background image

6

IO-230F

     08/04

Wire Sizing

Wire size is important to the operation of your equipment.
Use the following check list when selecting the appropriate
wire size for your unit.

Wire size must carry the Minimum Circuit Ampacity
(MCA).

Refer to the NEC (USA) or CSA (Canada) for wire
sizing.  The unit MCA for the air handler and the optional
electric heat kit can be found on the unit Series and
Rating Plate.

Wire size allows for no more than a 2% voltage drop
from the building breaker/fuse panel to the unit.

Refer to the latest edition of the National Electric Code
or in Canada the Canadian Electric Code when
determining the correct wire size.  The following table
shows the current carrying capabilities for copper
conductors rated at 75

o

C with a 2% voltage drop.  Use

the 

Table 7

  to determine the voltage drop per foot of

various conductors.

10

15

20

25

30

35

40

45

14

75

50

37

NR

NR

NR

NR

NR

12

118

79

59

47

NR

NR

NR

NR

10

188

125

95

75

63

54

NR

NR

8

301

201

150

120

100

86

75

68

6

471

314

235

188

157

134

118

110

*Based on NEC 1996

Maximum Allowable Length in Feet

to Limit Voltage Drop to 2%*

Minimum Circuit Ampacity (MCA) 

Wire Size

(AWG)

Table 7

Maximum Overcurrent Protection (MOP)

Every installation must include an NEC (USA) or CEC
(Canada) approved overcurrent protection device.  Also,
check with local or state codes for any special regional
requirements.

This protection can be in the form of fusing or HACR style
circuit breakers.  The Series and Rating Plate can be used
as a guide for selecting the MAXIMUM overcurrent device.

NOTE: Fuses or circuit breakers are to be sized larger
than the equipment MCA but not to exceed the MOP.

Electrical Connections – Supply Voltage
USE COPPER CONDUCTORS ONLY.

A knockout is provided on the air handler top panel or side
to allow for the entry of the supply voltage conductors. If
the knockouts on the cabinet sides are used for electrical
conduit, an adapter ring must be used in order to meet
UL1995 safety requirements.  An NEC or CEC approved
strain relief is to be used at this entry point.  The wire is to
be sized in accordance with the “Electrical Wire and MOP”
section of this manual.  Some areas require the supply
wire to be enclosed in conduit.  Consult your local codes.

Air Handler Only (Non-Heat Kit Models)

The building supply connects to the stripped black and white
wires contained in the air handler electrical compartment
cavity.  A ground screw is also contained in this area.  Attach
the supply wires to the  air handler conductors as shown in
the unit wiring diagram using appropriately sized solderless
connectors or other NEC or CEC approved means.

Air Handler With Non-Circuit Breaker Heat Kits

A terminal block is provided with the HKR kit to attach the
supply and air handler connections. Follow the HKR
Installation Manual and wiring diagram for complete wiring
details.

Air Handler With Heat Kits Containing a Circuit Breaker.

HKR models with a “C” suffix contain a circuit breaker(s).
The air handler has a plastic cover on the access panel
that will require either one or both sections to be removed
to allow the heat kit circuit breaker(s) to be installed.  See
the HKR Installation Instructions for further details. The air
handler wires and supply wires are installed directly onto
the HKR circuit breaker(s) as shown in the HKR Installation
Manual and wiring diagram.

Low Voltage Connections

Several combinations of low voltage schemes are available,
depending on the presence of a heat kit and whether the
heat kit is single-stage or multi-staging.  The low voltage
connections are determined by whether the outdoor unit is
a condenser or heat pump.  The 24V-control voltage
connects the air handler to the room thermostat and
condenser.  Low voltage wiring is to be copper conductors.
A minimum of 18AWG must be used for installations up to
50’  and 16AWG for installations over 50’.  Low voltage
wiring can be made through the top of the cabinet or through
either side.  See the “Thermostat Wiring” section of this
manual for the ARUF, ARPF and ARPT models for typical
low voltage wiring connections.  The Supplemental
Installation Manual included with the AEPT product shows
the wiring diagrams for these models.

REFRIGERANT LINES

WARNING

TO PROTECT  THE UNIT WHEN WELDING CLOSE  TO
THE PAINTED SURFACES, THE USE OF A QUENCHING
CLOTH IS STRONGLY  ADVISED  TO PREVENT
SCORCHING OR MARRING OF THE EQUIPMENT FINISH.
SOLDER WITH  A MINIMUM OF 5% SILVER IS
RECOMMENDED.

Tubing Preparation

All cut ends are to be round, burr free, and cleaned.  Failure
to follow this practice increases the chances for refrigerant
leaks.  The suction line is spun closed and requires pipe
cutters to cut off the closed end.

Post Brazing

Quench all welded joints with water or a wet rag.

Summary of Contents for AEPT

Page 1: ...Company L P IO 230F 2550 North Loop West Suite 400 Houston Texas 77092 08 04 www goodmanmfg com or www amana hac com 2003 2004 Goodman Manufacturing Company L P INSTALLATION OPERATING INSTRUCTIONS FO...

Page 2: ...092 713 861 2500 IMPORTANT SAFETY INSTRUCTIONS Recognize Safety Symbols Words and Labels The following symbols and labels are used throughout this manual to indicate immediate or potential hazards It...

Page 3: ...area such as a garage utility room or parking area and a carbon monoxide producing device is operated therein there must be adequate direct outside ventilation This ventilation is necessary to avoid t...

Page 4: ...USTAGREE UNLESS USING HKR3 3 PHASE SERIES HEAT KIT THIS AIR HANDLER DOES NOT HAVE FACTORY INSTALLED ELECTRIC HEAT ELECTRIC HEAT ISAVAILABLE AS AN ACCESSORY IF INSTALLING THIS OPTION THE ONLY HEAT KITS...

Page 5: ...OR OBJECTIONABLE FUMES ODORS INTO THE DUCTWORK The return ductwork is to be introduced into the air handler bottom upflow configuration Return Air Filters Each installation must include a return air f...

Page 6: ...e building supply connects to the stripped black and white wires contained in the air handler electrical compartment cavity Aground screw is also contained in this area Attach the supply wires to the...

Page 7: ...NT NOTE In order to prevent damage to the sensing bulb it is not permanently installed in the factory This bulb is to be removed prior to brazing Place in proper location after braze joint has cooled...

Page 8: ...that allows for access to all sides To prevent the evaporator coil pan from sweating the DPI accessory insulation kit is to be used when performing this conversion Note The DPI kit is not supplied wi...

Page 9: ...te The upper drain will become the secondary drain which is mandatory in many municipalities 7 Install the plastic plug removed in step 5 to the right side lower access panel and the oval shaped rubbe...

Page 10: ...n the OFF position For most applications this setting is to be changed according to the electric heat size and the outdoor unit selection The AEPT product uses a General Electric ECMTM motor This moto...

Page 11: ...PT MODELS SEE SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS FOR AEPT MODELS ROOM THERMOSTAT W Y G R 18 GA 4 WIRES WITH COOLING 3 WIRES WITHOUT R G W Y TO CONDENSING UNIT 24V CONNECTIONS 18 GA 2...

Page 12: ...UF ARPF ARPT 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R AR UNIT RED OT 1 OT 2 3 EHR 1 2 4 BROWN SEE NOTE 2 NOTES 1 OUTDOOR THERMOSTAT OT 1 SHOULD BE...

Page 13: ...y available Follow the thermostat manufacturer s instruction for installation START UP PROCEDURE Prior to start up ensure that all electrical connections are properly sized and tightened All panels mu...

Reviews: