Domestic Type I (SLI9, SLI14, SLI23 Only)

!

!

!

!

A = 6-inches (15.24 cm)

 B = 24-inches (60.96 cm)

EXAMPLE: For SLI23, 2 unrestricted openings measuring
6-inches by 24-inches (15.24 cm by 60.96 cm) are acceptable.

If a closet door is installed: unobstructed air openings are
required.  The air openings shall be located 3-inches
(7.62 cm) from the lower opening (above floor level) and upper
opening (below ceiling).  The total free area of the air openings
in the door shall not be less than 130 inch

2

 (838.708 cm

2

) for

SLI9; 179 inch

2

 (1154.836 cm

2

) for SLI14; and 293 inch

2

(1890.319 cm

2

) for SLI23.  Louvered doors with equivalent

air openings are acceptable.

No other fuel-burning appliance shall be installed in the same
closet as the dryer.

Fresh Air Supply Requirements _______

When the dryer is operating, it draws in room air, heats it,
passes this air through the tumbler, and exhausts it out of the
building.  Therefore, the room air must be continually
replenished from the outdoors.  If the make-up air is
inadequate, drying time and drying efficiency will be adversely
affected.  Ignition problems and sail switch “fluttering”
problems may result, as well as premature motor failure from
overheating.  The dryer must be installed with provisions for
adequate combustion and make-up air supply.

Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer.  As a general
rule, an unrestricted air entrance from the outdoors of 110
inch

2

 (710 cm

2

) is required for each SLI34, 90 inch

2

 (580 cm

2

)

for each SLI23, 55 inch

2

 (354 cm

2

) for each SLI14, and 40

inch

2

 (258 cm

2

) for each SLI9.  (Based on 1 inch

2

 [6.5 cm

2

] per

1,000 Btu [252 kcal].)

It is not necessary to have a separate make-up air opening
for each dryer.  Common make-up air openings are
acceptable.  However, they must be set up in such a manner
that the make-up air is distributed equally to all the dryers.

To compensate for the use of registers or louvers used over
the openings, this area must be increased by approximately
33%.  Make-up air openings should not be located in an area
directly near where exhaust vents exit the building.

Allowances must be made for remote or constricting
passageways or where dryers are located at high altitudes
or predominantly low pressure areas.

Note

Component failure due to dry cleaning solvent
fumes will void the warranty.

A = 10-inches (25.4 cm)

 B = 11-inches (27.94 cm)

EXAMPLE: For a bank of 4 SLI14 dryers, 2 unrestricted
openings measuring 10-inches by 11-inches (25.4 cm by
27.94 cm) are acceptable.

Important

Make-up air must be free of dry cleaning solvent
fumes.  Make-up air that is contaminated by dry

cleaning solvent fumes will result in irreparable damage to
the motors and other dryer components.

Exhaust Requirements ________________

Exhaust ductwork should be designed and installed by a
qualified professional.  Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, and shutdown of the burner by the
airflow (sail) switch, burner hi-limits, or lint chamber hi-limit
protector thermostat.  The dryer must be installed with a proper
exhaust duct connection to the outside.

The dryer shall not be exhausted into any gas vent, chimney,
wall, ceiling or concealed space of a building.

Caution

This dryer produces combustible lint and must be
exhausted to the outdoors.

Improperly sized or installed exhaust ductwork can create
a potential fire hazard.

The ductwork should be laid out in such a way that the
ductwork travels as directly as possible to the outdoors with
as few turns as possible.  There should be a minimum
6-inch (15.24 cm) clearance between the back guard and the
first bend in the ductwork for ease of servicing.  Single or
independent dryer venting is recommended.  It is suggested
that the use of 90° turns be avoided; use 30° and/or 45°
bends instead.  The radius of the elbows should preferably
be 1-1/2 times the diameter of the duct.  All ductwork should
be smooth inside with no projections from sheet metal
screws or other obstructions, which will collect lint.  When
adding ducts, overlap the duct being connected.  All ductwork
joints must be taped to prevent moisture and lint from
escaping into the building.  Back draft dampers must be
installed in all commonly ducted systems.  Inspection doors
should be installed at strategic points in the exhaust ductwork
for periodic inspection and cleaning of lint from the ductwork.

Important

It is recommended that exhaust or booster fans
not be used in the exhaust ductwork system.

Summary of Contents for SLI14

Page 1: ...SEMENT Assurez vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d al...

Page 2: ..._____________________________________________________________________ SERIAL NUMBER S ______________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ Replacement parts c...

Page 3: ...ircuit s ever be disabled The dryer must never be operated with any of the back guards outer tops or service panels removed Personal injury or fire could result The dryer must never be operated without the lint filter screen in place even if an external lint collection system is used FOR YOUR SAFETY Do not dry mop heads in the dryer Do not use dryer in the presence of dry cleaning fumes The dryers...

