22
FUNCTION
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
MIN.
÷
MAX.
0
÷
50
0
÷
6
0
÷
2
0
÷
7
0
÷
10
-
0
÷
5
0
÷
1
0
÷
2
0
÷
2
0
÷
2
DEFAULT
0
0
0
4
0
45
0
0
0
0
0
DESCRIPTION
DECELERATION TIME AT BEGINNING OF MANOEUVRE
0 = Function not active.
Adjustable between 1 and 50 seconds. The time is calculated from the beginning of the
manoeuvre; therefore, after starting, the motor will run at a reduced speed for the time set on
the display and then run at maximum speed.
DECELERATION SPEED AT BEGINNING OF MANOEUVRE
0 = Function not active (maximum speed – no deceleration).
1 = Minimum deceleration
6 = Maximum deceleration.
WARNING LIGHT (21-18)
0 = Comes on in the opening phase, remains on during pause and goes off at the start of the
closing phase or when pressing the stop button.
1 = Comes on in the opening phase, remains on during pause, flashes during the closing
phase and goes off when the closing limit switch has been reached or at the end of the
operating time. If the stop button is pressed when the gate is not at the closing limit
switch, the light will remain on.
2 = Flashes slowly during the opening phase, comes on during pause, flashes fast during
the closing phase. The light goes off when the closing limit switch has been reached or
at the end of the operating time. If the stop button is pressed when the gate is not at the
closing limit switch, the light will remain on.
FLASHING LIGHT (20-18)
0 = Fixed light output; it comes on at the beginning of the opening phase, goes off during
pause and comes on again at the beginning of the closing phase.
1 = Fixed light output: it comes on at the beginning of the opening phase, goes off during
pause and comes on again at the beginning of the closing phase, however, a pre-
flashing may be set during the closing phase.
2 = Fixed light output: it comes on at the beginning of the opening phase, goes off during
pause and comes on again at the beginning of the closing phase, however, a pre-
flashing may be set during the closing and opening phase.
3 = Fixed light output: the flashing light comes on at the beginning of the opening phase,
remains on during pause and goes off at the end of closing.
4 = Same function as “0” but with flashing light output.
5 = Same function as “1” but with flashing light output.
6 = Same function as “2” but with flashing light output.
7 = Same function as “3” but with flashing light output.
PRE-FLASHING TIME
Adjustable between 0 and 10 seconds.
COURTESY LIGHT TIME
Function not available.
SAFETY SWITCH TESTS
0 = No test.
1 = Test at beginning of manoeuvre only on internal photocell
2 = Test at beginning of manoeuvre only on external photocell
3 = Test at beginning of manoeuvre on internal and external photocell
4 = Test at beginning of manoeuvre on internal photocell and frame during the opening
phase
5 = Test at beginning of manoeuvre on all safety devices
N.B.: The torque regulator test is run in all conditions (also “0”).
MOTOR SELECTION
0 = 2 motors
1 = 1 motor. N.B.: for this equipment.
PROGRAMMING OF KEY 4 OF THE TRANSMITTER
0 = Performs the same functions as the start button (terminals 8-6).
1 = Performs the same functions as the pedestrian gate button (terminals 9-6).
2 = Performs the same functions as the closing button (terminals 7-6).
PROGRAMMING OF KEY 3 OF THE TRANSMITTER
0 = Performs the same functions as the start button (terminals 8-6).
1 = Performs the same functions as the pedestrian gate button (terminals 9-6).
2 = Performs the same functions as the closing button (terminals 7-6).
PROGRAMMING OF KEY 2 OF THE TRANSMITTER
0 = Performs the same functions as the start button (terminals 8-6).
1 = Performs the same functions as the pedestrian gate button (terminals 9-6).
2 = Performs the same functions as the closing button (terminals 7-6).