FURNACE SPECIFICATIONS
11
1.
These furnaces are manufactured for natural gas operation. Optional kits are available for conversion to propane operation.
2.
For elevations above 2000 feet the rating should be reduced by 4% for each 1000 feet above sea level. The furnace must not be derated, orifice changes should
only be made if necessary for altitude.
3.
The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufacturers method or in accordance with the "A.S.H.R.A.E.
GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total heat loss calculated should be
equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times output.
4.
Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps.
Unit specifications are subject to change without notice.
ALWAYS
refer to the units serial plate for the most up-to-date general and electrical information.
(1)
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
(3)
See Installation Instructions for appropriate vent diameter, length and number of elbows.
(4)
See Installation Instructions for appropriate combustion air pipe diameter, length and number of elbows.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in
accordance with all national and/or local electrical codes. Use copper wire only.
MODEL
GKS9
0453BX*
GKS9
0703BX*
GKS9
0704CX*
GKS9
0904CX*
GKS9
0905DX*
GKS9
1155DX*
Btuh
Input (US)
46,000
69,000
69,000
92,000
92,000
115,000
Output (US)
42,800
64,400
63,900
86,000
86,000
106,500
Input (CAN)
46,000
69,000
69,000
92,000
92,000
115,000
Output (CAN)
42,800
64,400
63,900
86,000
85,300
106,500
A.F.U.E.
92.1%
92.1%
92.1%
92.1%
92.1%
92.1%
Rated External Static (" w.c.)
.20 - .50
.20 - .50
.20 - .50
.20 - .50
.20 - .50
.20 - .50
Temperature Rise (°F)
35 - 65
35 - 65
35 - 65
35 - 65
35 - 65
35 - 65
ID Blower Pressure Switch Trip Point (" w.c.)
-1.20
-1.10
-1.10
-0.95
-0.75
-1.10
Blower Wheel (D" x W")
10 x 8
10 x 8
10 x 10
10 x 10
11 x 10
11 x 10
Blower Horsepower
1/3
1/3
1/2
1/2
3/4
3/4
Blower Speeds
4
4
4
4
4
4
Max CFM @ 0.5 E.S.P.
1200
1200
1600
1600
2000
2000
Power Supply
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
Minimum Circuit Ampacity (MCA)
(1)
9.4
9.4
13.8
13.8
13.2
13.2
Maximum Overcurrent Device
(2)
15.0
15.0
15.0
15.0
15.0
15.0
Transformer (VA)
40
40
40
40
40
40
Primary Limit Setting (°F)
150
160
160
150
160
170
Auxiliary Limit Setting (°F)
150
150
150
150
150
160
Rollout Limit Setting (°F)
200
200
200
200
200
200
Fan Delay On Heating
30 secs.
30 secs.
30 secs.
30 secs.
30 secs.
30 secs.
Off Heating
150 secs.
150 secs.
150 secs.
150 secs.
150 secs.
150 secs.
Fan Delay On Cooling
6 sec.
6 sec.
6 sec.
6 sec.
6 sec.
6 sec.
Off Cooling
45 secs.
45 secs.
45 secs.
45 secs.
45 secs.
45 secs.
Gas Supply Pressure (Natural/Propane) ("w.c.)
7 / 11
7 / 11
7 / 11
7 / 11
7 / 11
7 / 11
Manifold Pressure (Natural/Propane) ("w.c.)
3.5 / 10
3.5 / 10
3.5 / 10
3.5 / 10
3.5 / 10
3.5 / 10
Orifice Size (Natural/Propane)
43 / 55
43 / 55
43 / 55
43 / 55
43 / 55
43 / 55
Number of Burners
2
3
3
4
4
5
Vent Connector Diameter (inches)
(3)
2
2
2
2
2
2
Combustion Air Connector Diameter (inches)
(4)
2
2
2
2
2
2
Shipping Weight (lbs.)
132
135
153
158
170
175