DIAGNOSTICS
- The control panel displays the alarm and fault messages communicated by the
electronic board on the machine. The messages are all encoded with a multiple number
of 2 and are of two types:
- fault messages, indicate a malfunctioning sensor;
- alarm messages, indicate an anomalous operating condition.
Fault messages
Displayed
Meaning
Sensor Fault: 1
Delivery air temperature probe fault
Sensor Fault: 2
Evaporator temperature probe fault
Sensor Fault: 4
Undercooling temperature probe B fault
Sensor Fault: 8
Overheating temperature probe fault
Sensor Fault: 16
Undercooling temperature probe A fault
Sensor Fault: 32
Water temperature probe fault
Sensor Fault: 64
Compressor temperature probe fault
Sensor Fault: 128
Outside air temperature probe fault
Sensor Fault: 256
Coolant pressure transducer fault
Sensor Fault: 512
Failure on the flow sensor for air supply
Sensor Fault: 1024
Failure on the flow sensor for stale air
Sensor Fault: 2048
Failure on the flow sensor for renewal air
Alarms messages
Displayed
Meaning
Alarm: 1
Refrigeration circuit low pressure alarm
Alarm: 2
Refrigeration circuit high pressure alarm
Alarm: 4
Compressore high temperature alarm
Alarm: 8
Serial bus comunication alarm
Alarm: 32
Water temperature alarm
Alarm: 64
Inflow fan alam
Alarm: 128
Discharge fan alarm
If the alarm is permanent, the machine stops and cannot restart until the alarm is cleared by
cutting off the power supply to the machine.
The other alarms, on the other hand, cancel themselves when the cause that activated them is
no longer there.
The control panel displays only one message; in the presence of several alarms, the message
displayed will show a number equal to the sum of the numbers of the alarms present.
For example: a fault with the number 34 indicates the simultaneous presence of fault 32 and
fault 2.
When there are multiple Errors, the total number will appear (Alarms with Alarms and Sensor
Faults with Independent Sensor Faults).