Instruction Manual ZS100T, ZS150T & ZS200T Series II (MAM-870) Senator Industrial Air Compressors
12
will be necessary to guide the air entry of compressor to a place with clean air or to
install pre-filtration equipment.
d.
The compressor should be placed in a horizontal position on solid and flat ground to
avoid vibration occurring to the compressor due to poor ground condition. The use
of flexible vibration isolators underneath the mounting feet is highly recommended
and will reduce noise emissions.
2.3 Electrical Safety Requirements
a.
The 3-phase mains power supply voltage should be stabilized to 415 V. A separate
supply circuit is recommended for the compressor to avoid motor current overload
due to excessive voltage drop or unbalanced 3-phase caused by other electrical
equipment operating in parallel.
b.
The power supply cable diameter should be properly selected in accordance with
local regulations. Do not use an undersized cable.
c.
Make sure that the connected power supply is consistent with the rated voltage of
the motor of compressor.
d.
According to the power of the compressor, the necessary short circuit protection and
other safety devices such as breaker switch, etc. should be installed in front of the
lead-in power supply cable of the compressor.
e.
It is essential to connect the compressor to a secure grounding (earthing) line,
preventing the hazards due to electricity leakage. Do not connect the compressor’s
earth wire to the compressed air pipeline.