MDE-3116E Distribution Box PA0306 Installation Instructions · November 2015
Page 7
Overview
Each data loop has both current regulation and automatic isolation circuitry. The dispenser
data-loop drivers operate from an unregulated 12 VDC supply at 45 mA for Gilbarco
dispensers and CRIND devices, or 30 mA for other non-Gilbarco UL-listed dispensers
selected by jump jacks on board (for wiring connections, see
Notes: 1) Each distribution board must be dedicated for use with Gilbarco 45 mA dispensing
units, CRIND devices, or 30 mA for other non-Gilbarco UL-listed dispensers.
No mixing of differing current loop equipment on a distribution board is allowed.
2) Connect only one dispenser or CRIND to any one data-loop channel. The wiring
distance between the D-Box and dispensers is not to exceed 2600 feet (5200 feet of
total wire), and requires twisted-pair stranded 14 American Wire Gauge (AWG) wire.
Daisy chaining is not allowed with this unit. Shielded wire is not recommended for
dispensers.
Model Number Breakdown
shows the model number breakdown of the D-Box.
Figure 1: PA0306XXXX Model Number Breakdown
PA0306XXXX
Source Voltage: 1 - 230 VAC 50/60 Hz
0 - 115 VAC 50/60 Hz
Graphics/Housing: 0 - USA/Canada
1 - Europe
Data Input: 0 - Two-wire Input
Number of PCBs:
1 - 1 PCB (8 loops)
2 - 2 PCBs (16 loops)