26/32
03.06.20, Subject to alterations
Error code list LMV
85
1
Error group air drive
Referencing of fuel drive not successful.
Unable to reach reference point.
1. Check whether the drives have been
exchanged
2. Check whether the drive is blocked or over-
loaded
86
0 - 1
Error group fuel drive
Unable to achieve the target position within the
required tolerance.
-> Check whether the drive is blocked or over-
loaded. A line break was detected at the drive
connections.
-> Check wiring (voltage X54 between Pin 5 or 6
and Pin 2 >0.5 V).
87
0 - 4
Error air drive
Unable to achieve the target position within the
required tolerance.
-> Check whether the drive is blocked or over-
loaded. A line break was detected at the drive
connections.
-> Check wiring (voltage X53 between Pin 5 or 6
and Pin 2 >0.5 V).
90 - 92
#
Internal fault group
93
3
Short-circuit of probe
Short-circuit at QRB...
1. Check wiring
2. Flame probe possible defective
95
3 Ignition trans-
former
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
External supply NOC
Check wiring
96
3 Ignition trans-
former
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
Relay welded
Measure the contacts:
1. Device at voltage: Blower output must be de-
energised
2. Deactivated voltage: Disconnect blower. There
must be no ohmic connection between blower
output and N.
If one of the two tests fails, replace the unit, since
the contacts are definitely welded and safety can
no longer be guaranteed.
97
0
Safety relay welded or external voltage at
safety contact
Measure the contacts:
1. Device at voltage: Blower output must be de-
energised
2. Deactivated voltage: Disconnect blower. There
must be no ohmic connection between blower
output and N.
If one of the two tests fails, replace the unit, since
the contacts are definitely welded and safety can
no longer be guaranteed.
98
2 Safety valve
3 Ignition trans-
former
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
Replay does not pick up
Unlock; if it recurs, replace the unit
99 - 250
#
Internal error
loc.C:
loc.d:
Description
Measure