background image

APRIL  2019 REV.A

GFS-302

PAGE    2  of  4       

DESIGN CRITERIA

The Globe Residential Pendent Sprinkler Series GL-RES is

 

cULus Listed for installation in accordance with this data 

sheet as well as the applicable installation Standard being 

utilized.

Globe Residential Sprinkler Installation Guide

When conditions exist that are outside the scope of the pro

-

vided criteria, refer to the Globe Residential Sprinkler Instal-

lation  Guide  (Document  GFS-380)  for  recommendations 

that may be acceptable to the authority having jurisdiction.

Hydraulic Design (NFPA 13D and 13R)

For systems designed to NFPA 13D or NFPA 13R, the min

-

imum required sprinkler flow rate is given in Table A for the 

coverage areas shown. The sprinkler flow rate is the min

-

imum required discharge from each of the total number of 

“design sprinklers” as specified in NFPA 13D or NFPA 13R.

Hydraulic Design (NFPA 13)

The minimum required discharge from each design area 

sprinkler shall be the greater of the following:
 (1) 

In accordance with minimum flow rates indicated in 

TABLE A.

 (2)  In rooms or compartments greater than 800 ft

2

  

(74.3 m

2

), calculated based on delivering a minimum 

of 0.1 gpm/ft

2

 (4.1 mm/min) over the coverage area of 

each sprinkler, calculated in accordance with the 

S x L Rules for density area sprinklers.

 (3)  In rooms or compartments 800 ft

2

 (74.3 m

2

) or less 

(Defined as “Small Rooms”) calculated based on

 de-

livering a minimum of 0.1 gpm/ft

2

 (4.1 mm/min) over 

the room or compartment using the area of the room 

divided by the number of sprinklers in the room.

 (7psi 

minimum)

SIN

FACTOR 

GPM/PSI

½

 

 (lpm/bar

½

)

TEMPERATURE

MAX.AREA OF 

COVERAGE

 

FEET (m)

MINIMUM 

PRESSURE

 

PSI (bar)

MINIMUM 

FLOW

 

GPM (L/min.)

DEFLECTOR TO 

CEILING/ 

MOUNTING 

 SURFACE 

DISTANCE

 

INCHES (mm)

MINIMUM 

DISTANCE 

BETWEEN 

SPRINKLERS

 

FEET (m)

155°F 

(68°C)

175°F 

(79°C)

200°F 

(93°C)

GL3010

3.0 

(43.2)

cULus 

EU

(1)

cULus

cULus

12 (3.6) x 12 (3.6)

7.1 (.49)

8.0 (30.3)

Smooth Ceilings 

Recessed

1-1/8 (29) 

to 1-5/8 (41)

Smooth Ceilings 

Exposed

Max. 4 (101.6)

Beamed Ceilings 

Adjacent

per NFPA 13, 13D, 

or 13R

as appropriate

Beamed Ceilings 

In Beam

14” Max. Beam Depth

1-1/8 (29) 

to 1-5/8 (41)

8 (2.4)

cULus 

EU

(1)

cULus

cULus

14 (4.3) x 14 (4.3)

11.1 (.765)

10.0 (37.8)

GL4110

4.1 

(59)

cULus 

EU

(1)

cULus 

EU

(1)

NA

12 (3.6) x 12 (3.6)

7.2 (.5)

11.0 (42)

cULus 

EU

(1)

NA

NA

14 (4.3) x 14 (4.3)

8.6 (.59)

12.0 (45)

cULus 

EU

(1)

cULus

NA

16 (4.9) x 16 (4.9)

11.7 (.81)

14.0 (53)

GL4910

4.9 

(70.6)

cULus 

EU

(1)

cULus 

EU

(1)

NA

12 (3.6) x 12 (3.6)

7.0 (.48)

13.0 (49)

cULus 

EU

(1)

cULus 

EU

(1)

NA

14 (4.3) x 14 (4.3)

8.2 (.57)

14.0 (53)

cULus 

EU

(1)

cULus 

EU

(1)

NA

16 (4.9) x 16 (4.9)

8.2 (.57)

14.0 (53)

cULus 

EU

(1)

cULus 

EU

(1)

NA

18 (5.5) x 18 (5.5)

12.0 (.83)

17.0 (64)

cULus 

EU

(1)

cULus 

EU

(1)

NA

20 (6.1) x 20 (6.1)

16.7 (1.15)

20.0 (76)

GL5610

5.6 

(80.6)

cULus

NA

NA

12 (3.6) x 12 (3.6)

7.2 (.5)

15.0 (57)

cULus

NA

NA

16 (4.9) x 16 (4.9)

11.5 (.79)

19.0 (72)

cULus

NA

NA

18 (5.5) x 18 (5.5)

14.1 (.97)

21.0 (79)

cULus

NA

NA

20 (6.1) x 20 (6.1)

18.4 (1.27)

24.0 (91)

TABLE A:  NFPA 13, 13R, AND 13D 

HYDRAULIC AND INSTALLATION DESIGN CRITERIA

 

(1)

LISTED BY UNDERWRITERS LABORATORIES, INC. FOR USE IN THE U.S., CANADA,  AND EUROPEAN UNION.

NOTE:

  

Deflector-to-Ceiling Distance Criteria reflects 2019 Edition of NFPA 13D and 13R.

Summary of Contents for GL-RES Series

Page 1: ...FPA 13 13D 13R and any other related documents as appropriate The GL3010 is typically utilized when maximum coverag es are not needed thereby reducing flow demands The GL5610 is typically the sprinkler of choice when utilizing Residential Sprinklers within an NFPA 13 Occupancy The larger K factor can be advantageous when needed to con form to the NFPA 13 hydraulic Special Design Approach for Resid...

Page 2: ...the room or compartment using the area of the room divided by the number of sprinklers in the room 7psi minimum SIN K FACTOR GPM PSI lpm bar TEMPERATURE MAX AREA OF COVERAGE FEET m MINIMUM PRESSURE PSI bar MINIMUM FLOW GPM L min DEFLECTOR TO CEILING MOUNTING SURFACE DISTANCE INCHES mm MINIMUM DISTANCE BETWEEN SPRINKLERS FEET m 155 F 68 C 175 F 79 C 200 F 93 C GL3010 3 0 43 2 cULus EU 1 cULus cULus...

Page 3: ...e www globesprinkler com Always obtain permission from the proper authorities to shut down the affected fire protection system and notify all personnel who may be affected by this action before closing a fire protection system main control valve for maintenance work on the system that it controls Sprinklers should only be cleaned by means of gently dust ing with a feather duster otherwise non oper...

Page 4: ...VE CAPS SPRINKLER ESCUTCHEON Quantity Finish Part Number See TABLE C Quantity SIN Temperature Rating Finish Part Number See TABLE B TABLE B PART NUMBER SELECTION PART NUMBER SIN TEMPERATURE FINISH XXXX XXX XX SIN TEMPERATURE FINISH GL3010 3010 155 155 F 68 C 01 BRONZE GL4110 4110 175 175 F 79 C 02 CHROME GL4910 4910 200 200 F 93 C 03 WHITE POLYESTER GL5610 5610 04 BLACK POLYESTER Note All combinat...