10
UGT Series Manual
Freeze Protection
Make sure that in case of freezing weather that the
water heater and its water lines are protected to
prevent freezing. Damage due to freezing is not
covered by the warranty.
Loss of freeze protection may result in water damage
from a burst heat exchanger or water lines.
With electrical power supplied, the water heater will
not freeze when the outside air temperature is as cold
as –22°F (-30°C) for indoor models when protected
from direct wind exposure. Because of the “wind-
chill” effect, any wind or circulation of the air on the
unit will reduce its ability to freeze protect.
The unit may be drained manually. However, it is
highly recommended that drain down solenoid valves
are installed that will automatically drain the unit if
power is lost. These are available in a kit, P/N
15000029-A.
In addition, the solenoid valves should be connected
electrically to a surge protector with terminals. This
allows the solenoid valves to operate if the water
heater is disabled due to a diagnostic code.
The freeze protection features will not prevent the
external piping from freezing. It is recommended that
hot and cold water pipes are insulated. Pipe cover
enclosures may be packed with insulation for added
freeze protection.
In the event of a power failure at temperatures below
freezing the water heater should be drained of all
water to prevent freezing damage. In addition, drain
the condensate trap and drain line.
Maximum vent length
1. Determine the number of 90 degree elbows in
the vent system. (Two 45 degree elbows count as
one 90 degree elbow.)
2. Refer to the table to find the maximum vent
length based on the number of elbows.
3. Adjust switch No. 1 in the SW1 DIP switch (tan
switches) if required by the applicable note.
If the length is greater than 21 ft (6.4 m) then
move switch No. 1 (SW1) to OFF.
If the length is greater than 15 ft (4.6 m) then
move switch No. 1 (SW1) to OFF.
If the length is greater than 9 ft (2.7 m) then move
switch No. 1 (SW1) to OFF.
Move switch No. 1 (SW1) to OFF.
Example: If you have one elbow then your maximum
vent length is 35 feet (10.7 m). If your
actual length is greater than 15 ft (4.6 m)
then move switch no. 1 (SW1) to OFF.
Number of
90° Elbows
Maximum vent length
0
41 ft (12.5 m)
1
35 ft (10.7 m)
2
29 ft (8.8 m)
3
23 ft (7.0 m)
4
17 ft (5.2 m)
5
11 ft (3.4 m)
6
5 ft (1.5 m)
If you have a longer vent length (see above), switch
No. 1 is required to be in the OFF position. This
ensures the water heater will run properly. Blocked
flue diagnostic codes and shutdowns may result if
switch No. 1 is not in the correct position.
NOTICE