The device should be used in an air-tight appliance box. Otherwise temperature and hu-
midity reading can be negatively influenced by draughts.

Mount supporting frame (h) in the right orientation on an appliance box.

Note the TOP marking.

Use the enclosed box screws (k).

Pull off start-up rockers from push-button sensor.

The push-button sensor is delivered with start-up rockers. The operating rockers suitable
for the push-button sensor must be ordered separately (see accessories).

Connect push-button sensor (j) to the KNX (g) using KNX connecting terminal (red = +,
black = -).

Optional: Connect remote sensor (see accessories) to device connection terminal (d).

Attach push-button sensor (j) onto the supporting frame (h).

Screw push-button sensor (j) with the integrated locking screws (e) onto supporting frame.
Connection torque max. 0.8 Nm.

Optional: Cover up the locking screws (e) with the labels supplied with the rocker set (only
for the 2-gang and 4-gang device variants).
Push-button sensor can be put into operation.

Programming the physical address before operating rockers mounting.

Snap on the operating rockers (a).
Device is ready for operation.

7.2 Commissioning

Programming the physical address and application program

Project design and commissioning with ETS from 5.6 onwards.

The programming button (i) is located under the topmost operating rocker.
Precondition: The device is connected and ready for operation.
The topmost operating rocker is dismantled.

Activating Programming mode: push the programming button (i).
The status LED 1 and 2 flash red. Programming mode is activated.

Programming the physical address.
The status LED 1 and 2 return to their previous state. Physical address is programmed.

Programming the application program.

All status LEDs are switched off while the application program is programmed. As soon as
the programming is successfully completed, the status LEDs carry out their parameterised
function.

When the application program is discharged and the bus voltage is connected, all status
LEDs initially light up white. Whenever a button is actuated, the respective illuminated
status LED changes colour in (white → red → green → blue → yellow → cyan → orange → vi-
olet → white → ...).

8

Technical data

KNX
KNX medium

TP256

4 / 6

32401902

10866576

16.10.2019