35
Model: FSH
−
6
Operation & Filter Maintenance
4.03.3
E.A.C. Filter Status & Alarm
Two LED indicator light clusters on the control panel show the operational status of the
electronic air cleaner (EAC)
system
on each side of the hood.
[ON]
Indicates that the EAC collector cell is
installed, powered and operating.
When system is operating normally,
this is the
only
light ON.
[WASH]
This light turns ON to indicate:
• Filter cell is not installed or is mis
aligned.
• Collection fins contain an excessive amount of captured grease residue.
• There is poor connection between the filter cell contact plate & the hood contacts.
• Too many ionizer wires on cell are broken or missing.
When
[WASH]
light is ON, an alarm condition exists and air cleaning has stopped. After approximately
two (2) minutes, a beeping tone alarm will begin to sound and shortly thereafter, power to the cooking
appliances under the hood is shutdown.
IMPORTANT!
[WASH]
light is
NOT
intented to be a signal for routine cleaning of the cells,
DO NOT USE
AS SUCH
. Typically, the collection cells must be cleaned
DAILY
to ensure optimum air cleaning
performance. See
Section 4.04.2, EAC Filter Cell Cleaning
.
[CHECK]
This light turns ON to indicate:
• An ionizer wire is broken & shorting out against the cell frame.
• Cell is damaged & has shorted out to ground.
• Collection fins are shorted because of excessive moisture.
When
[CHECK]
light is ON
,
system is no longer operating to clean the air, even though the hood continues
to run and the cooking appliances are still receiving power.
DO NOT CONTINUE TO OPERATE HOOD
WHEN THIS CONDITION EXIST, DAMAGE TO SYSTEM CAN OCCUR ... DETERMINE THE CAUSE AND
CORRECT!
NOTE: If no LED
lights turn ON
when hood is started, the EAC power supply may be faulty ... call for service
.
The following actions may clear an EAC alarm condition:
1. Turn OFF hood
POWER
switch.
2. Remove the EAC collector cells and clean as described in
Section 4.04.2
.
3. Inspect cells for broken & missing ionizer wires, bent fins, or other damage. Ionizer wires are replaceable
(specify 20” when ordering replacements)
. Bent fins may be straightened gently by hand so that no fin is
touching an adjacent one. A cell with excessive damage (broken or badly bent frame, broken insulators, etc)
must be replaced.
4. Inspect cells for moisture on fins ... if present, allow cell to dry thoroughly before reinstalling.
5. Inspect the EAC contact plates inside hood compartment. Clean grease accumulation away with a mild
degreasing cleaner and dry thoroughly.
6. Replace collector cells
(
Section 4.02.7
)
and restart hood
(Section 4.01)
. If the condition persist, contact a
qualified service agent.
4.04
Filter Maintenance
The following sections explain the procedures for cleaning & maintaining ventless hood filters. Diligent adherence
to these procedures is essential for maintaining optimum and satisfactory Hood performance.
Summary of Contents for FSH-6
Page 2: ......
Page 4: ......
Page 26: ...16 Model FSH 6 Installation ...
Page 28: ...Model FSH 6 Overview 18 5 2 1 3 8 3 01 Control Panel 4 6 7 ...
Page 30: ...20 Model FSH 6 Overview 3 02 Filter Chamber Exhaust Not shown 2 7 8 1 5 3 4 9 9 6 ...
Page 34: ...24 Model FSH 6 Overview ...
Page 60: ...50 Model FSH 6 Parts List 7 03 Control Panel 7 5 6 8 10 4 3 2 9 1 Inside Panel Not Shown ...
Page 64: ...54 Model FSH 6 Parts List Not shown 4 5 2 1 3 1 3 6 7 05 Under Hood Components ...