5. Hood Cleaning & Maintenance
This section describes the steps to generally maintain and clean
FSH
‐
6 Hoods
. Attention to these procedures will
help ensure the Hood remains in satisfactory operating condition and continues to run efficiently and safely.
A
Maintenance & Service Log
is provided, see
Section 5.04
.
5.01
Monthly Hood Interlock Inspection (Can be Performed by User)
The hood design incorporates a series of interlock switches to ensure that the unit will shutdown when conditions exist
that are not consistent with safe and effective operation. These interlocks should be tested
MONTHLY
as described
below. Use the
Maintenance & Service Log
to record completion of the test. If problems are detected, contact
GILES
or an authorized service provider.
NOTE: Anytime a filter access door is opened and closed, the hood must be
restarted with the power switch
.
1.
Door Interlock Test:
Start hood ... with hood running, unlatch and slightly open each access door, one at a
time. When each side is opened, confirm that hood powers OFF
and cooking appliances under the hood
cannot be turned ON.
2.
Baffle Filter Test:
Remove the
baffle filter
from one side ... start hood. Verify that the red
[FILTER MISSING]
light turns ON. Check to ensure that cooking appliances under hood will not turn ON. Replace filter &
repeat the test on the other side. See
Sections 4.02.2 & 4.02.3, Removal & Installation
.
3.
Pre
Filter/Charcoal Filter Test:
Same procedure as
#2
except perform for each pre
filter and charcoal filter,
one at a time in succession
. Reinstall the filters. See
Sections 4.02.4, 4.02.5, 4.02.8 & 4.02.9, Removal &
Installation
.
3.
E.A.C. Filter Test:
Remove one of the EAC
collector cells, close & latch door ... start hood. Verify that
[WASH]
light on
EAC Status
comes ON for the side without cell. Wait approx. two (2) minutes. A beeping
alarm should begin sounding ... after a few seconds, check to ensure that cooking appliances under hood
cannot be turned ON. Turn off hood, reinstall cell, and repeat for other side. See
Section 4.02.6. & 4.02.7,
Removal & Installation
.
4.
Filter Clogged Test:
Perform this test ONLY after installing new prefilters & charcoal filters
.
Start hood
normally and allow to run. Use cardboard, or other suitable material, and completely block the hood
exhaust outlet ... hold firmly in place so that no air is escaping
.
Within a few seconds, a continuous tone
alarm should begin sounding. Check to ensure that cooking appliances under hood cannot be turned ON.
Remove the obstruction ... the alarm should silence and you should be able to turn ON cooking appliances
again.
Should any of the tests fail to yield the described results, contact a factory
authorized service company and have
the unit evaluated and repaired. A
Giles Manufacturer’s Representative
can provide information about nearby
authorized service providers, or call
GILES Services
at 800
554
4537
for assistance.
Summary of Contents for FSH-6
Page 2: ......
Page 4: ......
Page 26: ...16 Model FSH 6 Installation ...
Page 28: ...Model FSH 6 Overview 18 5 2 1 3 8 3 01 Control Panel 4 6 7 ...
Page 30: ...20 Model FSH 6 Overview 3 02 Filter Chamber Exhaust Not shown 2 7 8 1 5 3 4 9 9 6 ...
Page 34: ...24 Model FSH 6 Overview ...
Page 60: ...50 Model FSH 6 Parts List 7 03 Control Panel 7 5 6 8 10 4 3 2 9 1 Inside Panel Not Shown ...
Page 64: ...54 Model FSH 6 Parts List Not shown 4 5 2 1 3 1 3 6 7 05 Under Hood Components ...