3.2 Wiring

 

 

Use twisted pair cables with shield. 

Recommended cable: UL2464, UL2448, etc. 

 

The total extension length of the cable is up to 500m. A master station and up to 255 units of 

the SE series can be connected per line. 

 

Both ends of the cable should be connecting with terminate resistors 100  1/2W. 

 

The shield wire of the cable should be grounded at one place on the master station unit side. 

 

4. SETTING OF COMMUNICATION CONDITION 

In order that the master station and SE series can correctly communicate, 

following settings are required. 

 

All communication condition settings of the master station are the same as those of SE 

series. 

 

All SE series connected on a line are set to address (ADDR), which are different from each 

other. 

4.1 Set Items 

The parameters to be set are shown in the following table. Set them by operating the front 

panel keys. 

Parameter Item 

Value 

at 

delivery 

Setting range 

Remarks 

BAUD Transmission 

speed 

9600 

2400/4800/9600/19200 

--------- 

Data length 

8 bits 

Fixed (can’t be changed) 

--------- 

Stop bit 

2 bit 

Fixed (can’t be changed) 

--------- Parity 

setting  None 

Fixed (can’t be changed) 

Set the same 

communication 

condition to the 

master station and all 

slave station. 

ADDR Address 

 

1 to 255 

 

Set a different value 

to each station. 

4.2 Setting Operation Method 

The following example shows how to set the communication condition. 

Example: Setting a transmission speed is 9600 bps and address at 12 on a station. 

Key 

operation 

Indication Description 

Power ON 

25/100 

Power on running state (PV/SP indication) 

SET  

(5 seconds) 

PB 

Press SET key simultaneously for approximately 5 

seconds to get level parameter. 

SET  

(5 seconds) 

TYPE 

Press SET key simultaneously for approximately 5 

seconds to get level parameter. 

SET 

 

Press SET key to go into level. 

SET 

ADDR 

Press SET key repeatedly until ADDR is display. 

 or 

 

ADDR/12 

Press 

 or 

  key to setting “ADDR=12” 

SET 

BAUD 

Press SET key again to select next parameter “BAUD” 

 or 

 

BAUD/9.6K 

Press 

 or 

  key to setting “BAUD=9.6K”   

Summary of Contents for SE2000 SERIES

Page 1: ...ng Operation Method 2 5 MODBUS COMMUNICATION PROTOCOL 5 1 General 3 5 2 Composition of Message 3 5 3 Response of Slave Station 4 5 4 Function Code 4 5 5 Calculation of Error Check Code CRC 16 4 5 6 Tr...

Page 2: ...nication Specifications Item S pecification Electrical specification Based on EIA RS 485 Transmit system 2 wire semi duplicate Synchronizing system Asynchronous mode Connection format 1 N Number conne...

Page 3: ...at delivery Setting range Remarks BAUD Transmission speed 9600 2400 4800 9600 19200 Data length 8 bits Fixed can t be changed Stop bit 2 bit Fixed can t be changed Parity setting None Fixed can t be...

Page 4: ...is explained 1 Start In RTU mode messages start with a silent interval of at least 3 5 character times This is most easily implemented as a multiple of character times at the baud rate that is being...

Page 5: ...mand but creates and sends back a response message at error detection The composition of response message at error detection is shown on below the value used for function field is function code of com...

Page 6: ...1 1 5 For ensuring the safety make a confirmation of the response message and make an arrangement so as to provide 3 or more retries in case of no response error occurrence etc Note The above definiti...

Page 7: ...ytes 2 bytes Byte number Word number 2 2 Message transmission example The following show an example of reading the Setpoint Value 1000 from address No 1 controller Command message composition Address...

Page 8: ...controllers 1 Normal value The data value is transfer into Hexadecimal regardless of decimal For example 1000 will be transfered to 03E8 hex However such as output percentage and Pb proportional band...

Page 9: ...000F UNIT ENG English code 0010 DP 0000 000 0 00 00 0 000 English code 0011 ACT REV DIR English code 0012 LOLT 1999 9999 0013 HILT 1999 9999 0014 FILT 0 0 100 0 0015 A1FU None Hi Lo dif H dif L bd Hi...

Page 10: ...connection distance are as specified Whether communication conditions coincide between the master station host computer and slave station SE6000 Transmission speed 2400 bps 4800 bps 9600 bps 19200 bps...

Reviews: