GBESS 2.4_4.8KWH system user manual
48
E25
Boost current is over the tolerable
value.
Restart system
E26
Battery Manager input voltage is too
high
Re-confirm battery input voltage
E27
Battery Manager over temperature
Waiting for Battery Manager
cooling down
E28
Battery
Manager
boost
current
warning
Re-start Battery Manager
E29
PV inverter fan locked
Check fan
E30
BatteryManager fan locked
Check fan
E31
PV inverter GFCI fault
Re-start PV inverter, contact the
service if continue occur
E32
PV inverter current-sensor fault
Re-start PV inverter, contact the
service if continue occur
E33
PV inverter current is over the tolerate
value
Re-start PV inverter, contact the
service if continue occur
E35
PV inverter Bus fault
Re-start PV inverter, contact the
service if continue occur
E40
PV inverter relay fault
Re-start PV inverter, contact the
service if continue occur
E41
Communication failure between PV
inverter and Battery Manager
Check communication cable
between PV inverter and Battery
Manager
E42
Communication failure between PV
inverter and energy meter
Please check the energy meter and
communication line status
E43
Communication failure between PV
and BMS
Please check BMS and
communication line status
E46 +N
Battery (2+N) over voltage warning
Re-start battery
E47+N
Battery (2+N) low voltage warning
Re-start battery
E48+N
Battery (2+N)Charge Over Current
Warning
Re-start battery
E49+N
Battery (2+N) discharge Over Current
Warning
Re-start battery
E50+N
Battery (2+N)Discharge Temperature
Warning
Re-start battery
E51+N
Battery (2+N) Charge Temperature
Warning
Re-start battery
E52+N
Battery (2+N)Under Voltage Warning
Re-start battery
Table 14 Fault Lists
N = (battery address- 2* 7), only suit for Pylon, Battery address respectively are 2, 3, 4 and 5.