background image

13

T

ERMINATION

 L

OCATIONS

NOTES:

 Refer to 

Section IV, Location Requirements and

Considerations

 for combustion air contaminant restrictions.

The following bullets and diagram describe the restrictions con-
cerning the appropriate location of vent/flue pipe and combustion
air intake pipe (when applicable) terminations.  Refer to 

Non-Di-

rect Vent (Single Pipe) Piping

 and 

Direct Vent (Dual Pipe) Piping

located in this section for specific details on termination construc-
tion.

All terminations (flue and/or intake) must be located at
least 12 inches above ground level or the anticipated
snow level.

Vent terminations (non-direct and direct vent) must
terminate at least 3 feet above any forced air inlet located
within 10 feet.

NOTE:  

This provision does not apply to the combustion

air intake termination of a direct vent application.

The vent termination of a 

non-direct

 

vent

 application must

terminate at least 4 feet below, 4 feet horizontally from, or
1 foot above any door, window, or gravity air inlet into any
building.

The vent termination of a 

direct vent

 application must

terminate at least 12 inches from any opening through
which flue gases may enter a building (door, window, or
gravity air inlet).

The vent termination of vent pipe run vertically through a
roof must terminate at least 12 inches above the roof line
(or the anticipated snow level) and be at least 12 inches
from any vertical wall (including any anticipated snow
build up).

A vent termination shall not terminate over public walkways
or over an area where condensate or vapor could create
a nuisance or hazard or could be detrimental to the
operation of regulators, relief valves, or other equipment.

The combustion air intake termination of a direct vent
application should not terminate in an area which is
frequently dusty or dirty.

12"

Non-Direct Vent

Vent/Flue Termination

No Terminations
 Above Walkway

12"

min.

4'

min.

Non-Direct Vent

Vent/Flue Termination

Direct Vent

Vent/Flue Termination

<10'

Forced Air

Inlet

Non-Direct Vent

&

Direct Vent

Vent/Flue Terminations

Grade or Highest

 Anticipated 
Snow Level

3' min.

12" min.

4' min.

12" min.

Vent Termination Clearances

NOTE:

 In Canada, the Canadian Fuel Gas Code takes precedence

over the preceding termination restrictions.

D

UAL

 C

ERTIFICATION

: N

ON

-D

IRECT

/D

IRECT

 V

ENT

This furnace is dual certified and may be installed as a non-direct
vent (single pipe) or direct vent (dual pipe) appliance.  A 

non-direct

vent

 installation requires only a vent/flue pipe, while a 

direct vent

installation requires both a vent/flue pipe and a combustion air
intake pipe.  Refer to the appropriate section for details concerning
piping size, length, number of elbows, furnace connections, and
terminations.

M

ATERIALS

 

AND

 J

OINING

 M

ETHODS

WARNING

T

O AVOID BODILY INJURY, FIRE OR EXPLOSION, SOLVENT CEMENTS MUST BE

KEPT AWAY FROM ALL IGNITION SOURCES (I.E., SPARKS, OPEN FLAMES, AND

EXCESSIVE HEAT) AS THEY ARE COMBUSTIBLE LIQUIDS.  

A

VOID BREATHING

CEMENT VAPORS OR CONTACT WITH SKIN AND/OR EYES.

Two- or three-inch nominal diameter PVC Schedule 40 pipe meet-
ing ASTM D1785, PVC primer meeting ASTM F656, and PVC sol-
vent cement meeting ASTM D2564 specifications must be used.
Fittings must be DWV type fittings meeting ASTM D2665 and ASTM
D3311.  Carefully follow the manufacturer’s instructions for cutting,
cleaning, and solvent cementing of PVC.
As an alternative to PVC pipe, primer, solvent cement, and fittings,
ABS materials which are in compliance with the following specifi-
cations may be used.  Two-or-three-inch ABS Schedule 40 pipe
must meet ASTM D1527 and, if used in Canada, must be CSA
listed.  Solvent cement for ABS to ABS joints must meet ASTM
D2235 and, if used in Canada, must be CSA listed.  The solvent
cement for the PVC to ABS transition joint must meet ASTM D3138.
Fittings must be DWV type fittings meeting ASTM D2661 and ASTM
D3311 and, if used in Canada, must be CSA listed.  Carefully
follow the pipe manufacturers’ instructions for cutting, cleaning,
and solvent cementing PVC and/or ABS.
All 90° elbows must be medium radius (1/4 bend DWV) or long
radius (Long sweep 1/4  bend DWV) types conforming to ASTM
D3311.  A medium radius (1/4  bend DWV) elbow measures 3 1/
16” minimum from the plane of one opening to the centerline of the
other opening for 2” diameter pipe, and 4 9/16” minimum for 3”
pipe.

