8.4 Inserting connecting cables
-
Unroll system cable and insert continuously into the groove (protect mechanically!)
-
Cabling from control unit according to project specifications (observe channels / lines)
-
Feed-in 24V voltage
Hint
System MarkLED only needs a
very small cross section due to the
small power input.
Even with consideration of the
voltage drop, the cross section of
2.5 mm2 is sufficient.
Hazard
Protect the cables against me-
chanical damage!
embedding in
the cleaned
groove
system cable 2.5 mm
2
particularly heat proof
up to 250°