background image

IO-151 

7

GMPN080 

2” 

75’ 

67.5’ 

60’ 

52.5’ 

45’ 

GMPN100 

3” 

100’ 

100’ 

100’ 

100’ 

100’ 

GMPN120 

3” 

100’ 

100’ 

100’ 

100’ 

100’ 

Should more elbows be required, subtract 7.5’ from the vent length for each elbow used (over 4 
as noted above). A maximum of 6 elbows is acceptable. The use of two 45

o

 over one 90

o

 is 

preferred. Do not count the termination as an elbow. 
 
Minimum vent lengths are 5 ft. for vertical runs and 3ft. for horizontal runs. 
A pitch of 1/4” per foot toward the drain assembly is necessary for proper drainage. 
 
The GMPN series of gas furnace is a condensing type appliance. The products of combustion are 
recirculated through a secondary coil. During this process the flue products are brought to a 
temperature below dew point. Thus the moisture present in the flue products condense, leaving a 
liquid by-product. This by-product must be removed from the furnace and it’s collection system. 
In addition, the vent temperatures are also considerably lower than conventional furnaces. This 
allows the use of low temperature plastic as the vent system. The recommended material is 
schedule 40 PVC, DWV, ABS (or equivalent if allowed by local code). See previous chart for 
proper sizing. The drain trap and related parts must be installed as shown in the illustrations 
located elsewhere in these instructions. Failure to follow these instructions can cause products of 
combustion including 

Carbon Monoxide

 to enter the building. This appliance may be horizontally 

vented through an exterior wall. See the illustrations located elsewhere in this manual. 

 
IF THIS FURNACE IS INSTALLED IN AN ATTIC OR SIMILAR AREA WHERE CONDENSATE 
OVERFLOW MAY BE A PROBLEM AN AUXILIARY DRAIN PAN MUST BE INSTALLED 
UNDER THE FURNACE WITH THE AUXILIARY DRAIN LINES ROUTED TO THE OUTDOORS 
TO PREVENT WATER DAMAGE CAUSED BY LEAKS. 
 
The vent pipes must be inspected annually. 

Visually check the vent terminal screen and clean if necessary. 
Visually check for blockage of the condensate disposal system. Hoses may be disconnected to 
determine that proper flow is maintained. Should an obstruction be observed, it can be dislodged 
by forcing a stream of water through it using a device such as a garden hose. 
 
This appliance may be vertically or horizontally vented. Horizontal venting requires a 90

long 

sweep elbow be installed as the vent terminal.  This elbow is to be installed  discharging 
downward and the factory supplied termination screen is to be attached.  To prevent damage to 
the vent pipe and its terminal the distance from the terminal to the exiting wall is to be the 
minimum practical distance (within 12” would be acceptable). Vertical venting does not require 
any terminal. If desired, the vent may be faced downward to prevent water or other foreign objects 
from entering the vent pipe. In that case two long radius elbows may be employed, facing 
downward and terminating no less than one foot (1’) from the roof surface.  

PROTECTION FROM FREEZING 

The vent pipe and drain assembly must be properly protected from freezing particularly if it is 
installed in an UNHEATED SPACE. Low wattage tape heaters should be employed on the drain 
system. The vent pipe should be insulated using a one (1) inch thick closed foam insulation if 
exposed to the outdoors. For pipes located indoors or protected from the elements such as a 
garage, basement, etc. fiberglass with an R value of 7 or greater is acceptable. 

 

CAUTION 

Summary of Contents for GMPN

Page 1: ...THER CARBON MONOXIDE PRODUCING DEVICE i e ATUOMOBLIE SPACE HEATER WATER HEATER ETC INSURE THAT THE ENCLOSED AREA IS PROPERLY VENTILATED WARNING CARBON MONOXIDE REFERRED TO AS CO CAN CAUSE SERIOUS PERSONAL INJURY OR DEATH WARNING THIS FURNACE IS DESIGN CERTIFIED FOR INSTALLATION IN BUILDINGS CONSTRUCTED ON SITE ONLY Goodman Manufacturing Company L P IO 151D 1501 Seamist Houston Texas 77008 12 01 RE...

Page 2: ...Blower wheel Misc sheetmetal items Capacitor HEAT EXCHANGER Heat exchanger sections Innerfront Secondary coil ELECTRICAL CONTROLS Control board Auxiliary main limit switch Roll out switch Transformer Door interlock switch Air pressure switch Induced draft blower BURNER ASSEMBLY Burners Manifold Orifices Gas Valve Ignitor Flame sensor MISCELLANEOUS Wrapper Access doors Chimney Gaskets and seals Wir...