P

ROPER

 V

ENT

/F

LUE

 

AND

 C

OMBUSTION

 A

IR

 P

IPING

 P

RACTICES

Adhere to these instructions to ensure safe and proper furnace
performance. The length, diameter, and number of elbows of the
vent/flue pipe and combustion air pipe (when applicable) affects
the performance of the furnace and must be carefully sized.  All
piping must be installed in accordance with local codes and these
instructions.
Piping must be adequately secured and supported to prohibit sag-
ging, joint separation, and/or detachment from the furnace.  Hori-
zontal runs of vent/flue piping must be supported every three feet
and must maintain a 1/4 inch per foot downward slope, back to-
wards the furnace, to properly return condensate to the furnace’s
drain system.  Allowances should be made for minor expansion
and contraction due to temperature variations.  For this reason,
particular care must be taken to secure piping when a long run is
followed by a short offset of less than 40 inches.

Summary of Contents for GCH9

Page 1: ...tall the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of s...

Page 2: ...ER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 13 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 14 STANDARD FURNACE CONNECTIONS 14 ALTERNATE FURNACE CONNECTIONS 14 NON DIRECT VENT SINGLE PI...

Page 3: ...XVIII Troubleshooting 32 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 32 DIAGNOSTIC CHART 32 FAULT RECALL 32 RESETTING FROM LOCKOUT 32 XIX Maintenance 32 ANNUAL INSPECTION 32 FILTERS 32 BURNERS 33 INDUCED...

Page 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty cer tificate in a safe location for future reference If additional informatio...

Page 5: ...e Pipe Connection Alternate 15 Rubber Elbow 16 Induced Draft Blower 17 Electrical Connection Inlets Alternate 18 Coil Front Cover Pressure Tap 19 Coil Front Cover Drain Port 20 Drain Line Penetrations...

Page 6: ...The input rate and temperature rise are set per the furnace rating plate 100 outside air is provided for combustion air requirements during construction Temporary ducting can be used II SAFETY II SAF...

Page 7: ...ly air opening and the combustible floor Exposure to contaminated combustion air will result in safety and performance related problems Do not install the furnace where the combustion air is exposed t...

Page 8: ...tions of use g If improper venting is observed during any of the above tests the common venting system must be corrected halogen type refrigerants cleaning solutions such as perchloroethylene printing...

Page 9: ...ipping heavily insulated caulked vapor barrier etc addi tional air may need to be provided using the methods described in 5 3 3 b or 5 3 4 Space Unconfined For purposes of this Code a space whose volu...

Page 10: ...directly with an additional room s of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space The total input of all gas utilization equipment installed...

Page 11: ...ropriate in stallation positions ductwork connections and resulting airflow arrangements VII HO VII HO VII HO VII HO VII HORIZO RIZO RIZO RIZO RIZONT NT NT NT NTAL APPLI AL APPLI AL APPLI AL APPLI AL...

Page 12: ...s require an orifice change to compensate for the energy content difference between natural and propane gas High altitude installations may require both a pressure switch and an orifice change These c...

Page 13: ...nt flue pipe and a combustion air intake pipe Refer to the appropriate section for details concerning piping size length number of elbows furnace connections and terminations MATERIALS AND JOINING MET...

Page 14: ...rd against inadvertent blockage COMBUSTION AIR PIPE DIRECT VENT INSTALLATIONS On upflow units secure the combustion air intake pipe directly to the air intake coupling On counterflow units secure the...

