background image

41

Model:  FSH

6

Hood Cleaning & Maintenance

5. Hood Cleaning & Maintenance

This section describes the steps to generally maintain and clean 

FSH

6 Hoods

.  Attention to these procedures will 

help ensure the Hood remains in satisfactory operating condition and continues to run efficiently and safely. 

Maintenance & Service Log

 is provided, see 

Section 5.04

.

5.01

Monthly Hood Interlock Inspection (Can be Performed by User)

The hood design incorporates a series of interlock switches to ensure that the unit will shutdown when conditions exist 
that are not consistent with safe and effective operation.  These interlocks should be tested 

MONTHLY

 as described 

below.  Use the 

Maintenance & Service Log

 to record completion of the test.  If problems are detected, contact 

GILES

 or an authorized service provider.

  

NOTE:  Anytime a filter access door is opened and closed, the hood must be 

restarted with the power switch

 

1.        

Door Interlock Test:  

Start hood ... with hood running, unlatch and slightly open each access door, one at a 

time.  When each side is opened, confirm that hood powers OFF

and cooking appliances under the hood 

cannot be turned ON. 

2.        

Baffle Filter Test:

  Remove the 

baffle filter

 from one side ... start hood.  Verify that the red 

[FILTER MISSING]

 

light turns ON.  Check to ensure that cooking appliances under hood will not turn ON.  Replace filter & 
repeat the test on the other side.  See 

Sections 4.02.2 & 4.02.3, Removal & Installation

3.        

Pre

­

Filter/Charcoal Filter Test:  

Same procedure as 

#2

 except perform for each pre

­

filter and charcoal filter, 

one at a time in succession

.  Reinstall the filters.  See

 

Sections 4.02.4, 4.02.5, 4.02.8 & 4.02.9, Removal & 

Installation

3.        

E.A.C. Filter Test:

  Remove one of the EAC

collector cells, close & latch door ... start hood.  Verify that 

[WASH]

 light on 

EAC Status

 comes ON for the side without cell.  Wait approx. two (2) minutes.  A beeping 

alarm should begin sounding ... after a few seconds, check to ensure that cooking appliances under hood 
cannot be turned ON.  Turn off hood, reinstall cell, and repeat for other side.  See 

Section 4.02.6. & 4.02.7, 

Removal & Installation

4.        

Filter Clogged Test:

  

Perform this test ONLY after installing new prefilters & charcoal filters

 Start hood 

normally and allow to run.  Use cardboard, or other suitable material, and completely block the hood 
exhaust outlet ... hold firmly in place so that no air is escaping

.

  Within a few seconds, a continuous tone 

alarm should begin sounding.  Check to ensure that cooking appliances under hood cannot be turned ON.  
Remove the obstruction ... the alarm should silence and you should be able to turn ON cooking appliances 
again. 

Should any of the tests fail to yield the described results, contact a factory

­

authorized service company and have 

the unit evaluated and repaired.  A 

Giles Manufacturer’s Representative

 can provide information about nearby 

authorized service providers, or call 

GILES Services

 at 800

­

554

­

4537

 for assistance.

Summary of Contents for FSH-6

Page 1: ...d Committed to Quality 2750 Gunter Park Drive West Montgomery AL 36109 USA Toll Free 800 554 4537 USA Canada Only Other 334 272 1457 Fax 334 239 4117 Website www gfse com Email services gfse com Printed in USA Form 64898 Rel Date Jul 1999 Rev Date Jul 2022 Rev M ...

Page 2: ......

Page 3: ...is requested Giles will dispatch factory authorized service representatives to inspect repair recondition or replace units of its manufacture with such labor being rendered without cost to owner for twenty four 24 months from the date of installation Otherwise service including labor and transportation charges or other expenses in connection with the removal or installation of any part or parts su...

Page 4: ......

Page 5: ...ven Limitations 8 2 04 4 Oven Clearances 8 2 04 5 Griddle Limitations 9 2 04 6 Griddle Clearances 9 2 04 7 Range Constraints 10 2 04 8 Range Clearances 10 2 05 Electrical Specifications Hood Only 11 2 05 1 Electrical Connections 11 2 05 2 Routing Power Conduit Wiring 12 2 05 3 Hood and Appliance Interlock Diagram 12 2 06 Fire Suppression System Installation 13 2 06 1 Fire Suppression System Connec...

