background image

Subject to alterations, 03.06.20

25/32

Error code list LMV

25 Error code list LMV 

loc.C:

loc.d:

Description

Measure

No communication between basic unit 
LMV27... and AZL2… 

Check wiring for interruptions/loose contacts

2

1 - 4

No flame at the end of the safety time

3

0 - 84

Compressed air fault

No compressed air

4

0 - 86

External light

7

0 - 255

flame cut-off

12

0

Fuel valve 1 leaking
(fuel valve 2 for leakage check 9

For leakage check via X5-01 
(gas pressure switch min) 
- Check whether valve on burner side is leaking 
- Check whether pressure switch for leakage 
check

is closed when gas pressure is applied 

- Check wiring for short-circuit

1

Fuel valve 2 leaking
(fuel valve 1 for leakage check via 
X5-01)

For leakage check via X5-01 
(gas pressure switch min) 
- Check whether valve on gas side is leaking 
- Check wiring for short-circuit 

2- 5

Leakage check not possible

Leakage check activated but no input assigned

81

V1 leaking

Check whether valve on gas side is leaking 
Check the wiring for interruptions 

83

V2 leaking

Check whether the valve on the burner side is 
leaking 
Check whether the pressure switch for the leak 
test is closed when gas pressure is applied 
Check wiring for short-circuit

14

0

POC open

Check whether valve NC contact is closed 

1

POC closed

Check wiring 
Check whether valve NC contact opens when he 
valve is activated 

64

POC open start prevention

Check wiring for interruptions 
Check whether valve NC contact is closed 

19

80

Combustion pressure, POC start preven-
tion

Check whether the pressure switch is closed 
without combustion pressure being present 
Check wiring for short-circuit 

20

0 - 1

Pressure switch min no minimum gas 
pressure/oil pressure 

Check wiring for interruption

21

0- 64

Pressure switch max/POC

Check wiring for interruption. 
POC: Check whether valve NC contact 
is closed 

22 OFF S

0 - 87

Safety chain

23

0 - 2

Gas pressure switch min (Pmin)

Check wiring for interruption (X5-01)

50 - 67

#

Internal error

70

26 - 26

Error group

Set all curve points for gas and air actuators, and 
for the FC

71

0 - 3

Special position undefined

Parametrise actuators

75-84

Internal fault group

85

0

Error group fuel drive

Referencing of fuel drive not possible. 
Unable to reach reference point. 
1. Check whether the drives have been 
exchanged 
2. Check whether the drive is blocked or over-
loaded 

Summary of Contents for MG20-ZM-L-LN Series

Page 1: ...Issued in June 2020 Subject to tech modifications to improve the product Gas Technical Information Installation Instructions MG20 ZM L LN GB...

Page 2: ...nts 7 12 Electrical connection 8 13 Air flap positioning motor 9 14 Air pressure switch 9 15 Gas pressure monitor 10 16 Adjusting the ignition electrode 11 17 Measuring the ionisations current 11 18 A...

Page 3: ...s Before installing the gas burner please check the scope of delivery Scope of delivery burner housing gas jacket with burner pipe mount ing kit documentation and gas train Gas installation and commis...

Page 4: ...enuine parts or where the equipment has been used for purposes for which it was not intend ed 4 Operating instructions The operating instructions together with this techni cal information leaflet must...

Page 5: ...size Allen key The air pressure switch for the gas train must be at the top Burner type Technical specifications MG20 1 ZM L LN MG20 2 ZM L LN Burner output in kW 224 860 247 1350 Gas type Natural ga...

Page 6: ...on the burner housing in the gas jacket hinge and secure it with a rod The burner is now in the service position Attach the ignition and ionisation cable to the igni tion and ionisation electrodes Car...

Page 7: ...HLWH 0 0 09 0 HDUE 8UVSU 63B VWURNRVFK DWXP DWXP UVHW W GXUFK RLOHU bQGHUXQJ HSU UVDW YRQ QHUWHFK PE UHQQHU XQG HL V VWHPH D 1DPH HLFKQ 1U GHQW 1U HVVHO XQGH QVFKOXVV HVVHO ZHLVWXILJ QVFKOXVV HVVHO PR...

Page 8: ...r must be of the flexi ble type To access the firing unit the cover must be brought to the service position To do this remove the secur ing screws 1 and fold the cover down to the left After wiring ha...

Page 9: ...rners The motor is activated electron ically via the microprocessor controlled control box Do not open the air flap actuator while it is under voltage The internal optics would be destroyed No warrant...

Page 10: ...DK the GDW MIN jumper has to be replaced with the connection of the gas pressure switch MIN When using the gas cycle MB VEF 412 the connec tion is made via the 7 pin connector and is only evaluated as...

Page 11: ...tion current must be measured during burner start up and maintenance or after a fault in dication in the control box This done by disconnect ing the plug in the ionisation cable and connecting it to t...

