background image

7

IO-230F

08/04

Piping Size

For the correct tubing size, follow the specification for the
condenser/heat pump.

WARNING

THIS COIL IS SHIPPED UNDER PRESSURE.  FOLLOW
THESE INSTRUCTIONS  TO PREVENT INJURY

 (SEE

FIGURES 1 AND

 

2).

Evaporator Coil Metering Devices

Flowrater Models (ARUF and ARPF)
For most installations no change to the flowrater orifice is
required.  In mix-matched applications (condenser/heat
pump is a different tonnage than the air handler), a different
flowrater orifice may be required. See the Goodman piston
kit chart PKC-00 or latest revision. Consult your local
distributor for the details regarding mix-matched orifice
sizing.
1.

Loosen the 13/16 nut 

1 TURN ONLY

. No pressure loss

indicates possible leak.

2.

Remove the nut and discard the black or brass cap.

3.

Remove the check piston to

 verify it is correct.

 See

piston kit chart in instructions.

4.

Use a tube cutter to remove the spin closure on the
suction line.

5.

Remove the tailpiece clamped to the exterior.

6.

Slide the 13/16 nut into position.

 

Braze tailpiece to

the liquid tube.

7.

Insert the suction line into the connection, slide the
insulation and the rubber grommet at least 18" away
from the braze joint.

8.

AFTER THE TAILPIECE HAS COOLED,

 position the

white Teflon seal and hand tighten the nut.

9.

Torque the 13/16 nut to 20-30 ft-lbs. [2.77-4.15 meter
kg].

10. Replace suction line grommet and insulation.

TAILPIECE

13/16" NUT

PLASTIC or BRASS CAP

WHITE

TEFLON SEAL

PISTON

APPLY FLOWRATER
GASKET FOR AIR
TIGHT APPLICATION

 

Figure 1

 

RUBBER

GROMMET

SUCTION LINE

WITH SPIN CLOSURE

Figure 2

TXV Models (ARPT and AEPT)

IMPORTANT NOTE:  In order to prevent damage to the
sensing bulb, it is not permanently installed in the factory.
This bulb is to be removed prior to brazing. Place in proper
location after braze joint has cooled (Figure 3).
1.

Loosen the 13/16 nut 

1 TURN ONLY.

  No pressure

loss indicates possible leak.

2.

Remove the nut and discard the black or brass cap.

3.

Remove large front panel and remove sensing bulb
from suction manifold.  TO PREVENT DAMAGE TO
SENSING BULB, ENSURE BULB IS NOT NEAR
FLAME OR IN CONTACT WITH SUCTION LINE OR
MANIFOLD DURING BRAZING.

4.

Use a tube cutter to remove the spin closure on the
suction line.

5.

Remove the tailpiece clamped to the exterior.

6.

Slide the 13/16 nut into position (Figure 1).  

Braze

tailpiece to liquid tube.

7.

Insert the suction line into the connection, slide the
insulation and the rubber grommet at least 18" away
from the braze joint.

8.

AFTER THE TAILPIECE HAS COOLED, 

position the

white Teflon seal and hand tighten the nut.

9.

Torque the 13/16 nut to 20-30 ft-lbs. [2.77-4.15 meter
kg].

10. Replace sensing bulb to horizontal portion of suction

line (Figure 3) just inside cabinet. Place bulb parallel
with suction line in the 10 o’clock position.  If 10 o’clock
position is inaccessible, place in the 2 o’clock position.
Secure bulb to line with strapping provided in literature
envelope.  Insulate sensing bulb to line with self-
adhesive insulation provided in envelope.

11. Replace access panel, suction line grommet, and

insulation.

 

REATTACH BULB HERE USING
STRAPPING AND INSULATION
PROVIDED

Figure 3

For the majority of installations, no adjustment to the TXV
setting is required.  However, if the measured superheat is
less than 8° or greater than 20°, an adjustment is required.
The adjustment stem is at the base of the valve (opposite
the diaphragm) under the flare nut.

Summary of Contents for AEPT

Page 1: ...Company L P IO 230F 2550 North Loop West Suite 400 Houston Texas 77092 08 04 www goodmanmfg com or www amana hac com 2003 2004 Goodman Manufacturing Company L P INSTALLATION OPERATING INSTRUCTIONS FO...

Page 2: ...092 713 861 2500 IMPORTANT SAFETY INSTRUCTIONS Recognize Safety Symbols Words and Labels The following symbols and labels are used throughout this manual to indicate immediate or potential hazards It...

Page 3: ...area such as a garage utility room or parking area and a carbon monoxide producing device is operated therein there must be adequate direct outside ventilation This ventilation is necessary to avoid t...

Page 4: ...USTAGREE UNLESS USING HKR3 3 PHASE SERIES HEAT KIT THIS AIR HANDLER DOES NOT HAVE FACTORY INSTALLED ELECTRIC HEAT ELECTRIC HEAT ISAVAILABLE AS AN ACCESSORY IF INSTALLING THIS OPTION THE ONLY HEAT KITS...

Page 5: ...OR OBJECTIONABLE FUMES ODORS INTO THE DUCTWORK The return ductwork is to be introduced into the air handler bottom upflow configuration Return Air Filters Each installation must include a return air f...

Page 6: ...e building supply connects to the stripped black and white wires contained in the air handler electrical compartment cavity Aground screw is also contained in this area Attach the supply wires to the...

Page 7: ...NT NOTE In order to prevent damage to the sensing bulb it is not permanently installed in the factory This bulb is to be removed prior to brazing Place in proper location after braze joint has cooled...

Page 8: ...that allows for access to all sides To prevent the evaporator coil pan from sweating the DPI accessory insulation kit is to be used when performing this conversion Note The DPI kit is not supplied wi...

Page 9: ...te The upper drain will become the secondary drain which is mandatory in many municipalities 7 Install the plastic plug removed in step 5 to the right side lower access panel and the oval shaped rubbe...

Page 10: ...n the OFF position For most applications this setting is to be changed according to the electric heat size and the outdoor unit selection The AEPT product uses a General Electric ECMTM motor This moto...

Page 11: ...PT MODELS SEE SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS FOR AEPT MODELS ROOM THERMOSTAT W Y G R 18 GA 4 WIRES WITH COOLING 3 WIRES WITHOUT R G W Y TO CONDENSING UNIT 24V CONNECTIONS 18 GA 2...

Page 12: ...UF ARPF ARPT 18 60 ABOVE 10 KW HEAT PUMP B L U E W H I T E C W2 R E D Y O R R Y C O W2 18 GA 7 WIRE R G E R AR UNIT RED OT 1 OT 2 3 EHR 1 2 4 BROWN SEE NOTE 2 NOTES 1 OUTDOOR THERMOSTAT OT 1 SHOULD BE...

Page 13: ...y available Follow the thermostat manufacturer s instruction for installation START UP PROCEDURE Prior to start up ensure that all electrical connections are properly sized and tightened All panels mu...

Reviews: