0020313973_01 Compact Installation and maintenance instructions
45
Code
Parameter
Values
Unit
Increment, select, explanation
Factory
setting
Min.
Max.
d.35
3-port valve position
Current value
–
0 = Heating
40 = Mid-position (frost protection or filling)
Hi
= Domestic hot water
–
d.36
Value for the domestic
hot water flow rate
Current value
l/min
–
–
d.39
Water temperature in the
solar circuit
Current value
℃
The water temperature in the solar circuit is then
only displayed if an optional solar set has been
installed.
–
d.40
Heating flow temperature
Current value
℃
–
–
d.41
Heating return temperat-
ure
Current value
℃
–
–
d.43
Heat curve
0.2
4
K
Consult the accessory's operating instructions in
order to implement this setting.
1.2
d.45
Base point of the heat
curve
15
30
℃
Consult the accessory's operating instructions in
order to implement this setting.
20
d.47
Outdoor temperature
Current value
℃
–
–
d.50
Correction of the min-
imum fan speed
0
2500
rpm
Increment = 100
Fan speed = Display value x 1000
600 (0.6 x
1000)
d.51
Correction of the max-
imum fan speed
-2500
0
rpm
Increment = 100
Fan speed = Display value x 1000 (flashing)
-1000 (1.0 x
1000)
d.58
Solar circuit post-heating
0
3
–
Applies to: Installed solar set (optional)
0 = Product's anti-legionella function deactivated
3 = Domestic hot water activated (min. target
value 55 °C)
0
d.60
Number of blocks by the
temperature cut-out (limit
temperature)
Current value
–
If the value is greater than 99, the display shows
the number alternately.
Example using the number 1581: The display re-
peatedly shows the sequence 15
→
81
→
__.
–
d.61
Number of unsuccessful
ignitions
Current value
–
–
d.62
Day/set-back function
0
30
K
Increment = 1
0
d.64
Average burner ignition
time
Current value
s
–
–
d.65
Maximum burner ignition
time
Current value
s
–
–
d.67
Remaining burner anti-
cycling time (setting un-
der d.02)
Current value
min
–
–
d.68
Number of unsuccessful
ignitions at 1st attempt
Current value
–
If the value is greater than 99, the display shows
the number alternately.
Example using the number 1581: The display re-
peatedly shows the sequence 15
→
81
→
__.
–
d.69
Number of unsuccessful
ignitions at 2nd attempt
Current value
–
–
d.71
Maximum target heating
flow temperature
30
75
℃
Increment = 1
75
d.80
Running time in heating
mode
Current value
h
Running time = Display value x 1000
–
d.81
Running time in domestic
hot water mode
Current value
h
Running time = Display value x 1000
–
d.82
Number of burner igni-
tions in heating mode
Current value
–
Number of ignitions = Display value x 1000
–
d.83
Number of burner igni-
tions in domestic hot wa-
ter mode
Current value
–
Number of ignitions = Display value x 1000
–
d.85
Increase in the min. out-
put (heating and do-
mestic hot water mode)
–
–
kW
Increment = 1
–
d.88
Flow rate limit value for
ignition in domestic hot
water mode
0
1
–
0 = 1.5 l/min (no delay)
1 = 3.7 l/min (2 s delay)
0
d.90
Status of the eBUS room
thermostat
Current value
–
0 = Not connected
1 = Connected
–