4
www.goodmanmfg.com
SS-GSZ14
SS-GSZ14
www.goodmanmfg.com
5
Product Specifications (cont.)
GSZ14
0361K*
GSZ14
0371A*
GSZ14
0421K*
GSZ14
0481K*
GSZ14
0491K*
GSZ14
0601K*
Nominal Capacities
Cooling (BTU/h)
36,000
33,000
42,000
48,000
48,000
60,000
Heating (BTU/h)
36,000
34,000
42,000
48,000
48,000
60,000
Decibels
74
73
75
75
76
76
Compressor
RLA
15.4
14.1
16.7
18.5
19.9
26.4
LRA
83.9
72.2
109.0
124.0
109.0
134.0
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Condenser Fan Motor
Horsepower
1/6
1/4
1/6
1/4
1/6
1/4
FLA
0.95
1.30
1.1
1.30
1.1
1.30
Refrigeration System
Refrigerant Line Size¹
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
⅞"
⅞"
1⅛"
1⅛"
1⅛"
1⅛"
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.)
¾"
⅞"
⅞"
⅞”
⅞"
⅞"
Standard Line Set Length (max. feet)
80
80
80
80
80
80
Long Line Set Length (max. feet) ²
Equivalent Length
250
250
250
250
250
250
Linear Length
200
200
200
200
200
200
Vertical Length (outdoor below indoor)
80
80
80
80
80
80
Vertical Length (outdoor above indoor)
80
200
80
80
80
80
Valve Connection Type
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge
115
175
153
157
192
205
Electrical Data
Volts/Phase (60 Hz)
208-230/1
208-230/1
208-230/1
208-230/1
208-230/1
208-230/1
Minimum Circuit Ampacity ³
20.2
18.9
22.0
24.4
26.0
34.3
Max. Overcurrent Protection ⁴
35
30
35
40
45
60
Min / Max Volts
197 / 253
197/253
197 / 253
197 / 253
197 / 253
197 / 253
Electrical Conduit Size
½" or ¾"
1/2" or 3/4"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Unit Weights
Equipment Weight (lbs.)
173
220
191
226
273
277
Ship Weight (lbs)
184
240
207
237
288
292
ENERGY STAR® Certified ^
NO
NO
NO
^ Energy Star Notes
Proper sizing and installation of equipment is critical to achieving optimal performance. Split system air conditioners and heat pumps must
be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your contractor for details or visit www.energystar.gov.
The www.energystar.gov website provides up-to-date system combinations certified to meet ENERGY STAR requirements. See Page 24 for all ENERGY STAR certified combinations
as of this document’s revision date.
¹ Tested and rated in accordance with ARI Standard 210/240
² Reference TP-107* for additional application requirements
³ Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
⁴ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
•
Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
•
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
•
Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT
THE INDOOR COIL.