Page 6: ...ront Panel Stand 56 4 Operation Filter Maintenance 25 4 01 Starting the Hood 25 4 02 Filter System Filter Maintenance Filter Alarms 25 4 02 1 Ventless Hood Filter Table 25 4 02 2 Baffle Filter Removal 26 4 02 3 Baffle Filter Installation 27 4 02 4 Pre Filter Removal 28 4 02 5 Pre Filter Installation 29 4 02 6 E A C Filter Cell Removal 30 4 02 7 E A C Filter Cell Installation 31 4 02 8 Charcoal Fil...

Page 7: ...tive harm For more information go to www p65warnings ca gov Indicates an imminently hazardous situation which if not avoided will result in serious personal injury even death Indicates a potentially hazardous situation which if not avoided could result in serious injury even death Indicates a potentially hazardous situation which if not avoided may result in minor to moderate injury This notificat...

Page 8: ...or or highly unsatisfactory hood performance DO NOT use ventless recirculating hoods with gas fired cooking appliances due to a high potential for inhalation hazards from carbon monoxide build up in the operating space Hood is approved ONLY for use with electrically heated appliances Consult a qualified electrical contractor or kitchen equipment specialist to ensure that installation will comply w...

Page 9: ...ot pans utensils or foods Failure to comply with CAUTION notices may result in minor to moderate personal injury damage to equipment or property and potentially void the warranty Some components and controls are impact sensitive To avoid damage and maintain proper operation exercise due care when working near the hood Handle the electronic air cleaner E A C collector cell carefully DO NOT bend the...

Page 10: ...uild up GILES recommends using a mild biodegradable non toxic degreasing cleaner such as Simple Green Crystal Foaming Spray Cleaner Degreaser GILES assumes no responsibility with regard to code compliance during installation or the use of ventless recirculating ventilation equipment The customer shall be responsible for obtaining all of the necessary approvals from Authorities Having Jurisdiction ...

Page 11: ...ing performance missing filters or mis aligned filters Filter Cleaning Timer built in reminder system to alert associates when it is time the clean E A C collector cells and check the condition of all other filters Timely and routine cleaning of collection cells is essential to maintaining optimum air cleaning performance Filters 2 Baffle Filters capture remove largest grease particulate 2 Pre Fil...

Page 12: ...2 Model FSH 6 Introduction INCHES mm 1 04 Specifications 1 04 1 Overall Dimensions Code Dimension A 72 9 16 1843 B 68 7 16 1738 C 73 3 4 1873 D 72 1829 E 117 3 16 2977 ...

Page 13: ...3 Model FSH 6 Introduction Hood Crated Weight Uncrated Weight approx FSH 6 Stand 925 lbs 420 kg 725 lbs 329 kg 1 04 2 Agency Certifications 1 04 3 Weights ...

Page 14: ...the hood are all within the hood s listing limitations as outlined in Section 2 04 C The installation site complies with the specific requirements and limitations outlined in the GFSE Recirculating Ventless Hood Approval Letter HAL The HAL is available for review or download at www gfse com under the SUPPORT tab on the VENTLESS DOCUMENTS page To ensure satisfactory hood performance after installat...

Page 15: ... stretch film In most cases a wooden framework is built around the unit for added protection Unpack as follows 1 Position pallet in an area that provides adequate space for unpacking 2 Remove the stretch film strapping and other packaging materials as necessary 3 Carefully remove the hood stand sides back panels trim pieces appliance channels from the pallet using suitable equipment sufficient man...

Page 16: ... or when moving the assembled hood stand into a final position The assembly is very heavy and will be extremely top heavy Install upper back panel TRIM CAP ADJUST LEGS TO LEVEL HOOD ANCHOR LEGS TO FLOOR AS REQUIRED BY LOCAL CODE TRIM CAP TABS ON CHANNELS SHOULD FIT INTO SLOTS ALONG BOTTOM EDGE OF STAND SIDES ...

Page 17: ...rances 0 w Floor Stand 33 844 0 min 42 1066 8 max 117 3 16 2976 56 72 Stand MIN CEILING HEIGHT 0 w Floor Stand IMPORTANT The following clearance diagrams in this section depict ceiling suspended hoods over various appliances Ceiling mounting is no longer an acceptable installation method The side clearance minimum dimensions shown in these illustrations will not apply for the free standing hood ve...

