How To Install a Server into a Tank
G292
@GIGABYTESERVER
GIGABYTE
GIGABYTEChannel
gigabyteserver
Installing Server
2
1
1
Installation
1 Attach the two carabiners to server handles.
2 Put the server into the tank vertically.
Strongly recommended to use gloves when handling the coolant.
Before handling coolant, handlers must read the material safety data sheet (MSDS) for their safety.
The thermal pad contains Indium foil, so it is strongly recommended to use gloves
when replacing the thermal pad.
DANGER!
CAUTION!
Make sure the crane can handle at least 60 KG before installing the server into a tank.
Only licensed professionals are authorized to access the restricted access location.
The power supply fan is disabled by default, so the server must be immersed in the fluid before powering on.
Consult with immersion cooling tank vendor to ensure compatibility and read their tank manual thoroughly.