11. After tightening the hanger nut onto the exposed connector, disconnect and remove the rod.

12. 

If applicable; use silicon tape to thoroughly wrap and seal the hanger connector sealing bolt (fig. 

4.5). For hanger connector sealing bolts equiped with an o-ring or gasket, silicone tape is not 

needed.

13. If applicable; insert the sealing bolt into the open connector, ensure it is properly seated and tighten it.  

Do NOT over-tighten (fig. 4.6).

14. Fill 2 bar (30 psi) of precharge air or nitrogen and using a soap solution check for leaks all around 

the air valve, pressure gauge, top nut and bottom flange.

15. Lift tank upright and attach to pressure system as described earlier in this manual.

16. Open gate valve and allow some water into tank and then pump more air/nitrogen to set tank to 

appropriate precharge as described in section 1.3.

17. Now open isolation gate valve to allow full functionality of tank.

Note: For tanks with a flange instead of a hanger on top of the tank, first mount the membrane to 

the top flange.

5. Disposal

Check with local authorities for proper disposal and recycling. Do not dispose of the manual - keep 

it for further reference.

6. Warranty

Global Water Solutions Ltd. (GWS) warrants its SuperFlow™ tanks 

for a period of 1 years from the date of manufacture for manufacturing defects on the steel shell. 

Warranty applies to GWS products only when used for their intended purpose, and does not 

apply if a defect is due to improper use of the product, result of accident, misuse, or abuse. If the 

product was improperly installed or altered in any way, not specifically authorized by the factory, 

the warranty is void. The warranty set forth in this paragraph is made expressly in lieu of all other 

warranties expressed, or implied, including but not limited to merchantability or fitness for a 

particular purpose.

For replacement of the membrane, provided the tank is installed by an authorized installer and 

pre-charge is set properly as per instruction manual and the pre-charge is checked as per the same 

manual at a time interval of every 3 months, warranty is granted for a period of 3 months from date 

of manufacture on membrane defects.

In no event shall GWS be liable for cost of processing, lost profits, goodwill or any other 

consequential or incidental damage of any kind resulting from the order or use of its products 

whether arriving from breach of warranty, nonconformity to ordered specifications, delay in delivery, 

or any loss sustained by the buyer nor will GWS be liable for labor and expenses necessary to 

remove and reinstall replacement product.

To obtain service under this warranty, consumer must deliver alleged defective product, freight 

prepaid, to an authorized GWS distributor or OEM partner. GWS will either issue credit or at its 

option, repair or replace defective product freight prepaid to the distributor. GWS reserves the right 

to make changes in construction, which, in its judgment, constitutes a product improvement.

All warranty is subject to verifiable proper installation, adjustment of pre-charge as per our 

engineering bulletins and installation of a pressure relief valve as recommended in the installation 

manual.

Standard manufacturer’s warranty as defined in the standard GWS warranty terms and conditions.

2.4 Solar Heating System 

Connections

SuperFlow™ tanks can be used in the solar 

liquid loop of indirect thermal transfer systems 

and may be mounted either on the suction 

or pressure side of the circulation pump. 

If a condenser is employed to cool 

evaporated solar liquid it must be in the 

location between the solar liquid loop and 

the expansion tank.  A relief valve should 

be employed and maximum operating 

parameters must not be exceeded.  If the 

temperature of the solar system has the 

potential to rise above the evaporation point 

of the solar liquid, a condenser chamber or 

coil is required between the solar collector 

and the expansion tank (See Fig. 2.4).

2.5 Thermal Expansion Operating Principles

As water is heated it expands. A thermal expansion tank is used to accommodate for this natural 

water expansion, which otherwise may lead to increased system pressure and cause damage to piping, 

fittings  and  other  system  components. A  thermal  expansion  tank  uses  a  membrane  sealed  inside 

the vessel to create a barrier between water and air chambers. The air chamber acts as a cushion 

which compresses as heated water expands. The thermal expansion tank absorbs the expanded water 

volume and ensures constant system pressure is maintained. Using a thermal expansion tank also 

conserves water and energy. This is accomplished by eliminating the need to refill and reheat water 

lost due to venting from the relief valve during heating cycles.

