Instruction Manual M A M - 8 7 0
Senator Industrial Air Compressors
7
PARAMETER
SET VALUE
FUNCTION
AIR FILTER RST
0000 H
Reset time for air filter changing. Do not
reset unless the filter is replaced.
LUBE RESET
0000 H
Reset time for lubricating oil changing.
Do not reset unless the oil is replaced.
GREASE RESET
0000 H
Reset time for lubricating grease changing.
Do not reset unless the grease is replaced.
BELT RESET
0000 H
Reset time for belt changing.
Do not reset unless the belt is replaced.
OIL FILTER SET
1000 H
Set this value to “0” to disable the oil filter
alarm function.
O-A FILTER SET
2000 H
Set this value to “0” to disable the O-A
separator alarm function.
AIR FILTER SET
2000 H
Set this value to “0” to disable the air filter
alarm function.
LUBE SET
2000 H
Set this value to “0” to disable the
lubricating oil alarm function.
GREASE SET
0000 H
Set this value to “0” to disable the
lubricating grease alarm function.
BELT SET
0000 H
Set this value to “0” to disable the belt
alarm function.
LANGUAGE SEL.
ENGLISH
Set this value to the required display
language.
USER PASSWORD
9999
For access to the User Set Parameters.
2.3 Factory Set Parameters
The factory set parameters can be reviewed in a similar manner to that described above
for the user set parameters. However, they cannot be changed without the FACTORY
SET PASSWORD, which is only made available upon request. It is unlikely that any
of the factory set parameters would need to be changed during the life of the air
compressor set.
The factory set parameters have been pre-programmed in accordance with the following
table.
Note that any parameter marked “#” can only be accessed with the FACTORY SET
PASSWORD and the SUPER PASSWORD.
PARAMETER
SET VALUE
FUNCTION
MOTOR CURR
014.3 A [ZS100T]
021.1 A [ZS150T]
028.8 A [ZS200T]
After the starting delay time, when the main motor
current is greater than 1.2 times the set value and
less than 4 times the set value, the unit will
shutdown per overload feature.
FAN CURR
000.5 A [ZS100T]
001.2 A [ZS150T]
001.2 A [ZS200T]
After the starting delay time, when the fan motor
current is greater than 1.2 times the set value and
less than 4 times the set value, the unit will
shutdown per overload feature.