Start-up and calibration
21 Start-up and calibration
Determine the burner output according to the table on page 23 ff. P0 = Start stage, P1 = 1st stage / min.
output, P9 = 2nd stage / max. output.
Normally, P0 = P1. For the condensing boiler, P0 must be set higher than P1. The setting is dependent on
the boiler. The mixer head must be set according to the table.
To enter this adjustment mode, the burner must be on standby.
Standby means that the burner is supplied with voltage, gas pressure is built up and there is no demand
for heat.
The firing managers are parametrized in the factory. OFF UPr appears in the display during first start-up.
Enter password
Action button
Display
Description
OFF UPr
means burner off and
non-programmed.
OFF
means burner off and programmed.
Action button
Display
Description
Press
F and A button
simultaneously.
The display
CodE
appears
After releasing the buttons, 7 bars appear and
the first one flashes.
Use the
- or + button
to select a number or let-
ter.
Confirm each value with
i/reset
.
Confirm the password
1234
with
i/reset
after the
last input.
After correct input, the following appears for a
max. of two seconds
/reset
/reset