background image

5

g.)

Make  sure  that  the  drain  line  has  not been

dislodged  or  broken  during  shipping  and  that  the

drain  trap  terminates  properly  in  the  condensate

pan or floor drain. (

See Condensate Pan on Top

Mounted Compressor.

)

h.)

Listen for any unusual noise such as lines vibrating,

fan  blades  hitting  etc.  Correct  problem  by

tightening screws, slightly bending tubing, etc.

i.)

Check proper tension on doors. (See

Door Closer

Adjustment

.)

Thermostat Settings

The  refrigerator  or  freezer  is  shipped  from  the  factory

with a thermostat setting of approximately the mid-point

of the operating range. Final thermostat setting must be

made in the field. Allow the cabinet to operate until the

compressor cycles on the thermostat.

The  normal  operating  temperature  ranges  are:  42°F  to

36°F for Refrigerator models;

20°F to -20°F for Display freezers;

0°F to -20°F for Storage freezers;

0°F to -30°F (or-40°)F for Hardening freezers;

The thermostat is easily adjusted with a standard screw-

driver.  In  models  where  the  thermostat  has  control

settings  1  through  7,  turn  the  thermostat  to  a  higher

number  to  lower  the  cabinet  temperature.  See  the

section  Electronic  Control  for  thermostat  adjustment  on

units so equipped.

NOTE:  DO  NOT  OPERATE  MEDUIM  TEMPERATURE

CABINETS (REFRIGERATORS) BELOW 32°F

Door Adjustment & Removal

Glass doors use an internal torsion rod to adjust closing

tension; solid doors use a cam in the hinges to control

closing.

Door Closer Adjustment

( Glass Doors)

Loosen Nut "A" and turn the square shaft to increase or

decrease  the  torsion  rod  tension  to  the  desired torque.

Turn  the  square  shaft  towards  door  handle  to  increase

torque; then tighten

Nut

"A" to lock.

The  door  should  be  set  to  swing  smoothly  and  should

not slam. Also the door should self-close when opened

only a couple. of inches

Removing Outer Doors

(Solid Doors)

If the assembled cabinet is too wide to move through narrow
doorways, the cabinet doors can be removed as follows:

1  )Open  the  door  180°and  support  the  outer  edge.

Remove the screws in the upper hinge at the cabinet,

leaving  the  hinge attached  to  the  door.  Lift  and

remove from lower hinge  pin.  CAUTION: The upper

hinge cam is under significant spring tension. Leave

the  hinge  in  the  open  position  (KEEP  HANDS

CLEAR)

2) After legs are on and the cabinet is in final position,

set the doors back on the hinge pins.

Energy Conservation Measures

These  cabinets  are  designed  for  efficiency  with  heavy

foam insulation. However, there are things that the user

can do to maintain the cabinet in operating condition.

1) Do not operate the cabinet any colder than necessary

to maintain safe, product storage temperatures.

2) Make sure the cabinet is located to prevent direct

exposure to sunlight, air ducts, etc.

3) Keep  the  doors  closed  except  for  normal  use.  Inspect

the doors often to see that they self-close and that the

4) Do not overstock the product in the cabinet which will

block normal air flow.

5)

Keep the condenser coil clean. The coils should be

inspected at least twice a year.

6) Have at least annual inspections by a qualified service

company  to  see  that  the  fan  motors  are  functioning
properly and that the refrigerant charge is correct.

7) These  cabinets  operate  more  efficiently  in  a  cooler

ambient  than  in  a  "hot  ambient.  Try  to  maintain  an

ambient  below  80°F  (27°C)  and  65%  RI-I.  for  maxi-

mum efficiency.

ROUTINE MAINTENANCE
Cleaning the Interior

Wash the inside surface of the storage one tablespoon

of  baking  soda  per  quart  of  water.)  Rinse  thoroughly

with  clean,  warm  water  and  wipe  dry.  The  procedure

can also be used for cleaning the door gasket. Be sure

the power is turned off before cleaning.

Cleaning the Exterior

Wipe  the  cabinet  exterior  occasionally  with  a  cloth

damp-ened in mild detergent water, rinse and wipe dry

with  a  soft  cloth.  Do  not  use  abrasive  or  caustic

cleaners or scouring pads.

Cleaning the Condenser

Clean the condenser periodically by brushing the coil with
a  soft  brush  and/or  using  a  vacuum  cleaner  with  a  brush
attachment. Be sure that the power is disconnected

Summary of Contents for T30HSP

Page 1: ...ss door Merchandisers T30MGP T50MGP T80MGP Low Temperature Storage Cabinets T30LSP T50LSP T80LSP Ice Cream Hardening Cabinets T30HSP T50HSQL T50HSQHP T50HSP IMPORTANT THE REFERENCE INFORMATION FOR THE...

Page 2: ...STANCE For Customer Service or Technical Assistance please call our manufacturing facility toll free number 1 888 650 9799 or 1 864 260 6600 Our Customer Service Representative and Engineers are willi...

Page 3: ...nches between the back of the cabinet and wall for proper air circulation through the condensing unit Installing the Cabinet Models with Top Mounted Compressors Whenever possible leave the crate skid...

Page 4: ...e removable without the use of a tool At the time of initial installation all shelf bracket screws should be loosened with a tool and re tightened hand tight Floor sealing of cabinets without legs or...

Page 5: ...be removed as follows 1 Open the door 180 and support the outer edge Remove the screws in the upper hinge at the cabinet leaving the hinge attached to the door Lift and remove from lower hinge pin CAU...

Page 6: ...The heating element used to vaporize the water in the pan can get quite hot After unplugging the unit allow 10 minutes for it to cool prior to removing the pan The pan is located on the bottom of the...

Page 7: ...r a failure to close the door fully To initiate a defrost manually press and hold the lower button for 4 seconds Note For all units with top mounted compressors the thermostat is located directly on t...

Page 8: ...tactor and the compressor will run As the temperature falls to the set point the control will de energize the compressor relay After 8 hours of operation or other interval specified in param d03 the u...

Page 9: ...efrigeration system capacity low due to Professional service required provide service defective component or refrigerant charge agent with unit s model serial no at time of service request Compressor...

Page 10: ...n irregular surface Level or support unit silicon seal base to floor Unit Noisy Service level problems Refrigerant flood Request professional service back fan blade contact incidental component contac...

Reviews: