16
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD
NOTES:
High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
---
---
---
---
---
---
---
---
---
---
7203
2.18
6718
1.94
0.4
---
---
---
---
---
---
7306
2.54
6777
2.14
6257
1.80
5711
1.66
0.6
---
---
7477
2.97
6899
2.51
6323
2.10
5716
1.72
5103
1.39
---
0.8
7112
2.96
6467
2.46
5795
2.01
5101
1.61
---
---
---
---
---
---
1.0
5983
2.38
5190
1.89
---
---
---
---
---
---
---
---
---
---
1.2
4426
1.71
---
---
---
---
---
---
---
---
---
---
---
---
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
---
---
---
---
---
---
---
---
---
---
---
---
9664
4.05
0.4
---
---
---
---
---
---
---
---
9570
4.08
9197
3.82
8702
3.51
0.6
---
---
---
---
---
---
9038
3.82
8460
3.46
7949
3.14
---
---
0.8
---
---
8171
2.93
7630
3.70
7068
2.79
---
---
---
---
---
---
1.0
---
---
7901
2.85
7203
3.42
---
---
---
---
---
---
---
---
1.2
7344
4.35
---
---
---
---
---
---
---
---
---
---
---
---
CPC240 STANDARD BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
6
CPC180 STANDARD BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
6