3. Maintenance

SuperFlow™ pressure tanks should be checked by an authorized service professional, every 3 months. 

To check precharge, shut off power to the pump, isolate and drain the tank. Check precharge using a 

pressure gauge. If needed, top up air to appropriate precharge level using an air pump or compressor. 

Open isolation gate valve allowing the pump to fill the tank with water.

Always release all water and air from tank before disassembling the parts exposed to pressure such 

as flanges, air valve, pressure gauge etc. Make sure that the system is switched off and no electricity 

or electrical devices are running.

If the pump short cycles or the heating system relief valve constantly opens, check the air valve 

mounted on the tank. If water bleeds from the valve the membrane has burst. Please call an authorized 

service provider to replace the membrane with a factory replacement, following the instructions for 

membrane replacement in this manual.

Check the quality of the water by draining water from the tank using the drain valve. If the water is 

rusted, calcified, or has solid deposits, then either the membrane has failed which can be verified by 

above mentioned process or the tank is blocked.

4. Membrane Replacement Instructions

1.  Turn off the water and/or disconnect the power to the pump.

2.  Release the air and drain all water from tank.

3. 

Unbolt and remove the flange (water connection) from the tank.

4.  Remove the nut and the washer on the top of the tank which is attached to the membrane hanger 

that is anchoring the top of the membrane (fig. 4.1, fig. 4.4).

5. 

Pull and remove the membrane through the bottom opening to which the flange was attached.

6.  Remove the top connection membrane hanger from the damaged membrane, this can be reused 

and should be cleaned.

7. 

Take the membrane hanger and attach it to a rod, a cable or alike, as seen in fig. 4.2.

8.  Pull the rod and hanger up through the membrane until the top of the hanger is protruding from 

the top of the membrane (fig. 4.3).

9.  Feed the rod from the bottom of the tank up through the opening at the top of the tank until the 

hanger is protruding from the top of the tank and the threads are visible.

10. Slip the washer and then the hanger nut over the end of the rod/cable and tighten onto the 

exposed connector (fig. 4.4).

Hot

Cold

Pump

Pump

Solar Collector

Condenser
Solar

Tank

Storag

e

Tank

Heat

Exchanger

Fig. 2.4

Fig. 4.2

rod

cable

Fig. 4.3

membrane

rod or cable

Fig. 4.5

hanger connector 

sealing bolt

silicone tape

Fig. 4.6

hanger connector

sealing bolt

washer

hanger nut

Fig. 4.4

rod or cable

hanger nut

washer

tank

membrane hanger

Fig. 4.1

EC declaration of conformity

We,  Global  Water  Solutions  Ltd.,  declare  under 

our  sole  responsibility  that  the  pressure  vessels 

types

  MCPA / MCMA / MCUA

,  to  which  this 

declaration relates, are in conformity with these 

Council  directives  on  the  approximation  of  the 

laws of the EC member states:

The products are diaphragm tanks. All products are examined under these conditions:

Type

Maximum 

Pressure [bar]

Volume 

[litres]

Category Used

Design 

Standard

MCPA-10

10

50-3000

II, III, IV

EN13831

MCMA-16

16

50-3000

II, III, IV

EN13831

MCUA-25

25

50-3000

II, III, IV

EN13831

Fluid group: 2   

Certificate Number: CE-0062-PED-B3.1-GWS 001-17-CHN-rev-A

Notified body: CE 0062  - Bureau Veritas

 

Newtime  - 52 Boulevard du Parc - Ile de la Jatte, 92200 Neuilly sur Seine, France

Manufacturer: Global Water Solutions China Manufacturing Co.,Ltd.