Page 18: ... Hood Max Temp Max kW Input Total FSH 6 500 55 kW Inches mm 2 04 3 Oven Limitations Electrically Heated Appliances ONLY 2 04 4 Oven Clearances 68 max 1727 2 Floor Stand 42 1066 8 max 117 3 16 2976 56 72 Stand MIN CEILING HEIGHT ...

Page 19: ...60 x 26 Inches mm 2 04 5 Griddle Limitations Electrically Heated Appliances ONLY 2 04 6 Griddle Clearances 33 838 2 MIN 42 1066 8 MAX 0 w Floor Stand 0 w Floor Stand 117 3 16 2976 56 72 Stand MIN CEILING HEIGHT Side to side overhang clearances DO NOT apply for the floor stand installation ...

Page 20: ...2 04 7 Range Limitations Electrically Heated Appliances ONLY 2 04 8 Range Clearances Inches mm 0 w Floor Stand 0 w Floor Stand 33 838 2 MIN 42 1066 8 MAX 5 MIN 381 117 3 16 2976 56 72 Stand MIN CEILING HEIGHT Side to side overhang clearances DO NOT apply for the floor stand installation ...

Page 21: ... of sufficient rating for the hood and appliance load Improper installation adjustment alteration service or maintenance could result in serious injury or possible death equipment or property damage and could void the warranty 1 Install appropriate circuit breaker in main electrical panel see Section 2 05 Electrical Specifications 2 As required by code route suitable sized flexible conduit from ma...

Page 22: ...nder Hood appliances Once properly connected cooking appliances should not receive service power unless hood is running properly 2 05 3 Hood Appliance Interlock Diagram IMPORTANT Failure to interlock cooking appliances with the hood such that appliances are not powered unless the hood is operating is not compliant with the hood s UL listing and may also be in violation of local building fire and h...

Page 23: ...zles must be installed and in place at all times 3 A manual activation station for the fire system NOT included shall be installed in a conspicuous location in the path of egress exit from the area The pull station must be clearly marked and easily accessible 4 The regulated release mechanism with a 3 gal suppressant storage tank shall be the mechanical type Ansul Automan 79290 5 Installation oper...

Page 24: ...ot supplied w hood Nozzles centered over cooking surface s 2 06 2 Fire Suppression Detector Links Location 2 06 3 Appliance Nozzles 165 F Ansul 56811 165 F Ansul 56811 Fire Damper 285 F Factory installed 165 F Ansul 56811 All fusible detector links shall be supplied installed by an authorized Ansul technician ...

Page 25: ...uisher Nozzle Locations Appliance nozzle 2 minimum sized installed by authorized Ansul service technician Customer supplied Plenum Nozzle 1 2N flow Factory installed Plenum Nozzle 1 2N flow Factory installed Plenum Nozzle 1W flow Factory installed ...

Page 26: ...16 Model FSH 6 Installation ...

Page 27: ...ef overview of the hood s components functions and accessories Please review carefully before proceeding Left Filter Chamber Section 3 02 3 Overview Right Filter Chamber Section 3 02 Hood Stand Hood Exhaust Duct w Fire Damper Control Panel Section 3 01 ...

Page 28: ...Model FSH 6 Overview 18 5 2 1 3 8 3 01 Control Panel 4 6 7 ...

Page 29: ...ppliances remain powered but air leaning system is not functioning DO NOT continue operation check system determine cause 4 CLOGGED FILTER Light Turns ON if a filter baffle pre filter or charcoal filter is excessively dirty and restricting airflow through hood Other obstructions such as blocked exhaust may also be present A constant steady alarm will sound 5 FILTER MISSING Light Turns ON to indica...

Page 30: ...20 Model FSH 6 Overview 3 02 Filter Chamber Exhaust Not shown 2 7 8 1 5 3 4 9 9 6 ...

Page 31: ...coal Filter 2 Single use disposable filters that help to control cooking aromas in exhausted air Filters must be replaced periodically NEVER attempt to clean and re use charcoal filters Typically replace with fresh NEW filters every 30 to 45 days Replacement cycle is dependent on appliances in use cooking activity and type of foods being cooked NO FILTER WILL COMPLETELY REMOVE COOKING ODORS 6 Hood...