Page 15: ...LT IN LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES INCLUDING CARBON MONOXIDE 7 Upflow and Counterflow units For upright installations externally mount the rubber elbow to the ven...

Page 16: ...r of elbows in the piping system Pipe Size 4 inc 2 3 4 5 6 7 8 045_3 2 68 65 62 59 56 53 50 070_3 2 68 65 62 59 56 53 50 070_4 2 46 43 40 2 16 13 10 3 68 65 62 59 56 53 50 090_5 3 68 65 62 59 56 53 50...

Page 17: ...ter pipe can be used in place of 2 diameter pipe 4 Increased Clearance Configurations using 2 45 deg Long Sweep elbows should be considered equivalent to one 90 deg elbow VENT FLUE AND COMBUSTION AIR...

Page 18: ...furnace NOTE If the alternate vent flue outlet is utilized in an upright installation the drain trap and drain connections must be located on the same side as the alternate vent flue outlet In horizon...

Page 19: ...Hose B with green hose clamps Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding For details concerning mounting of the drain trap refer to S...

Page 20: ...ht down side panel grommet holes Secure tubes to Hose A and Hose B using green hose clamps Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or bound For details...

Page 21: ...must be sized in accordance with the maximum overcurrent pro tection specified on the unit rating plate An electrical disconnect must be provided at the furnace location NOTE Line polarity must be ob...

Page 22: ...Blower pressure switch is powered anytime the pressure switch is closed and provides 24 VAC humidifier control Remove the yellow wire and connect the supplied brown jumper wire to the pressure switch...

Page 23: ...plying the furnace must be properly sized based on the gas flow required specific gravity of the gas and length of the run The gas line installation must comply with local codes or in their absence wi...

Page 24: ...ctors and semi rigid tubing against physical and thermal damage when installed Ensure aluminum alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry...

Page 25: ...ne gas leak Rust can reduce the level of odorant in propane gas Do not rely on your sense of smell Contact a local propane gas supplier about installing a gas detecting warning system If the presence...

Page 26: ...uipped with means to prevent operation of either unit unless the damper is in the full heat or cool position When the furnace is installed without a cooling coil it is recom mended that a removable ac...

Page 27: ...bility of flue gases escaping through the drain system FURNACE OPERATION Purge gas lines of air prior to startup Be sure not to purge lines into an enclosed burner compartment Check for leaks using an...

Page 28: ...NT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR...

Page 29: ...rtially open position 2 Place thermometers in the return and supply ducts as close to the furnace as possible Thermometers must not be influenced by radiant heat by being able to see the heat exchange...

Page 30: ...MODE DIP SWITCH IS SET TO 2 STG POSITION The normal operational sequence in sequence is as follows R and W thermostat contacts close initiating a call for heat Integrated control module performs safet...

Page 31: ...Y CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION GENERAL A number of safety circuits are employed to ensure safe and proper furnace...

Page 32: ...e least recent fault RESETTING FROM LOCKOUT Furnace lockout results when a furnace is unable to achieve igni tion after three attempts during a single call for heat It is character ized by a non funct...

Page 33: ...AME SENSOR QUALIFIED SERVICER ONLY Under some conditions the fuel or air supply can create a nearly invisible coating on the flame sensor This coating acts as an insulator causing a drop in the flame...

Page 34: ...E LEA RE LEA RE LEAVIN VIN VIN VIN VING AN INST G AN INST G AN INST G AN INST G AN INSTALL ALL ALL ALL ALLA A A A ATI TI TI TI TIO O O O ON N N N N Cycle the furnace with the thermostat at least three...

Page 35: ...kage proper length elbows and termination Check drain system Correct as necessary Correct pressure switch setpoint or contact motion Tighten or correct wiring connection Pressure switch hose blocked p...

Page 36: ...e due to improper gas pressure or combustion air Induced draft blower and circulator blower runs continuously No furnace operation Integrated control module diagnostic LED is flashing FIVE 5 flashes F...