 

No. 69 Shaohai Road, Hongdao Economic Zone, Qingdao, Shandong Province, China

Konformitätserklärung

Wir,  Global  Water  Solutions  Ltd.  erklären  in 

alleiniger Verantwortung, dass die Druckbehälter 

Typ

  MCPA / MCMA / MCUA

,  auf  die  sich  diese 

Erklärung  bezieht,  mit  den  folgenden  Richtlinien 

des Rates zur Angleichung der Rechtsvorschriften 

der EU-Mitgliedsstaaten übereinstimmen:

Dichiarazione di Conformità

Global Water Solutions Ltd. dichiara sotto la sua 

esclusiva  responsabilità  che  i  vasi  di  espansione 

tipo

  MCPA / MCMA / MCUA

,  ai  quali  si  riferisce 

questa  dichiarazione,  sono  conformi  alle 

seguenti  direttive  del  Consiglio  riguardanti  il 

riavvicinamento  delle  legislazioni  degli  Stati 

membri CE:

Declaração de Conformidade

Global  Water  Solutions  Ltd.  declaramos  sob 

nossa única responsabilidade que os tanques de 

pressão type

 MCPA / MCMA / MCUA

, aos quais diz 

respeito esta declaração, estão em conformidade 

com  as  seguintes  Directivas  do  Conselho  sobre 

a  aproximação  das  legislações  dos  Estados 

Membros da CE:

Försäkran om överensstämmelse

Vi,  Global  Water  Solutions  Ltd.  försäkrar 

härmed  att  tryckkärl  av  typen

  MCPA / MCMA 

/ MCUA

,  som  omfattas  av  denna  försäkran,  är 

i  överensstämmelse  med  rådets  direktiv  om 

inbördes  närmande  till  EU-medlemsstaternas 

lagstiftning, avseende:

Overensstemmelseserklæring

Vi,  Global  Water  Solutions  Ltd.  erklærer  under 

ansvar,  at  trykbeholdere  type

  MCPA / MCMA 

/ MCUA,

  som  denne  erklæring  omhandler, 

er  i  overensstemmelse  med  disse  af  Rådets 

direktiver  om  indbyrdes  tilnærmelse  til  EF-

medlemsstaternes lovgivning:

Déclaration de Conformité

Nous,  Global  Water  Solutions  Ltd.,  déclarons 

sous  notre  seule  responsabilité,  que  les  vases 

d’expansion  type

  MCPA / MCMA / MCUA, 

auxquels  se  réfère  cette  déclaration,  sont 

conformes  aux  Directives  du  Conseil  concernant 

le  rapprochement  des  législations  des  Etats 

membres  CE  relatives  aux  normes  énoncées  ci-

dessous :

Declaración de Conformidad

Nosotros, Global Water Solutions Ltd. declaramos 

bajo  nuestra  única  responsabilidad  que  los 

tanques a presión type

 MCPA / MCMA / MCUA, 

a  los  cuales  se  refiere  esta  declaración,  están 

conformes  con  las  Directivas  del  Consejo  en 

la  aproximación  de  las  leyes  de  las  Estados 

Miembros del EM:

Декларация Соответствия

Мы,  компания  Global  Water  Solutions  Ltd., 

полностью  несем  ответственность  за  то,  что 

сосудов  под  давлением  типов

  MCPA / MCMA 

/ MCUA

,  к  которым  относится  настоящая 

декларация, 

соответствуют 

следующим 

Директивам Совета Евросоюза об унификации 

законодательных  предписаний  стран-членов 

ЕС:

Vastaavuusvakuutus

Me, 

Global  Water  Solutions  Ltd.  vakuutamme, 

että  valmistamamme  paineastiat  type

  MCPA / 

MCMA / MCUA

,  joita  tämä  vakuutus  koskee, 

ovat 

EY:n 

jäsenvaltioiden 

lainsäädännön 

yhdenmukaistamiseen  tähtäävien  Euroopan 

neuvoston  direktiivien  vaatimusten  mukaisia 

seuraavasti:

DECLARATION OF CONFORMITY

Pressure Vessels Types MCPA / MCMA / MCUA

Alexander Staudt

Technical Manager

Luxembourg, November16

th

, 2017

Global Water Solutions Ltd.

5th floor, 37 Esplanade

St. Helier – JE1 2TR

Jersey

The Channel Islands

PED 2014/68/EU