Page 32: ...gest grease particulate in cooking vapors Pre Filter 2 P N 91707 Removes additional grease laden vapor and moisture from the air Single use only disposable must be replaced E A C Filter Cell P N 20521 Left Side P N 20520 Right Side Captures fine grease particulates and some smoke contaminant from the air Sustainable must be cleaned DAILY ...

Page 33: ...ot remove odor completely 2 Sample Cans Foaming Crystal Cleaner Degreaser P N 41510 12 count Case NSF approved GILES recommended collector cell cleaner Spray on foaming degreaser for cleaning EAC collector cells Cleaner is readily available from Giles and on line distributors as well as many nationwide retail outlets 3 03 Accessory Items Included w Hood continued ...

Page 34: ...24 Model FSH 6 Overview ...

Page 35: ...the hood The hood will NOT power up if either access door is open or ajar 4 Operation Filter Maintenance 4 01 Starting the Hood 4 5 4 02 Filter System Maintenance Alarms 4 02 1 Ventless Hood Filter Table Filter When to Clean Replace How to Remove How to Clean How to Install Baffle Filter Clean daily Section 4 02 2 Section 4 04 1 Section 4 02 3 Pre Filter Replace every 7 to 10 days Section 4 02 4 D...

Page 36: ...26 Model FSH 6 Operation Filter Maintenance 4 02 2 Baffle Filter Removal Turn OFF power Baffle filters are located on under side of hood directly above the appliances ...

Page 37: ...27 Model FSH 6 Operation Filter Maintenance Switch arm must be actuated by the filter as shown Front View 4 02 3 Baffle Filter Installation Position filters w baffles in the vertical position ...

Page 38: ... Model FSH 6 Operation Filter Maintenance Door open Front View 4 02 4 Pre Filter Removal Pre Filters Turn OFF power Pre filters are located inside the filter chamber in the outermost position on each side ...

Page 39: ...changed always record the installation date of the new filter in the space provided on the label 4 02 5 Pre Filter Installation Metal mesh side facing toward middle Pre Filter Paper side to outside Paper side to outside Roller on switch must be actuated by the filter frame when installed Close Door ...

Page 40: ...nce Folding handle use this handle to avoid damaging cell Left E A C Cell Right E A C Cell Door open 4 02 6 E A C Collector Cell Removal Turn OFF power Collector cells are located inside the filter chamber in the middle position on each side ...

Page 41: ... damaging cell IMPORTANT Collector cells are side specific Always take care when installing to avoid improper positioning Contact plates of both cells must be positioned toward top of hood when inserted and airflow arrows must point toward the hood center If cell does not engage the alignment pin and slide fully into the hood it is NOT positioned properly Contact strips on cell must make good conn...

Page 42: ...FSH 6 Operation Filter Maintenance Charcoal Filter Door open Front View 4 02 8 Charcoal Filter Removal Turn OFF power Charcoal filters are located inside the filter chamber in the innermost position on each side ...

Page 43: ... 6 Operation Filter Maintenance 4 02 9 Charcoal Filter Installation Door open Close Door Front View Charcoal Filter Blue fiber fill side faces middle Roller on switch must be actuated by filter frame when installed ...

Page 44: ...ing A clogged filter alarm will occur if airflow through hood is reduced to a level that is below the minimum required for effective capture of cooking vapors The red PRE FILTER CHARCOAL OR BAFFLE FILTER CLOGGED light turns ON a constant tone audible alarm will sound power to cooking appliances under the hood is turned OFF until the condition is corrected This alarm is most commonly caused by clog...

Page 45: ...horted because of excessive moisture When CHECK light is ON system is no longer operating to clean the air even though the hood continues to run and the cooking appliances are still receiving power DO NOT CONTINUE TO OPERATE HOOD WHEN THIS CONDITION EXIST DAMAGE TO SYSTEM CAN OCCUR DETERMINE THE CAUSE AND CORRECT NOTE If no LED lights turn ON when hood is started the EAC power supply may be faulty...

Page 46: ... lead to system malfunction and result in an interruption of power to cooking appliances under the hood Two 2 different cleaning methods are endorsed by GILES Food Service as follows Preferred Spray foam method using Simple Green Crystal Foaming Spray Cleaner Degreaser an exceptionally effective foaming spray cleaner It is readily available as well as being safe for use on aluminum NSF approved fo...

