Configuration in the ETS
Order No. 2089 00
Page 25
7.5.3. Parameter page Data logger
The parameter page Data logger is only visible when the data logger is activated on the parameter
page General.
7.5.4. Notifications
According to the number of notifications selected above, you can now specify the DP types and other
parameters for the respective notification (notification no. 1 = group object 101, notification no. 2 =
group object 102…).
Parameters
Entry / Selection
Remarks
Format
This parameter determines which format the data
should be logged in on the microSD card.
ETS4/ETS5
The data is stored in an ETS4-compliant format
(.xml) which is also readable by the ETS5.
ETS3
The data is stored in an ETS3-compliant format
(.trx).
Memory type
cyclic buffer
static buffer
This parameter specifies how the microSD card
memory is to be used.
Memory status type
Only visible when "Memory type" is set to "static
buffer". This parameter specifies what type the sta
-
tus object of the card occupancy level should be.
binary
A 1-bit object is used.
The value "1" means that the microSD card is full,
"0" means that there is still space on the microSD
card for logging
value (0-255)
A 1-byte object is used. The value range is between
0 – 255. The value "255" corresponds to a card
occupancy level of 100%.
Parameters
Entry / Selection
Remarks
Data type
Bool (1 bit, DPT 1.001)
Percent (1 byte, DPT
5.001) Counter (1 byte,
DPT 5.010) Floating
point (2 bytes, DPT 9.*)
Text (14 bytes, DPT
16.001)
You can select the required data type of the respec
-
tive notification.
Notification only in case
of value change
Checkbox
(inactive)
Threshold
0-1000
Specification as an inte
-
ger
Suppress notifications.
Only send a notification again once the threshold
value is exceeded.
The threshold value is the deviation from the last
value (as an absolute number) that a notification
generated.
0: not a threshold value. You will receive a notifica
-
tion for each change.