30
www.goodmanmfg.com
SS-GSZ14
SS-GSZ14
www.goodmanmfg.com
31
Expanded Heating Data (cont.)
GSZ140301K* / ARUF29B14** + TXV
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
MBh
37.15
34.70
32.29
29.92
28.40
27.27
24.40
21.77
19.62
18.03
16.84
16.20
15.39
13.35
11.32
9.29
7.25
T/R
39.5
36.9
34.4
31.8
30.2
29.0
26.0
23.2
20.9
19.2
17.9
17.2
16.4
14.2
12.0
9.9
7.7
kW
2.48
2.42
2.37
2.31
2.27
2.25
2.19
2.14
2.08
2.02
1.96
1.93
1.91
1.85
1.79
1.74
1.68
Amps
11.9
10.9
10.1
9.4
9.0
8.8
8.3
7.8
7.4
7.0
6.6
6.4
6.2
5.8
5.4
5.0
4.5
COP
4.39
4.20
4.00
3.80
3.66
3.55
3.26
2.99
2.77
2.61
2.51
2.46
2.36
2.12
1.85
1.57
1.27
GSZ140311A* - ARUTXV
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
MBh
39.73
37.29
34.88
32.52
31.00
29.90
27.11
24.49
22.34
20.77
19.62
19.00
18.20
16.20
14.20
12.20
10.20
T/R
42.28
39.68
37.13
34.61
32.99
31.82
28.85
26.06
23.78
22.10
20.88
20.22
19.37
17.24
15.11
12.98
10.86
kW
3.01
2.92
2.83
2.74
2.69
2.65
2.56
2.47
2.39
2.30
2.21
2.15
2.12
2.03
1.94
1.85
1.76
Amps
14.3
13.2
12.2
11.4
10.9
10.6
10.0
9.4
8.9
8.5
8.0
7.7
7.6
7.1
6.6
6.1
5.5
COP
3.87
3.74
3.61
3.47
3.38
3.30
3.10
2.90
2.75
2.65
2.61
2.59
2.52
2.34
2.15
1.93
1.70
GSZ140361K* / ARUF37C14** + TXV
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
MBh
42.72
39.94
37.21
34.52
32.80
31.52
28.28
25.30
22.87
21.06
19.72
19.00
18.08
15.78
13.48
11.18
8.88
T/R
37.0
34.6
32.2
29.9
28.4
27.3
24.5
21.9
19.8
18.2
17.1
16.4
15.6
13.7
11.7
9.7
7.7
kW
2.81
2.76
2.71
2.66
2.63
2.61
2.56
2.50
2.45
2.40
2.35
2.32
2.30
2.25
2.20
2.15
2.10
Amps
13.6
12.5
11.6
10.8
10.3
10.0
9.4
8.9
8.4
7.9
7.5
7.3
7.1
6.6
6.2
5.7
5.1
COP
4.46
4.24
4.03
3.81
3.66
3.55
3.24
2.96
2.73
2.57
2.46
2.40
2.30
2.06
1.80
1.53
1.24
GSZ140371A* - ARUTXV
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
MBh
42.85
40.38
37.94
35.55
34.00
32.87
30.16
27.45
25.32
23.73
22.61
22.00
21.20
19.20
17.20
15.20
13.20
T/R
40.28
37.95
35.67
33.42
31.96
30.90
28.35
25.80
23.80
22.31
21.25
20.68
19.93
18.05
16.17
14.29
12.41
kW
2.75
2.71
2.67
2.64
2.61
2.60
2.56
2.52
2.48
2.44
2.40
2.38
2.37
2.33
2.29
2.25
2.21
Amps
13.7
12.6
11.6
10.8
10.4
10.1
9.5
9.0
8.5
8.0
7.6
7.3
7.2
6.7
6.3
5.8
5.2
COP
4.57
4.36
4.16
3.95
3.82
3.71
3.45
3.19
2.99
2.85
2.76
2.71
2.63
2.42
2.20
1.98
1.75
Calculations are based on nominal CFM and 70°F indoor dry bulb.
Amps = Outdoor unit amps (comp.+fan)
Note: Shaded area is AHRI Rating Conditions at 47°F outdoor ambient temperature.
kW = Total system power