Page 47: ...ng that both sides of all collector fins are completely covered with foam 3 Allow foam to soak for 5 to 10 minutes In cases of extreme build up a second application may be required after rinsing 4 Carefully move cells to sink and rinse thoroughly using hot water spray Rinse ONLY DO NOT scrub with brushes 5 Stand cells upright on end on a drain board w contact plate up allow to drain and air dry ov...

Page 48: ...olution sufficient to completely cover the cell hold it by the contact plate frame or handle and carefully place it into the solution Be sure that it is fully submerged add water if needed 4 Allow cell to soak for approximately 20 minutes no more than 30 mins then lift it slightly and briefly agitate it in the solution to help dislodge grease residue 5 Carefully remove cell from container and foll...

Page 49: ...ithin the allowed time the timer enters TIMEOUT mode the red indicator light turns ON and an audible alarm sounds to signal that allowed time between cleanings has expired The alarm condition will continue until cleaning activities are performed or the SNOOZE button is pressed see 3 below Placing the hood POWER switch in the OFF position will silence the alarm but it will sound again hood will not...

Page 50: ...nsumable items which must be replaced periodically see Sections 4 02 8 4 02 9 These CANNOT be cleaned and reused Typical replacement cycle is every 30 to 40 days depending on usage Use GILES replacement Item No 32056 Write the replacement date on new filter IMPORTANT Failure to use Giles OEM parts and OEM replacement filters may void the factory warranty 4 03 5 Charcoal Filter Maintenance ...

Page 51: ...he test on the other side See Sections 4 02 2 4 02 3 Removal Installation 3 Pre Filter Charcoal Filter Test Same procedure as 2 except perform for each pre filter and charcoal filter one at a time in succession Reinstall the filters See Sections 4 02 4 4 02 5 4 02 8 4 02 9 Removal Installation 3 E A C Filter Test Remove one of the EAC collector cells close latch door start hood Verify that WASH li...

Page 52: ...ay cleaner To maintain effectiveness and performance the hood must be deep cleaned at a minimum every 3 months 1 Disconnect power from the unit at circuit breaker panel 2 If possible unplug and remove cooking appliances from underneath hood 3 Remove all filters 4 Use a soft cloth or sponge and a mild bio degradable degreasing cleaner Simple Green Crystal Foaming Spray Degreaser Cleaner is recommen...

Page 53: ... at all pulleys detectors replace cable if necessary Record maintenance date service performed in a permanent record sign off attach tag to system in a conspicuous location Inspection service for the fire suppression system must be performed by a technician from a qualified Ansul Distributor Dealer As a minimum field inspection of the system must be conducted semi annually every 6 months and shall...

Page 54: ... 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 Check Initial Date 1 Door Check Section 5 01 2 Baffle Filter Check Section 5 01 3 EAC Filter Check Section 5 01 4 P...

Page 55: ...nect to proper electrical supply e Not properly connected to power source Confirm connections correct f Blown fuse or tripped circuit breaker Check main electrical panel FILTER MISSING light ON start up a Baffle pre filter or charcoal filters not installed or not properly seated Install filters and or check filter positioning inside hood EAC WASH light ON start up beeping alarm tone sounding a Exc...

Page 56: ...lades are loaded with grease build up Check voltage and inspect blower clean if needed Cooking appliances will not power up Hood running FILTER MISSING light OFF WASH light ON Beeping tone alarm sounding a Excessive grease film built up on collector fins too dirty Clean the EAC cell Section 4 04 2 b EAC cell is not installed Install clean EAC cell c EAC driver board is faulty Test replace EAC powe...

Page 57: ...del Serial Number Voltage Phase UNITED STATES CANADA call 800 554 4537 ALL OTHERS call 334 272 1457 Normal business hours are 8 00 AM to 5 00 PM Central Time calls are handled by an automated answering system Please follow the recorded message to route your call appropriately If necessary after hours leave a voicemail message and a service representative should respond within 30 minutes Website ww...

Page 58: ...48 Model FSH 6 Parts List 7 7 02 Component Drawer 4 10 1 2 5 8 9 6 17 12 13 18 3 11 14 15 16 19 ...

