Leak detector type LAG 2000 A
4 / 28
part no. 15 071 53 e
INTENDED USE
Operating media
Bioethanol*)
Diesel fuel*)
Aviation fuel
Fuel oil*)**)
FAME*)**)
Petrol*)
Kerosene**)
Bio fuel oil*)**)
Urea solution
Marine fuel
Special petrol
Industrial oil
HVO
Liquid fertiliser (AHL,ASL,HAS) Water*)**)
Vegetable oil*)**)
*) are compatible with the following storage media
**) scope of approval: Construction Products Regulation CPR
For operating media without *) and **) as well as others, compatibility with the leak
detector liquid is to be proved in coordination with the manufacturer of the leak
detector liquid in individual cases. If the LAG 2000 A is used in combination with other
tanks or other substances that are hazardous to water, the relevant statutory and
technical requirements must be complied with.
You will find a
list of operating media
with descriptions, the relevant
standards and the country in which they are used in the Internet at
www.gok.de/liste-der-betriebsmedien.
Place of operation
In the case of systems in connection with areas where there is a risk of explosion,
compliance is required with the appropriately valid national regulations and installation
regulations!
In the case of repair work or changes to explosion-proof apparatus, compliance is required
with the national regulations!
In the case of repair work and maintenance,
original spare parts
may only be used.
The LAG 2000 A type leak detector is only intended for use areas where there is a risk
of explosion (EX protection zones).
Depending on the component, the operation of the LAG 2000 A type leak detector is
permitted in:
Component
EX protection
zone
Ignition protection type and/or
labelling
Indicator
1
)
not permitted
II (1) G [Ex ia] IIC
Leak detector liquid tank
2
)
1
II 1 G Ex ia IIC Ga
Sensor unit
3
)
1
)
The indicator is equipped with
-labelling, but has to be installed outside an
EX protection zone!
2
)
The leak detector liquid tank (LDL tank) is made from conductive plastic.
It requires electrical earthing in order to conduct charges away from its surface.
3
)
In potentially explosive atmospheres, install only the intrinsically safe model of the sensor
unit.
Installation location
•
operate indoors and outdoors, if protected against the weather