Installation
15
6.2.2
Coolant plumbing
The chiller must not be installed more than 65 feet above the heat exchangers and cryro compressor. The chiller
pumps can deliver up to 165 feet of head. The heat exchangers and cryro compressor are rated at 230 feet
maximum. If the chiller is mounted more than 65 feet above the heat exchangers and cryro compressor, the
maximum allowable pressure on the heat exchangers and cryro compressor may be exceeded. Consult the
factory for installations requiring the chiller to be installed more than 65 feet above the Heat Exchanger. The
maximum equivalent linear feet of
2”
piping which may be installed external to the chiller is 500ft.
Table 5: Standard Fitting Losses in Equivalent Feet of Pipe
Fitting Description
Feet of loss
2
”
90° Standard Elbow
5.0
2
”
90° Street Elbow
8.2
2
”
45° Standard Elbow
2.6
2
”
45° Street Elbow
4.5
2
”
Globe Valve
55.0
2
”
Gate Valve
2.3
2
”
Angle Valve
24.0
The chiller has the following plumbing connections:
Table 6: Chiller Plumbing Connections
Connection Description
Connection Type
Supply
2” Female NPT
Return
2”
Female NPT
NOTICE
Exceeding recommended plumbing lengths can increase system pressure beyond
the capabilities of the pumps and can cause the pumps to supply less than the
required flow rate for proper operation. Consult the factory if recommended
lengths are to be exceeded.
NOTICE
Do not allow the fluid pumps to run dry. This will damage the pump seals and
will not be covered under warranty.
To install connecting plumbing between the chiller and process:
1.
Remove all caps at each plumbing port on the chiller.
2.
Pipe installation should adhere to ASME B1.20.1 for best practices.
3.
Ensure that all plumbing is routed in an orderly fashion and free of kinks.
4.
Fully open all valves (if present) on plumbing lines.
Summary of Contents for Koolant Koolers WO2-2-10000
Page 1: ...Original Instructions 800 968 5665 dimplexthermal com User Manual...
Page 17: ...Installation 11 Figure 7 Removal or Doors Blockers 3 8 DOOR BOLT 3 8 BLOCKER BOLT BLOCKER DOOR...
Page 18: ...Installation 12 Figure 8 Removal of Lower Doors LATCHES...
Page 28: ...Operation 22 Figure 10 Controller Restart Warning Figure 11 Controller Home Page...
Page 30: ...Operation 24 Figure 15 Controller On Off Menu Figure 16 Controller Pump Enable Disable Menu...
Page 31: ...Operation 25 Figure 17 Controller Setpoint Menu Figure 18 Controller Alarm Menu...
Page 37: ...Internal Components 31 Figure 20 Door Side PUMP 2 PUMP 1 FLOAT SWITCH...
Page 44: ...Appendix A Plumbing 38 Appendix A Plumbing...
Page 45: ...Appendix B Pump Curve 39 Appendix B Pump Curve...
Page 46: ...Appendix C Refrigeration WO2 2 5000 40 Appendix C Refrigeration WO2 2 5000...
Page 47: ...Appendix C Refrigeration WO2 2 7500 41 WO2 2 7500...
Page 48: ...Appendix C Refrigeration WO2 2 10000 42 WO2 2 10000...