Page 59: ...ER BOARD 8 23782 1 SONALERT 250V CONTINUOUS TONE 9 21659 1 SONALERT 120V INTERMITTENT BEEP TONE 10 21337 1 TRANSFORMER 230VAC TO 115VAC COMES w MOUNTING HARDWARE 11 98592 1 BRACKET VACUUM SWITCH 12 21203 1 RELAY SPST NO NC 240VAC 13 21512 1 DISTRIBUTION BLOCK 12 PL PTFIX 12 26 AWG ORANGE 14 21509 1 DISTRIBUTION BLOCK 12 PL PTFIX 12 26 AWG RED 15 21510 1 DISTRIBUTION BLOCK 12 PL PTFIX 12 26 AWG BLA...

Page 60: ...50 Model FSH 6 Parts List 7 03 Control Panel 7 5 6 8 10 4 3 2 9 1 Inside Panel Not Shown ...

Page 61: ...ICATOR LIGHT AMBER 250V 0 5W 4 20420 2 INDICATOR LIGHT RED 250V 0 5W 5 20694 1 PILOT LIGHT YELLOW EAC TIMER 6 20693 1 PILOT LIGHT RED EAC TIMER 7 24209 2 LED EAC STATUS INDICATOR 8 21441 2 SWITCH ROCKER ON 0N OFF 250V 20A 9 30833 2 BRACKET LED CLUSTER 10 20692 1 SWITCH MOMENTARY PUSH BUTTON EACTMR 7 03 Parts List for Control Panel Inside Panel Not Shown ...

Page 62: ...52 Model FSH 6 Parts List Not Shown 7 04 Hood Filter Chamber 6 2 9 1 4 8 7 2 1 3 4 5 5 7 7 7 8 10 11 12 13 ...

Page 63: ...SEMBLY 5 21157 2 SWITCH LIMIT 15A 250V BROWN BODY 6 20520 1 FILTER EAC 12 X 20 RIGHT SIDE ONLY 7 23200 4 SWITCH SNAP ACTION ROLLER 8 21125 2 EAC CONTACT BOARD 9 34616 1 DUAL BLOWER ASSEMBLY 10 91522 1 BOX POWER CONNECTION FSH HOOD 11 90550 1 DIN RAIL TERMINAL BLOCK 4 12 20319 5 TERMINAL BLOCK 24 8 AWG 600V 50A 13 20320 2 TERMINAL BLOCK GROUND 24 8 AWG 7 04 Parts List for Hood Filter Chamber Not Sh...

Page 64: ...54 Model FSH 6 Parts List Not shown 4 5 2 1 3 1 3 6 7 05 Under Hood Components ...

Page 65: ...T NO QTY DESCRIPTION 1 42300 2 BAFFLE FILTER S S 20 X 20 2 32776 1 DRIP CUP 3 32102 2 BAFFLE FILTER SWITCH ASSY 4 40625 2 LIGHT FIXTURE 5 20395 2 FLUORESCENT BULB COATED 6 98104 2 CONDUIT COVER 7 05 Parts List for Under Hood Components ...

Page 66: ...56 Model FSH 6 Parts List Not shown 7 05 Doors Front Panel 11 9 8 10 7 4 2 1 3 6 5 8 12 NOTE Legs are welded in place cannot be replaced 13 ...

Page 67: ... 98142 1 SCREEN FIRE DAMPER 6 98037 1 ACCESS DOOR ASSY RIGHT 7 91945 1 SKIRT FSH 6 8 UNIVERSAL 8 91583 2 72 HOOD STAND SIDE 9 91938 1 72 HOOD STAND TOP BACK PANEL FSH 6 10 91940 1 72 HOOD STAND BOTTOM BACK PANEL FSH 6 11 92063 2 CHANNEL APPLIANCE POSITIONING FSH 6 12 91708 2 CHANNEL FRONT TRIM HOOD STAND 72 13 90844 1 ACCESS COVER VACUUM SWITCH 7 05 Parts List for Doors Front Panel ...

Page 68: ...2750 Gunter Park Drive West Montgomery Al 36109 USA Phone 334 272 1457 Toll Free 800 554 4537 USA Canada Only FAX 334 239 4117 www gfse com Form No 64898 Rel Date Jul 1999 Rev Date Jul 2022 Rev M ...

Reviews: