Uninterruptible Power Supply (UPS)
UPS Figure A
UPS Figure B
UPS Problem
Diagnostics
The On Battery light (light #2
– UPS Figure
B) on the front of the UPS is yellow. The
UPS sounds four beeps every 30 seconds.
The backup UPS is running on battery and powering equipment
connected to the battery backup outlets.
Consider saving work in progress in the event the unit shuts
down.
UPS sounds a continuous beeping.
The backup UPS battery has reached a low battery condition,
and battery run-time is very low.
1. Promptly save work in progress and exit all open
applications.
2. Shutdown the OS, computer and UPS.
3. Replace the battery.
The Overload light (light #3
– UPS Figure B)
on the front of the UPS is red.
The power demand has exceeded the capacity of the UPS.
UPS sounds a continuous tone.
Battery backup outlets are overloaded.
Circuit breaker button located on the rear
panel of the UPS extends out.
An overload forced the UPS to disconnect from the AC power.
1. Disconnect non-essential equipment.
2. Reset the circuit breaker by pressing the circuit breaker
button back in place.
The Replace Battery light (light #4
– UPS
Figure B) is red. The battery chirps for one
minute every five hours.
Battery has failed its automated diagnostic test. The battery is
near the end of its useful life, or the battery is not connected.
A battery near the end of its useful life has insufficient run time.
Replace the battery.