Page 12: ...XV UXQQLQJ 6DIHW YDOYH 69 JQLWLRQ XHO YDOYH 9 3LORW YDOYH 39 3UHVVXUH VZLWFK PLQ JDV PLQ RLO 3 PLQ RQQHFWLRQ 20 XLOGLQJ DXWRPDWLRQ FWXDWRU IXHO FWXDWRU DLU 96 UHTXHQF FRQYHUWHUV 1 3 6DIHW FKDLQ 3RZHU...

Page 13: ...in parametrisation mode Unlock in case of fault One menu level down Button Reduce value For navigating in curve setting information and service mode Button Increase value For navigating in curve setti...

Page 14: ...th voltage gas pressure is built up and there is no demand for heat The firing managers are parametrized in the factory OFF UPr appears in the display during first start up Enter password Action butto...

Page 15: ...the setting tables to preset the values Action button Display Description When the firing machine is programmed run is displayed i reset skips the next steps an continues at the section Start heat set...

Page 16: ...oad air flap Hold down button A and set the value with the or button Move to the next curve point Action button Display Description When heat demand is present Confirm with i reset button Burner start...

Page 17: ...button to confirm Ignition ON Valves ON Ignition OFF Flame in start position When transferring P1 to P2 for the first time CALC appears briefly The curve points P2 to P9 are calculated auto matically...

Page 18: ...Action button Display Description Check the high load setting via the gas flow at the gas meter or compare the nozzle pressure with the values stated in 24 Adjustment tables Hold down A button and use...

Page 19: ...fety time ignition transformer ON Ph42 First safety time ignition transformer OFF Ph44 Interval 1 Ph50 Second safety time Ph52 Interval 2 Ph60 Operation 1 stationary Ph62 Maximum time small load setti...

Page 20: ...tion and repeat start KEV 1 KEV2 KEV DN65 VGD20 40 VGD20 50 VGD40 65 all SKP15 75 KEV412 1 MB VEF 412 Installation of the gas train Installation position only in horizontal line not tilted Minimum dis...

Page 21: ...too low O2 too high Change in direction if CO2 too high O2 too low Small flame N setting Exhaust gas analysis values Change in direction if CO2 too low O2 too high Change in direction if CO2 too high...

Page 22: ...ospheric pressure B acc to Tab 989 mbar Gas pressure PG at gas meter 20 mbar Gas temperature G 16 C Boiler output Qn 220 kW Efficiency K assumed 92 Calorific value Hi n 10 4 kWh m3 Gas flow in standar...

Page 23: ...Stage 1 Stage2 Stage1 Stage2 Stage1 Stage2 Stage1 Stage2 Stage1 Stage2 Stage1 Stage2 Stage1 Stage2 Stage1 450 224 419 26 0 9 22 7 3 2 1 49 9 24 8 5 7 1 6 44 6 22 2 7 4 2 0 17 4 8 7 520 260 484 33 0 12...

Page 24: ...5 66 5 33 3 5 4 2 0 59 5 29 7 7 5 2 4 23 2 11 6 800 400 736 40 20 22 12 8 4 2 88 7 44 3 10 0 3 3 79 3 39 7 12 8 3 7 30 9 15 4 1000 500 920 90 25 22 19 6 5 2 110 9 55 4 15 3 4 1 99 1 49 6 19 5 5 4 38 6...

Page 25: ...ide is leaking Check whether the pressure switch for the leak test is closed when gas pressure is applied Check wiring for short circuit 14 0 POC open Check whether valve NC contact is closed 1 POC cl...

Page 26: ...ble defective 95 3 Ignition trans former 4 Fuel valve 1 5 Fuel valve 2 6 Fuel valve 3 External supply NOC Check wiring 96 3 Ignition trans former 4 Fuel valve 1 5 Fuel valve 2 6 Fuel valve 3 Relay wel...

Page 27: ...just ments log Boiler type Gas fitting Measured values min max Date P0 start point P1 min load P9 max load Flue gas temperature C Carbon dioxide CO2 level O2 content CO level Flue mbar Nozzle pressure...

Page 28: ...28 32 03 06 20 Subject to alterations Exploded view drawing spare parts list 27 Exploded view drawing spare parts list ZBZ_2 529...

Page 29: ...Sight glass cover 5 47 50 12106 11 Hood MG20 1 47 90 24857 12 Inspection glass with seal 5 36 50 11544 13 Fan wheel 218 x 80 for MG20 1 1 36 90 11540 01 13 Fan wheel 224 x 82 for MG20 2 1 47 90 24847...

Page 30: ...s We Enertech GmbH Adjutantenkamp 18 in D 58675 Hemer declare under our responsibility that gas burner type MG20 is conform with the regulations of these directives MD2006 42 EG EMC2014 30 EU GAD 2016...

Page 31: ...Subject to alterations 03 06 20 31 32 Declaration of Conformity for Gas Burners...

Page 32: ...be duplicated without our written permission given in advance Subject to alterations 29 Dimensions all dimensions are given in mm 30 Working ranges Working ranges acc to DIN EN 676 The working ranges...

Reviews: