Page 5
c
ONDENSING
c
OMBI BOILE
r
6.0
ELEcTrIcAL WIrING
6.1 GENErAL
The boiler must be permanently connected to a 30V~, 50Hz supply and it MUST
BE EARTHED.
In GB: All external wiring to the boiler must be in accordance with the latest I.E.E.
Wiring Regulation, and any local regulations which may apply.
In IE: Reference should be made to the current addition of the ETCI rules.
There must be only one common isolator for the boiler and its control system, and
it must provide complete electrical isolation via a double pole isolator with 3mm
contact separation in both poles and fused at 5A maximum.. The fused spur box
should be readily accessible and located within 1 metre of the appliance and it
should be identified as to its use.
Alternatively the connection can be made through an un-switched shuttered socket
and 5A fused 3-pin plug both to the current issue of BS 1363, provided they are
not used in a room containing a bath or shower.
In the event of an electrical fault after installation of the appliance, preliminary
electrical checks must be carried out i.e. Earth Continuity, Short Circuit, Polarity,
and Resistance to Earth.
Figure 6.1
Mains supply and
room thermostat
cable route
Control panel cover
& wiring diagram