INSTALLATION
3.3.1 DC WIRING SIZING
The distance between the battery bank and the GP-ISW should be as short as possible to achieve
maximum efficiency and to reduce fire hazards. The size of the cable should be thick enough
to limit the voltage drop to less than 2% when carrying the maximum input current to prevent
frequent low-input voltage warnings and shutdown. Only use high quality copper wire.
For greater efficiency, the cables should be as short as possible. The combined cable length should
be no more than 10ft (3m). Keeping your wire runs as short as possible helps to prevent: low
voltage shutdowns and nuisance tripping of the DC breaker because of increased current draw.
The table below shows the recommended DC cable size, fuses/circuit breakers and DC grounding
cable sizes for the GP-ISW (
Note:
these values are correct for cables in free air, not conduit)
Model
Wire AWG
Inline Fuse / Circuit Breaker
GP-ISW200-12
#6
F-110A
GP-ISW200-24
#6
F-110A
GP-ISW400-12
#6
F-110A
GP-ISW400-24
#6
F-110A
GP-ISW700-12
#6
F-110A
GP-ISW700-24
#10
F-110A
GP-ISW1000-12
#4
F-110A
GP-ISW1000-24
#8
F-110A
GP-ISW1500-12
#2
F-200A
GP-ISW1500-24
#6
F-200A
GP-ISW2000-12
#2/0
F-300A
GP-ISW2000-24
#4
F-200A
GP-ISW3000-12
#4/0
F-400A
GP-ISW3000-24
#2
F-300A
GP-ISW4000-24
#2/0
F-400A