0020313973_01 Compact Installation and maintenance instructions
23
7.5.7
External termination into rain water down
pipe
≤ 3 m
Ø22mm
Ø 32mm
NB only combined foul/rainwater drain
7.5.8
Additional methods of introducing air breaks
1
2
3
1
Air break
2
Using a tundish
3
Using a pipe
7.5.9
Connection of condensate pump
Ø32mm
Ø22mm
≥ 3 m
Preferred option for external connection
7.6
Connecting the drain pipework for the
expansion relief valve
1
1.
Ensure that the pipeline is visible.
2.
Connect the expansion relief valve
(1)
to a suitable
discharge siphon.
–
The components must be set up in such a way that
you can see the water flowing out.
3.
Ensure that you can view the end of the pipe and that
discharged water or steam cannot cause injury to per-
sons or damage to electronic components.
7.7
Filling the condensate siphon
▶
Fill the condensate siphon with water.
–
≈
250 ml
7.8
Air/flue system
7.8.1
Installing and connecting the air/flue pipe
1.
You can find out which air/flue pipes may be used
by consulting the enclosed set-up instructions for the
air/flue system.
Condition
: Installation in damp rooms
▶
Connect the product to a room-sealed air/flue system.
Summary of Contents for Compact 24c-AS/1
Page 59: ......