26
Room
Thermostat
Y2
Y
W
W2
R
G
C
Ylo
Y
W
W2
R
G
C
Ylo
Y
W
W2
R
G
C
Furnace 1
Furnace 2
Figure 37
115 Volt Line Connection of Accessories
(Humidifier and Electronic Air Cleaner)
The furnace integrated control module is equipped with line
voltage accessory terminals for controlling power to an op
-
tional field-supplied humidifier and/or electronic air cleaner.
The accessory load specifications are noted in the chart
below:
Humidifier
1.0 Amp maximum at 120 VAC
Electronic Air Cleaner
1.0 Amp maximum at 120 VAC
Turn OFF power to the furnace before installing any acces-
sories. Follow the humidifier or air cleaner manufacturers’
instructions for locating, mounting, grounding, and controlling
these accessories. Accessory wiring connections are to be
made through the 1/4” quick connect terminals provided on
the furnace integrated control module. The humidifier and
electronic air cleaner hot terminals are identified as HUM
and EAC. The humidifier and electronic air cleaner neutral
terminals are identified as NEUTRAL. All field wiring must
conform to applicable codes. Connections should be made
as shown.
If it is necessary for the installer to supply additional line
voltage wiring to the inside of the furnace, the wiring must
conform to all local codes, and have a minimum temperature
rating of 105°C. All line voltage wire splices must be made
inside the furnace junction box.
The integrated control module humidifier terminal (HUM) is
energized with 115 volts whenever the induced draft blower
is energized. The integrated control module electronic air
cleaner terminal (EAC) is energized with 115 volts whenever
the circulator blower is energized. This terminal can also be
used to provide 115 volt power to a humidifier transformer.
The remaining primary transformer wire would be connected
to the Line N on the control board.
HIGH VOLTAGE !
T
O
AVOID
PERSONAL
INJURY
OR
DEATH
DUE
TO
ELECTRICAL
SHOCK
,
DISCONNECT
ELECTRICAL
POWER
BEFORE
SERVICING
OR
CHANGING
ANY
ELECTRICAL
WIRING
.
WARNING
Accessories - Accessories Wiring
Gas Supply and Piping
T
O
AVOID
POSSIBLE
UNSATISFACTORY
OPERATION
OF
EQUIPMENT
DAMAGE
DUE
TO
UNDERFIRING
OR
EQUIPMENT
,
USE
THE
PROPER
SIZE
OF
NATURAL
/
PROPANE
GAS
PIPING
NEEDED
WHEN
RUNNING
PIPE
FROM
THE
METER
/
TANK
TO
THE
FURNACE
.
WARNING
Natural Gas
Minimum: 4.5" w.c.
Maximum: 10.0" w.c.
Propane Gas
Minimum: 11.0" w.c. Maximum: 13.0" w.c.
INLET GAS SUPPLY PRESSURE
The furnace rating plate includes the approved furnace gas
input rating and gas types. The furnace must be equipped
to operate on the type of gas applied. This includes any con
-
version kits required for alternate fuels and/or high altitude.
Inlet gas supply pressures must be maintained within the
ranges specified in the adjacent table. The supply pressure
must be constant and available with all other household gas
fired appliances operating. The minimum gas supply pres
-
sure must be maintained to prevent unreliable ignition. The
maximum must not be exceeded to prevent unit overfiring.
High Altitude Derate
When this furnace is installed at high altitude, the appropriate
High Altitude orifice kit must be applied. This is required due
to the natural reduction in the density of both the gas fuel
and combustion air as altitude increases. The kit will provide
the proper design certified input rate within the specified
altitude range.