Page 4: ...ber and also may be a fire hazard A program should be established for the inspection and cleaning of lint in the burner area exhaust ductwork and area around the back of the dryer The frequency of inspection and cleaning can best be determined from experience at each location Do not operate steam dryers with more than 150 psi 10 34 bar steam pressure Excessive steam pressure can damage the steam c...

Page 5: ...____________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________...

Page 6: ...T 265 lb 120 20 kg AIRFLOW 230 cfm 6 51 cmm EXHAUST CONNECTION DIAMETER 4 10 16 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A OVEN SIZE kW Btu hr kcal hr 4 1 13 843 3 488 5 0 17 065 4 300 5 4 18 430 4 644 5 6 19 112 4 816 6 1 20 819 5 246 6 5 22 184 5 590 6 8 23 208 5 848 7 4 25 255 6 364 7 5 25 597 6 450 8 1 27 644 6 966 VOLTAGE AVAILABLE 120 240v 1ø 2w 50 60 Hz APPROXIMATE NET WEIGH...

Page 7: ...113432 1 girbau girbau es 7 SLI9 Specifications _________________________________________________________________ ...

Page 8: ...XIMATE SHIPPING WEIGHT 310 lb 140 61 kg AIRFLOW 360 cfm 10 19 cmm EXHAUST CONNECTION DIAMETER 6 15 24 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A OVEN SIZE kW Btu hr kcal hr 7 9 26 962 6 794 8 3 28 327 7 138 9 0 30 716 7 740 11 3 38 566 9 719 12 4 42 320 10 665 12 5 42 661 10 751 13 5 46 074 11 611 VOLTAGE AVAILABLE 120 240v 1ø 2w 50 60 Hz APPROXIMATE NET WEIGHT 305 lb 138 35 kg APP...

Page 9: ...113432 1 girbau girbau es 9 SLI14 Specifications ________________________________________________________________ ...

Page 10: ... INPUT 90 000 Btu hr 22 680 kcal hr EXHAUST CONNECTION DIAMETER 8 20 32 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION 1 2 M N P T 1 2 F B S P T CE ONLY VOLTAGE AVAILABLE 200 416v 1 3ø 3 4w 50 60 Hz APPROXIMATE NET WEIGHT 545 lb 247 21 kg APPROXIMATE SHIPPING WEIGHT 565 lb 256 28 kg AIRFLOW 525 cfm 14 87 cmm EXHAUST CONNECTION DIAMETER 8 20 32 cm COMPRESSED AIR CO...

Page 11: ...113432 1 girbau girbau es 11 SLI23 Specifications ________________________________________________________________ ...

Page 12: ...272 16 kg APPROXIMATE SHIPPING WEIGHT 620 lb 281 23 kg AIRFLOW 560 cfm 15 86 cmm EXHAUST CONNECTION DIAMETER 8 20 32 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A OVEN SIZE kW Btu hr kcal hr 18 4 62 763 15 816 20 2 68 975 17 382 20 3 69 418 17 493 20 4 69 521 17 519 22 0 75 084 18 921 VOLTAGE AVAILABLE 120 240V 1ø 2 3w 50 60 Hz APPROXIMATE NET WEIGHT 600 lb 272 16 kg APPROXIMATE SHIPP...

Page 13: ...113432 1 girbau girbau es 13 SLI34 Specifications ________________________________________________________________ ...

Page 14: ...is manual refer to Exhaust Requirements section Important The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be installed with adequate clearance for air openings into the combustion chamber Caution This dryer produces combustible lint and must be exhausted to the outdoors Every 6 months inspect the exhaust ducting and remove any lint buildup Imp...

Page 15: ...ricting passageways or where dryers are located at high altitudes or predominantly low pressure areas Note Component failure due to dry cleaning solvent fumes will void the warranty A 10 inches 25 4 cm B 11 inches 27 94 cm EXAMPLE For a bank of 4 SLI14 dryers 2 unrestricted openings measuring 10 inches by 11 inches 25 4 cm by 27 94 cm are acceptable Important Make up air must be free of dry cleani...

Page 16: ...iance category in accordance with national installation regulations of the country of destination Outside Ductwork Protection To protect the outside end of the horizontal ductwork from the weather a 90 elbow bent downward should be installed where the exhaust exits the building If the ductwork travels vertically up through the roof it should be protected from the weather by using a 180 turn to poi...

Page 17: ...cordance with electric codes for making all service connections Note The use of aluminum wire will void the warranty An individual ground circuit must be provided to each dryer do not daisy chain Component failure due to improper voltage application will void the warranty The manufacturer reserves the right to make changes in specifications at any time without notice or obligation Important A sepa...

Page 18: ... 6 20 220 1ø 2 8 4 20 230 1ø 2 8 5 20 SLI34 Gas 120 1ø 2 15 6 20 200 1ø 2 10 5 20 208 1ø 2 10 5 20 220 1ø 2 10 0 20 240 1ø 2 9 7 20 220 1ø 2 10 7 20 230 1ø 2 10 8 20 SLI34 Steam 120 1ø 2 14 4 20 200 1ø 2 8 2 20 208 1ø 2 8 2 20 220 1ø 2 7 8 20 240 1ø 2 7 6 20 220 1ø 2 8 4 20 230 1ø 2 8 5 20 1 25 06 ELECTRICAL SERVICE SPECIFICATIONS IMPORTANT NOTES A B C 208 VAC AND 230 240 VAC ARE NOT THE SAME When...