Page 3: ...ON 19 20 REMOVING AN EXISTING APPLIANCE 20 21 INSPECTING AND CLEANING THE HEAT EXCHANGER 21 COMBUSTION AIR BLOWER OFF DELAY EAC CONTROL 22 HUMIDIFIER CONTROL 23 DRAIN CONNECTIONS 23 24 LIGHTING INSTRUCTIONS 25 WIRING DIAGRAM 26 THIS FURNACE CONTAINS ELECTRONIC COMPONENTS WHICH REQUIRE A DEFINITE GROUND PROVISIONS ARE MADE FOR CONNECTION OF THE GROUND IF THIS PRODUCT IS NOT PERMANENTLY AND POSITIVE...

Page 4: ...RSION IF REQUIRED MUST BE PERFORMED BY A QUALIFIED TECHNICIAN FAMILIAR WITH PERFORMING THIS TYPE OF CONVERSION IF LP CONVERSION IS REQUIRED ALL INSTRUCTIONS INCLUDED WITH THE FACTORY AUTHORIZED KIT MUST BE FOLLOWED THE ONLY KIT THAT MUST BE USED FOR THIS CONVERSION IS THE FACTORY AUTHORIZED LPM 01 FAILURE TO FOLLOW THOSE INSTRUCTIONS EXPLICITLY MAY CAUSE FIRE EXPLOSION OR PERSONAL AND PROPERTY DAM...

Page 5: ...uch a manner so that it is protected from water If any components should become wetted or submerged under water replace those parts before returning the furnace to operation DO NOT use as a construction heater DO NOT use in an area where freezing may occur without properly protecting the vent and drain system The drain may crack and leak if subjected to freezing temperatures DO NOT install in a ro...

Page 6: ...ECTION ON CIRCULATING AIR SUPPLY FOR RETURN DUCT INSTRUCTIONS Before proceeding with this installation check the following Correct clearance from combustible materials Adequate accessibility for servicing Flooring is not carpet or any other combustible material except wood Adequate combustion ventilation air is supplied Metal base plate is in place when using side s for return air In a garage the ...

Page 7: ...REA WHERE CONDENSATE OVERFLOW MAY BE A PROBLEM AN AUXILIARY DRAIN PAN MUST BE INSTALLED UNDER THE FURNACE WITH THE AUXILIARY DRAIN LINES ROUTED TO THE OUTDOORS TO PREVENT WATER DAMAGE CAUSED BY LEAKS The vent pipes must be inspected annually Visually check the vent terminal screen and clean if necessary Visually check for blockage of the condensate disposal system Hoses may be disconnected to dete...

Page 8: ...an seven 7 feet above public walkways or where it could cause a nuisance or hazard This also applies to steps and stairwells DO NOT locate the termination where condensate may present a problem such as flower beds patios etc DO NOT locate within four 4 feet of a gas or electric meter or gas regulator DO NOT locate the vent terminal within four 4 feet between buildings DO NOT locate the vent termin...

Page 9: ...s require this condensate to be neutralized prior to disposal See illustrations elsewhere in this I O for proper drain connections GAS PIPING GAS PIPE CAPACITY TABLE Check the rating plate to make certain that the gas supplied is compatable with the unit requirements Care should be taken after the installation of this appliance that the gas control valve is not subjected to high gas supply line pr...

Page 10: ...50 730 590 500 440 400 370 350 1 1 2 1600 1100 890 760 670 610 560 530 Nominal size of Iron Pipe in inches After the length of pipe has been determined select the pipe size which will provide the minimum cubic feet per hour of gas flow for the required input of the appliance In the case where more than one appliance utilizes the same supply pipe be sure to consider the sum of all appliances The cu...

Page 11: ...nstallation of Air Conditioning and Ventilating Systems NFPA 90A or the Standard for the Installation of Warm Air Heating and Air Conditioning Systems NFPA 90B If installed in parallel with a cooling unit the damper or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and if manually operated must be equipped with means to prevent operati...

Page 12: ... rating plate on the furnace A separate supply line with a current overload device and a manual switch where required must be installed Type T wire or equivalent with a minimum rating of 95 o F 35 o C temperature rise must be run directly from the main power supply to the junction box in the furnace Copper conductors are required Installation of the electrical supply must be in accordance with loc...

