3
IMPORTANT:
To register your Goodman
®
brand unit, go to
www.goodmanmfg.com and click on “Warranty Registration”.
Complete registration as prompted.
To register your Amana
®
brand unit, go to www.amana-
hac.com and click “Warranty Registraion”. Complete regis-
tration as prompted.
Product limited warranty certificates for models currently in
production can be viewed at www.goodmanmfg.com or
www.amana-hac.com. If your model is not currently in pro-
duction or does not appear on the website, please contact
your installing contractor or contact customer service (877-
254-4729) to obtain a copy of your warranty certificate.
Each product overview page contains a Product Warranty
link; by clicking on it you will be able to view the limited war-
ranty coverage for that specific product. To view warranty reg-
istration information, click on the Product Warranty text on
the left navigation panel on the home page of each website.
The Online Product Registration pages are located in this
same section.
Keep this literature in a safe place for future reference.
Shipping Inspection
Always keep the unit upright; laying the unit on its side or top
may cause equipment damage. Shipping damage, and sub-
sequent investigation is the responsibility of the carrier. Verify
the model number, specifications, electrical characteristics,
and accessories are correct prior to installation. The distribu-
tor or manufacturer will not accept claims from dealers for
transportation damage or installation of incorrectly shipped
units.
Codes & Regulations
This product is designed and manufactured to comply with
national codes. Installation in accordance with such codes
and/or prevailing local codes/regulations is the responsibility
of the installer. The manufacturer assumes no responsibility
for equipment installed in violation of any codes or regula-
tions.
The United States Environmental Protection Agency
(EPA) has issued various regulations regarding the in-
troduction and disposal of refrigerants. Failure to follow
these regulations may harm the environment and can lead
to the imposition of substantial fines.
Should you have
any questions please contact the local office of the EPA.
Replacement Parts
When reporting shortages or damages, or ordering repair
parts, give the complete product model and serial numbers
as stamped on the product. Replacement parts for this prod-
uct are available through your contractor or local distributor.
For the location of your nearest distributor consult the white
business pages, the yellow page section of the local telephone
book or contact:
CONSUMER AFFAIRS
GOODMAN MANUFACTURING COMPANY, L.P.
7401 SECURITY WAY
HOUSTON, TEXAS 77040
(877) 254-4729
If replacing an air handler, the system must be manufacturer
approved and Air-Conditioning, Heating, and Refrigeration
Institute (AHRI) matched.
NOTE:
Installation of unmatched
systems is strongly discouraged.
Pre-Installation Instructions
Carefully read all instructions for the installation prior to in-
stalling product. Make sure each step or procedure is under-
stood and any special considerations are taken into account
before starting installation. Assemble all tools, hardware
and supplies needed to complete the installation. Some items
may need to be purchased locally. Make sure everything
needed to install the product is on hand before starting.
Location
NOTE:
Air handlers are designed for
indoor installation
only
.
Give special consideration to minimizing the length of refrig-
erant tubing when installing air handlers. Refer to Remote
Cooling/Heat Pump Service Manual, TP-107 Long Line Set
Application R-410A for guidelines. The unit clearance from a
combustible surface may be 0". However, service clearance
is to take precedence. In addition allow a minimum of 24" in
front of the unit for service clearance.
Do not install the air handler in a location that violates the
instructions provided with the condenser.
If the unit is located in an area with high ambient tempera-
ture and/or high humidity the air handler maybe subject to
nuisance sweating of the casing. On these installations a
wrap of 2” fiberglass insulation with a vapor barrier is recom-
mended.
Consult all appropriate regulatory codes prior to determining
final clearances. When installing this unit in an area that may
become wet, elevate the unit with a sturdy, non-porous ma-
terial. In installations that may lead to physical damage (i.e.
a garage) it is advised to install a protective barrier to pre-
vent such damage.
Ductwork
This air handler is designed for a complete supply and re-
turn ductwork system.
Do not operate this product without all the ductwork
attached.
To ensure correct system performance, the ductwork is to
be sized to accommodate 375-425 CFM per ton of cooling
with the static pressure not to exceed .5" WC. Inadequate
duct work that restricts airflow can result in improper perfor-
mance and compressor or heater failure. Ductwork is to be
constructed in a manner that limits restrictions and main-
tains suitable air velocity. Ductwork is to be sealed to the
unit in a manner that will prevent leakage.