Page 19: ...l wire size must conform to rating of dryer or the dryer can be hard wired directly to the service breaker panel In both cases a strain relief must be installed where the wiring enters the dryer For CE Models Only The means for disconnection from the supply must be incorporated into wiring having a minimum contact separation of 3 0mm in all poles Single Phase 1ø Wiring Connections Hookup The elect...

Page 20: ...dryer must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure test of the gas supply system at test pressures equal to or less than 1 2 psig 3 5 kPa for non CE dryers or 50 mb for CE dryers Warning Fire or explosion could result due to failure of isolating or disconnecting the gas supply as noted Note Undersized gas piping will result i...

Page 21: ...al I2E 1 000 20 40 000 11 72 1 133 M3 H 38 2 578 1 830 25 40 000 11 72 1 365 M3 H 38 2 578 1 Butane I3 3 175 28 30 40 000 11 72 0 845 kg H 52 1 613 1 Propane I3 2 500 37 40 000 11 72 0 845 kg H 52 1 613 1 Butane I3B P 3 175 28 30 50 40 000 11 72 0 845 kg H 49 1 854 1 18 0 Propane I3P 2 500 28 30 50 40 000 11 72 0 845 kg H 49 1 854 1 23 0 Natural I2H I2E 1 000 20 55 000 16 12 1 557 M3 H 22 3 988 1 ...

Page 22: ... ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___...

Page 23: ...sconnect the union 3 electrical plugs and the gas train mounting screws from the burner Carefully slide the gas train out of the gas train enclosure The carbon ignitor located at the far end of the gas train is very fragile Remove 2 burner tube mounting screws and remove burner tube in order to gain access to the orifice Using a 3 8 wrench or socket remove the existing orifice and replace it with ...

Page 24: ...crew under vent cap Remove spring under screw and replace with spring from kit P N 140415 Replace regulator adjustment screw Install the gas train back into the dryer gas train enclosure Be sure the tab at the rear of the gas train engages into the mounting slot Connect the union and the 3 electrical plugs Open all shutoff valves reconnect electrical power to the dryer and test for leaks Operate t...

Page 25: ...eter Tighten screw inside the pressure tap or install plug Turn gas cock to ON position and check for leaks with soap solution with main burner ON Steam Information ____________________ It is your responsibility to have all plumbing connections made by a qualified professional to ensure that the steam plumbing installation is adequate and conforms with local state and country regulations or codes ...

Page 26: ... the steam supply header causing the condensate in the line to drain to the header Install a bypass trap in any low point to eliminate wet steam Operating Steam Pressure Model Maximum Heat Input Normal Load Consumption Approx 125 psi 8 6 bar Inlet Return SLI9 150 psig 1 0 MPa 1 2 Bhp 45 lb hr 20 41 kg hr 1 2 1 2 SLI14 150 psig 1 0 MPa 1 75 Bhp 63 lb hr 28 58 kg hr 1 2 1 2 SLI23 150 psig 1 0 MPa 3 ...

Page 27: ...mbler drum by hand to be sure it moves freely Check bolts nuts screws terminals and fittings for tightness and security Check that the vent is connected to the dryer and is exhausted to the outdoors STEAM MODELS Check to ensure all steam shutoff valves are open Preoperational Test ___________________ All dryers are thoroughly tested and inspected before leaving the factory However a preoperational...

Page 28: ... Cycle begins at the end of the heat cycle the L E D display will read COOL DOWN TEMP ___ ___ MINUTES remaining At the end of the heat cycle the dryer will shut off the heat and continue the fan and tumbler until the Cool Down Time or temperature is reached Shutdown Instructions ________________ If the dryer is to be shutdown taken out of service for a period of time the following must be performe...

Page 29: ... lint accumulation from lint chamber thermostat and microprocessor temperature sensor area Warning To avoid the hazard of electrical shock discontinue electrical supply to the dryer Steam Dryers Clean the steam coil fins It is suggested that compressed air and a vacuum cleaner with brush attachment be used Warning When cleaning steam coil fins be careful not to bend the fins If fins are bent strai...

Page 30: ...electric or steam 2 Serial Number Allows the manufacturer to gather information on your particular dryer 3 Type of Heat This describes the type of heat for your particular dryer gas either natural gas or L P gas electric or steam 4 Heat Input For Gas Dryers This describes the heat input in British thermal units per hour Btu hr or kilowatts kW 5 Orifice Size For Gas Dryers Gives the number drill si...

Page 31: ..._____________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ______...

Page 32: ...Part No 113432 1 01 25 06 0 ...

Reviews: