GIRA
Info
Instabus
Continuous Controller
Installation Instructions
Powernet Continuous Controller
19/99
Page: 3 of 3
Specifications
Supply
Instabus EIB:
24 V DC (+6/-4 V) through bus coupler (BC)
Power consumption
Instabus EIB:
150 mW max.
Connection
Instabus:
Connecting and branch terminal
User interface:
to be plugged onto BC (2 x 5-pole edge connector)
Basic stage control:
Alternative continuous (PI control) or switching control signal
(PWM or two-position control)
Additional stage control:
Alternative continuous (P control) or switching control signal
(PWM or two-position control)
Measuring range:
0 to 40 °C
Atmospheric humidity:
0 to 95 % (no condensation)
Resolution:
±
0.08
K
Set value
Comfort temperature:
adjustabe from 7 to 40°C
Set value shift:
± 10 K max., continuous
Ambient temperature:
-5 °C to +45 °C
Storage temperature:
-25 °C to +70 °C
Protective system:
IP 20
Protection class:
III
Acceptance of guarantee
We accept the guarantee in accordance with the corresponding legal provisions.
Please return the unit postage paid to our central service department giving a brief description
of the fault:
Gira
Giersiepen GmbH & Co. KG
Service Center
Dahlienstrasse 12
D-42477 Radevormwald
The CE sign is a free trade sign addressed exclusively to the authorities and does not include
any warranty of any properties.
Gira
Giersiepen GmbH & Co. KG
Postfach 1220
D-42461 Radevormwald
Telefon: +49 / 21 95 / 602 - 0
Telefax: +49 / 21 95 / 602 - 339
Internet: www.gira.de