Retrofitting the earth connection for the flush-mounted box of the
Gira/Pro-face ServerClient 15
Mounting and electrical connection
The flush-mounted box for the ServerClient 15 has no earth connection and is therefore
not suitable for connection of a Control 19 with 230 V. An earthing set is included for ret-
rofitting this flush-mounted box.
Secure both earthing wires to the earthing connection of the Control 19 (Fig. 1).
Drill two
2.5 mm holes into the rear wall of the flush-mounted box (Fig. 2).
Fasten both earthing wires to the flush-mounted box (Fig. 3).
Connect the 230 V AC mains connection cable to the 230 V AC connection (17) of the
Control 19.
Connect the network cable to the terminal (21) of the Control 19.
Mount the Control 19 in the flush-mounted box (Fig. 4). Use the included screws for
this.
Insert the design frame into the intended mounts and carefully pull down.
DANGER!
Electric shock if live parts are touched.
Electric shock may lead to death.
Isolate all appropriate circuit breakers before working on the device.
Cover up live parts in the vicinity!
1
2 x 2,5 mm
2
3
230 V AC
LAN
4