TROUBLE SHOOTING (CONT’D)
SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION
2. Pilot will not stay lit
A. Defective pilot
1. Check pilot, flame must
after carefully following
generator
impinge on pilot generator.
lighting instructions.
Clean and or adjust pilot for
maximum flame impingement
on generator.
2. Be sure wire connections
from generator at gas valve
terminals are tight and
generator is fully inserted into
pilot bracket.
3. Check thermogenerator
with millivolt meter. Take
reading at “TH-TP” and “TP”
terminals of gas valve.
Should read 325 millivolts
minimum while holding valve
knob depressed in pilot
position, pilot lit, and ON/OFF
switch “OFF”. Replace faulty
generator if reading is below
specified minimum.
B. Defective valve
1. Connect the millivolt
meter probes to the “TH-TP”
and “TP” terminals on the gas
valve. Turn knob to
pilot position, depress and
light pilot light. If meter
reading is greater than 325
m.v. after 30 seconds, the
pilot generator is good. If
pilot does not stay lit, the
valve is defective. If the
meter reading is less than
325 m.v., the thermo-
generator is defective.
C. Open wire connection
1. Check wire continuity and
in pilot circuit connections in pilot circuit.
18
Summary of Contents for EL GRANDE
Page 11: ...LOG PLACEMENT FOR MODEL HD5030 TV LOG SET STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 11 ...
Page 12: ...STEP 7 STEP 8 FINAL ARRANGEMENT 12 ...
Page 13: ...13 LOG PLACEMENT FOR MODEL HD4240TBF STEP 1 STEP 2 STEP 3 STEP 4 FINAL ARRANGEMENT ...
Page 15: ...14a Enervex ADC 100 Draft Switch connection 50D50 843 Enervex ADC 100 Draft Switch connection ...
Page 16: ...14B 14B ...