01-NO2: relay 250V AC – 5A is activated as alarm in case of fault.
MODBUS CONNECTION: the connection is made with 4 wires, 2 wires are used for the 24VDC
power supply to the control panel, the other 2 are for serial communication.
For connection, use a shielded cable, sect. minimum 0.5 mm2.
Connection to unit
Output relays
Digital inputs