background image

 

D1014 

- SIL 2 Repeater Power Supply Hart compatible 

G.M. International ISM0052-16 

 

Ordering information 

 

Front Panel and Features 

D1014 

1  2  3  4 

9  10  11  12 

16 

15 

14 

13 

5  6  7  8 

PWR ON 

1 2 



SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 9 / 10 years (

10% / >10 % of total SIF). 



PFDavg (1 year) 1.05 E-04, SFF 87.01%. 



SIL 3 Systematic capability. 



2 fully independent channels. 



Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2. 



4-20 mA Input, Output Signal. 



Hart compatible. 



Input and Output short circuit proof. 



High Accuracy. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1 



In-field programmability by DIP Switch. 



ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications. 



TÜV Functional Safety Certification. 



Type Approval Certificate DNV and KR for maritime applications. 



High Reliability, SMD components. 



High Density, two channels per unit. 



Simplified installation using standard DIN Rail and plug-in terminal blocks. 



250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier. 

Not used 

Terminal block connections 

HAZARDOUS AREA 

SAFE AREA 

+ Input Ch 2 for 2 wire Transmitters 

- Input Ch 2 for 2 wire Transmitters 

Not used 

Not used 

+ Input Ch 1 for 2 wire Transmitters 

- Input Ch 1 for 2 wire Transmitters 

Not used 

9

 

10

 

11

 

12

 

13

 

14

 

15

 

16

 

+ Output Ch 1 for Current Source mode or + Output Ch 1 for 
Voltage Source mode or + Output Ch 1 for Current Sink mode 

1

 

- Output Ch 1 for Current Source mode or - Output Ch 1 for 
Voltage Source mode or - Output Ch 1 for Current Sink mode 

2

 

+ Ch 1 Power Supply 12-24 Vdc 

3

 

- Ch 1 Power Supply 12-24 Vdc 

4

 

+ Output Ch 2 for Current Source mode or + Output Ch 2 for 
Voltage Source mode or + Output Ch 2 for Current Sink mode 

5

 

- Output Ch 2 for Current Source mode or - Output Ch 2 for  
Voltage Source mode or - Output Ch 2 for Current Sink mode 

6

 

+ Ch 2 Power Supply 12-24 Vdc 

7

 

- Ch 2 Power Supply 12-24 Vdc 

8

 

Model:  

D1014 

1 channel 

Power Bus enclosure 

2 channels 

/B 

 

Power Bus and DIN-Rail accessories: 
DIN rail anchor MCHP065   

DIN rail stopper MOR016 

Terminal block male MOR017 

Terminal block female MOR022 

Summary of Contents for D1014D

Page 1: ...D1014 SIL 2 Repeater Power Supply Hart compatible ISM0052 16 D1014S D1014D INSTRUCTION SAFETY MANUAL SIL 2 Repeater Power Supply Hart compatible DIN Rail Models D1014S D1014D ...

Page 2: ...ion accuracy 0 1 of full scale Linearity error 0 1 of full scale Supply voltage influence 0 05 of full scale for a min to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance change Temperature influence 0 01 on zero and span for a 1 C change Compatibility CE mark compliant conforms to Directive 2014 34 EU ATEX 2014 30 EU EMC 2014 35 EU LVD 2011 65 EU RoHS Environment...

Page 3: ...N Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier Not used Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 2 for 2 wire Transmitters Input Ch 2 for 2 wire Transmitters Not used Not used Input Ch 1 for 2 wire Transmitters Input Ch 1 for 2 wire Transmitters Not used 9 10 11 12 13 14 15 16 Output Ch 1 for Current Source mode...

Page 4: ...A D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 of the Co and Lo parameters of the Associated Apparatus excluding the cable then 50 of Co and Lo parameters are applicable and shall not be exceeded 50 of the Co and...

Page 5: ...C SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1014D 14 15 3 4 1 2 RL mA mA V HHT Ch 1 Supply 12 24 Vdc Source I Source V Sink I Out 1 HHT 2 Wire Tx I In 1 10 11 5 6 RL mA mA V Source I Source V Sink I Out 2 2 Wire Tx In 2 RL RL HHT HHT I 7 8 Ch 2 Supply 12 24 Vdc MODEL D1014S 14 15 3 4 1 2 RL mA mA V HHT Ch 1 ...

Page 6: ...fety logic solver is config ured to detect High failures and does not automatically trip on these failures this failure mode has been classified as a dangerous detected DD failure Fail Low failure mode that causes the output signal to go below the minimum output current 4 mA Assuming that the application program in the Safety logic solver is config ured to detect Low failures and does not automati...

Page 7: ...ished via conduit connections or another acceptable Division 2 Zone 2 wiring method according to the NEC and the CEC Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground D1014 series must be installed operated and maintained only by qualified personnel in accordance to the relevant national international installation standards e g I...

Page 8: ...responding section as an example Connect 12 24 Vdc power supply positive at terminal 3 and negative at terminal 4 for channel 1 For Model D1014D connect 12 24 Vdc power supply positive at terminal 7 and negative at terminal 8 for channel 2 For Model D1014S connect positive output of channel 1 at terminal 1 and negative output at 2 For Model D1014D in addition to channel 1 connections above connect...

Page 9: ...allows the mA sink or source mode or Volt operating mode configuration Configuration Side A Panel View Span Trimmer CH1 Screwdriver for Trimmers 1 x 0 5 mm Dip switch configuration Ω Ω Vtx Adjust Ch1 Screwdriver for Trimmers 2 x 0 5 mm Zero Trimmer CH1 Calibration Trimmer Ch1 Turn the trimmer clockwise to Increase Output value or turn the trimmer counterclockwise if you want to decrease Output val...

Page 10: ...ly is the same for all channels there for don t separate the terminals because one channel remains switched off Different power supply Cut both pins of the connector to open the wiring between the terminals using a wire cutter Turn the trimmer clockwise to Increase Output value or turn the trimmer counterclockwise if you want to decrease Output value Turn the trimmer clockwise to Increase Output v...

Page 11: ...llow step 1 Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA mA mA MODEL D1014D 14 15 3 4 1 2 10 11 5 6 7 8 V V Out 2 PS Supply _ Out 1 DMM V1 CAL In 2 V1 CAL In 1 DMM mA mA MODEL D1014D 14 15 3 4 1 2 10 11 5 6 7 8 If the maximum deviation is exceeded repeat the board calibration and proceed in the following way Set the calibrator CAL at 20 000 mA and regulate the current read by mult...