108
TECHNICAL DATA
UPS Models
GM 360 PRO
GM 380 PRO
GM 3100 PRO
INPUT STAGE
Nominal Voltage
380-400-415 V AC Three-phase with neutral (4 wire)
Nominal Frequency
50-60Hz
Maximum input current
(1)
96A
125A
155A
Maximum battery current
150A
200A
250A
Input voltage tolerance accepted for no
battery intervention (referred to 400V AC)
±
20% @ 100% load
-40% +20% @50% load
Input frequency tolerance accepted for no
battery intervention (referred to 50/60Hz)
±
20%
40-72Hz
Input current Harmonic Distortion
THDi = 2,5%
(2)
Input power factor
≥
0.99
Power Walk In mode
Programmable from 1 to 125 sec. at steps of 1 sec
OUTPUT STAGE
Nominal Voltage
(3)
380/400/415 V AC three-phase with neutral (4 wire)
Nominal Frequency
(4)
50/60Hz
Output nominal current
87A
116A
145A
Nominal apparent power in output
60kVA
80kVA
100kVA
Nominal active power in output
54kW
72kW
90kW
Output power factor
0.9
Short-circuit current
1.5 x In for t > 500ms
Output voltage precision (referred to output
voltage 400V AC)
±
1%
Static stability
(5)
±
0.5%
Dynamic stability
±
3% resistive load
(6)
Output voltage harmonic distortion with linear
load and normalized distortion
≤
1% with linear load
≤
3% with distorted load
≤
1% with linear load
≤
3% with distorted load
≤
1% with linear load
≤
3,5% with distorted load
Crest factor accepted at nominal load
3:1
Frequency accuracy in free running mode
0.01%
Inverter overload (Vin>345V AC )
103% Infinite, 110% 10 min, 125% 1 min
Bypass Overload
110% Infinite,125% 60 minutes, 150% 10 minutes
BATTERY CHARGE STAGE
Nominal voltage
±
240Vdc
Maximum recharging current
(7)
10A (20A optional)