Page 13: ...e of the furnace to prevent an overfiring situation Overfiring can cause premature heat exchanger failure The input is controlled by the supply pressure orifice size manifold pressure and heating calorific value of the gas The supply pressure must be measured with this and all other gas burning appliances in operation The supply pressure must be adjusted to the pressure range stated on the series ...

Page 14: ...e sea level Kit HA 02 for natural and LP gases is required to convert furnaces from elevations of 2 000 to 4 500 feet 610m to 1 370m Canadian certification applies to the installations of up to 4 500 feet above sea level Installations above 4 500 feet is subject to acceptance by the local authorities having jurisdiction WARNING BEFORE ATTEMPTING ANY SERVICE OR ADJUSTMENTS INSURE THAT THE GAS AND E...

Page 15: ...E 1 100 MIN SEC 40 000 1 10 1 21 13 30 1 30 15 00 1 33 15 36 1 39 16 30 60 000 1 10 0 54 9 00 1 00 10 10 1 03 10 24 1 06 11 00 80 000 1 10 0 41 6 45 0 45 7 30 0 47 7 48 0 50 8 15 100 000 1 10 0 32 5 24 0 36 6 00 0 37 6 14 0 40 6 36 120 000 1 10 0 27 4 30 0 30 5 00 0 31 5 12 0 33 5 30 MAIN BURNER ADJUSTMENT The main burners should not need adjustment in most instances However air shutters are provi...

Page 16: ...s The burner flames should be extinguished if the flame sensor fails to detect the presence of burner flame To test disconnect the flame sensor wire before placing the furnace in operation The electronic ignition should ignite the burners However the burners should shut off after a few seconds of operation Disconnect the electrical supply to the furnace reinstall the disconnected sensor wire and r...

Page 17: ...ce on this furnace including checking or replacing circulating air filters disconnect main power DO NOT operate the furnace for extended periods of time without filters in place Dust and dirt in the air will restrict the air movement over the secondary coil causing nuisance cycling of safety controls which may result in a no heat condition MINIMUM FILTER SIZES INPUT BTUH FILTER SIZE TYPE 40 000 32...

Page 18: ...es are unobstructed DO close doors and windows This will reduce the heat load on the system DO avoid excessive use of bathroom and kitchen exhaust fans DO NOT let heat generated by televisions lamps direct sunlight etc influence the thermostat operation Exclusive of the mounting platform keep all combustible materials at least three 3 feet from the furnace DO NOT use the furnace room as a storage ...

Page 19: ...ace will remain inoperable until the condition is corrected During an open limit condition the circulating air blower will be energized The status light will blink four 4 times The condenser contactor will close After approximately five 5 seconds the circulating air blower will start on the cooling speed After the room thermostat is satisfied the condenser contactor will open The circulating air b...

Page 20: ...n servicing controls Wiring errors can cause dangerous and improper operation Verify proper operation after servicing It is the obligation of the installer to advise the user to have the furnace inspected and cleaned annually To clean the heat exchanger perform the following Adjust the room thermostat to its lowest setting Turn off the gas and electric supply to the furnace Remove the control acce...

Page 21: ...e no exposure to the substances listed in 3 below 3 The following installations may require OUTDOOR AIR for combustion due to chemical exposures Commercial buildings Buildings with indoor pools Furnaces installed in laundry rooms Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas Exposures to the following substances in the combustion air supply may also requ...

Page 22: ...is terminal is powered in both the heating and air conditioning modes when the circulating blower is operating HUMIDIFIER CONTROL The screw terminal on the ignition control called HUM is designed to give a 24 VAC signal to a humidistat in the heating mode DO NOT USE ON HUMIDIFIERS WHICH USE 115 VAC DRAIN CONNECTIONS UPFLOW LEFT SIDE DOWNFLOW LEFT SIDE ...

Page 23: ...IO 151 23 DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE HORIZONTAL LEFT HORIZONTAL RIGHT ...

Page 24: ...Move the gas control switch or knob above on this label If you don t smell Follow B in the safety information 7 Wait five 5 minutes to clear out any the control system and any gas control the appliance and to replace any part of a qualified service technician to inspect has been under water Immediately call D Do not use this appliance if any part tools If the gas control switch or knob control swi...

Page 25: ...IO 151 25 ...

Reviews: