Version 4.0
- 13 -
6.3 Write-in of Word Data (1 word) [Function Code: 06]
1. Message composition
Command message composition
Address
Function
Starting Address
Word Data
CRC-16
1 ~ FF
06
0xxx
0xxx
Low-order
byte
High-order
byte
1 byte
1 byte
2 bytes
2 bytes
2 bytes
Response message composition
Address
Function
Starting Address
Word Data
CRC-16
1 ~ FF
06
0xxx
0xxx
Low-order
byte
High-order
byte
1 byte
1 byte
2 bytes
2 bytes
2 bytes
2. Message transmission (example)
The following show an example of writing the Set point Value to address No.1
controller.
Command message composition
Address
Function
Starting Address
Word Data
CRC-16
01
06
0000
01F4
89DD
Response message composition
Address
Function
Starting Address
Word Data
CRC-16
01
06
0000
01F4
89DD