Airflow Data — GCEC960803BN

Notes

• 

All furnaces ship as high speed for cooling.  Installer must adjust blower speed as needed.

• 

For most jobs, about 400 CFM per ton when cooling is desirable.

• 

INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

COOLING

Dipswitch Setting:

S1-1  S1-2  S1-3

Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Tstat Call

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

**OFF OFF OFF

Ylo

894

842

784

726

682

618

562

519

1111

1068

1025

984

941

885

860

801

ON OFF OFF

Ylo

750

644

569

507

442

388

328

N/A

894

842

784

726

682

618

562

519

ON ON OFF

Ylo

750

644

569

507

442

388

328

N/A

1111

1068

1025

984

941

885

860

801

OFF ON OFF^

Ylo

894

842

784

726

682

618

562

519

1221

1172

1128

1087

1049

1005

959

922

OFF OFF ON^

Ylo

894

842

784

726

682

618

562

519

1311

1293

1249

1203

1172

1122

1088

1041

OFF ON ON

Ylo

750

644

569

507

442

388

328

N/A

1221

1172

1128

1087

1049

1005

959

922

ON OFF ON

Ylo

1311

1293

1249

1203

1172

1122

1088

1041

1111

1068

1025

984

941

885

860

801

ON ON ON^ 

Ylo

1311

1293

1249

1203

1172

1122

1088

1041

750

644

569

507

442

388

328

N/A

CONTINUOUS FAN

Dipswitch Setting:

S2-2  S2-3  S2-4

Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Tstat Call

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

**OFF  OFF  OFF

G

1221

1172

1128

1087

1049

1005

959

922

ON  OFF  OFF

G

1311

1293

1249

1203

1172

1122

1088

1041

ON  ON  OFF

G

750

644

569

507

442

388

328

288

OFF  ON OFF

G

894

842

784

726

682

618

562

519

OFF  OFF  ON

G

1111

1068

1025

984

941

885

860

801

OFF  ON  ON

G

1221

1172

1128

1087

1049

1005

959

922

ON  OFF  ON

G

1221

1172

1128

1087

1049

1005

959

922

ON  ON  ON 

G

1221

1172

1128

1087

1049

1005

959

922

HEATING

Dipswitch Setting:

S1-4   S2-1

Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

CFM

CFM

**OFF OFF

W1

1221

40

1172

42

1128

44

1087

45

1049

47

1005

959

922

W2

1311

54

1293

54

1249

56

1203

58

1172

60

1122

1088

1041

ON OFF

W1

750

66

644

N/A

569

N/A

507

N/A

442

N/A

388

328

N/A

W2

1311

54

1293

54

1249

56

1203

58

1172

60

1122

1088

1041

ON ON

W1

750

NA

644

N/A

569

N/A

507

N/A

442

N/A

388

328

N/A

W2

894

N/A

842

N/A

784

N/A

726

N/A

682

N/A

618

562

519

OFF ON

W1

894

55

842

59

784

NA

726

NA

682

N/A

618

562

519

W2

1111

63

1068

66

1025

69

984

NA

941

NA

885

N/A

801

**  Factory Default

SINGLE STAGE COOLING^

*NOT RECOMMENDED

Summary of Contents for GCEC96

Page 1: ...down flow horizontal left or right Certified for direct vent 2 pipe or non direct vent 1 pipe Easy to install top venting with optional side venting Convenient left or right connection for gas and ele...

Page 2: ...ontrol Configuration NOx M Upflow Horizontal N Low NOx C Downflow Horizontal Cabinet Width Motor B 17 C 21 V Variable Speed ECM ComfortNet D 24 E Multi Speed ECM S Single Speed Maximum CFM 2 800 CFM 4...

Page 3: ...ipes The optional Combustion Air Pipe is dependent on installation code requirements and must be 2 or 3 diameter PVC Minimum Circuit Ampacity 1 25 x Circulator Blower Amps ID Blower amps Wire size sho...

Page 4: ...ernate Gas High Voltage Electrical Outlet Standard Drain Trap Drain Trap Holes Alternate Gas Supply Alternate Vent High Voltage Electrical Outlet Right Side Exterior Drain Trap Holes Low Voltage Elect...

Page 5: ...78 1035 1002 964 ON ON ON Ylo 939 894 846 806 759 706 661 614 Y 1137 1096 1056 1018 981 940 897 859 CONTINUOUS FAN Dipswitch Setting S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CF...

Page 6: ...969 928 ON ON ON Ylo 1328 1287 1249 1215 1170 1131 1085 1046 Y 782 629 547 469 396 333 N A N A CONTINUOUS FAN Dipswitch Setting S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM CF...

Page 7: ...Ylo 1311 1293 1249 1203 1172 1122 1088 1041 Y 750 644 569 507 442 388 328 N A CONTINUOUS FAN Dipswitch Setting S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM CFM CFM CFM CFM CFM...

Page 8: ...73 ON ON ON Ylo 1866 1817 1774 1729 1684 1637 1593 1552 Y 1477 1422 1364 1301 1244 1190 1135 1078 CONTINUOUS FAN Dipswitch Setting S2 2 S2 3 S2 4 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Tstat Call CFM...

Page 9: ...BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 800...

Page 10: ...GND INTERNAL TO SWITCH PRESSURE HIGH FIRE PROT DEVICE INTEGRATED CONTROL PK PU PLUG CONNECTION L N BK C DOOR OPEN OPEN WHEN DOOR SWITCH COMPARTMENT BLOWER SWITCH TEMP GND 1 BLOWER CIRCULATOR JUNCTION...

Page 11: ...5 CFSB21 Downflow Sub Base 21 RF000142 Drain Kit Horizontal Left Vertical Flue 0170K00000S Flush Mount Vent Kit 3 or 2 0170K00001S Flush Mount Vent Kit 2 AFE18 60A Fossil Fuel Dual Fuel Kit HASFK Hig...

Page 12: ...EC96 Goodman Manufacturing Company L P reserves the right to discontinue or change at any time specifications or designs without notice or without incurring obligations 2021 Goodman Manufacturing Comp...

Reviews: