44
Installation and maintenance instructions Compact 0020313973_01
Code
Parameter
Values
Unit
Increment, select, explanation
Factory
setting
Min.
Max.
d.06
Target domestic hot wa-
ter temperature
Current value
℃
–
–
d.08
Status of the 230 V room
thermostat
Current value
–
OF
= Open (0 V, no heating mode)
on
= Closed (230 V, heating mode)
–
d.09
Target heating flow tem-
perature that is set on
the eBUS room thermo-
stat
Current value
℃
–
–
d.10
Status of the internal
pump in the heating cir-
cuit
Current value
–
OF
= Pump off
on
= Pump on
–
d.11
Status of the heating
circuit's shunt pump
Current value
–
Applies to: Installed heating circuit shunt pump
(optional)
OF
= Pump off
on
= Pump on
–
d.13
Status of the domestic
hot water circuit's circula-
tion pump
Current value
–
Applies to: Installed domestic hot water circuit
circulation pump (optional)
OF
= Pump off
on
= Pump on
–
d.14
Operating mode of the
modulating pump
0
5
–
0 = Speed-regulated (automatic pump operation in
levels 1 to 5)
1 = PWM = 55 %
2 = PWM = 65 %
3 = PWM = 75 %
4 = PWM = 85 %
5 = PWM = 95 %
1; 2; 3; 4; 5 = Fixed rotational speeds
→
Section
"Setting the pump output"
0
d.15
Pump speed
Current value
%
Hi
= 100%
–
d.16
Status of the 24 V room
thermostat (ON/OFF)
Current value
–
OF
= Heating off
on
= Heating on or eBUS control used
–
d.17
Heating control
–
–
–
0 = Flow temperature
1 = Return temperature (adjustment for underfloor
heating. If you have activated the return temperat-
ure control, the automatic heat output determina-
tion function is not active.)
0
d.18
Pump overrun operating
mode
1
3
–
1 = Comfort (continuously operating pump)
3 = Eco (pump runs intermittently)
3
d.20
Maximum target do-
mestic hot water tem-
perature
50
55
℃
Increment = 1
55
d.21
Status of the warm start
for domestic hot water
Current value
–
This function is displayed by the warm start is
not actually available for this product.
OF
is per-
manently displayed since the function is deactiv-
ated.
on
= function is activated and available
–
d.22
Status of the DHW de-
mand
Current value
–
OF
= No current requirement
on
= Current requirement
–
d.23
Status of the heat de-
mand
Current value
–
OF
= Heating off (Summer mode)
on
= Heating on
–
d.27
Function of relay 1
(multi-functional module)
1
10
–
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extraction hood
5 = External solenoid valve
6 = Fault message
7 = Solar pump (omitted)
8 = eBUS remote control
9 = Anti-legionella pump
10 = Solar valve
1
d.28
Function of relay 2
(multi-functional module)
1
10
–
2
d.33
Fan speed target value
Current value
rpm
Fan speed = Display value x 1000
–
d.34
Value for the fan speed
Current value
rpm
Fan speed = Display value x 1000
–