background image

GIRA

 

Info

 

 

Instabus

 Continuous Controller 

Installation Instructions 

 

 

Powernet Continuous Controller 

19/99 

Page: 3 of 3 

Specifications 

Supply 

Instabus EIB: 

 

24 V DC (+6/-4 V) through bus coupler (BC) 

 
Power consumption 
 

Instabus EIB: 

 

150 mW max. 

 
Connection 

Instabus: 

 

 

Connecting and branch terminal 

User interface: 

 

to be plugged onto BC (2 x 5-pole edge connector) 

 
Basic stage control: 

Alternative continuous (PI control) or switching control signal  

 

(PWM or two-position control) 

 
Additional stage control: 

Alternative continuous (P control) or switching control signal  

 

(PWM or two-position control) 

 
Measuring range: 

 

0 to 40 °C 

Atmospheric humidity:   

0 to 95 % (no condensation) 

Resolution: 

  ± 

0.08 

 
Set value 
Comfort temperature:   

adjustabe from 7 to 40°C 

Set value shift:   

 

± 10 K max., continuous 

 
Ambient temperature:   

-5 °C to +45 °C 

Storage temperature:   

-25 °C to +70 °C 

 
Protective system: 

 

IP 20 

Protection class: 

 

III 

 