41
User Manual V1.1-2022-11-15
10 Technical Parameters
AC Connector
AC Connector
Environmental Category
4K4H
Pollution Degree
III
Overvoltage Category
DC II / AC III
Protective Class
I
The Decisive Voltage Class (DVC)
PV: C AC: C Com: A
Active Anti-islanding Method
AFDPF + AQDPF
*4
Country of Manufacture (Only for
Australia)
China
Technical Data
GW8500-MS
GW10K-MS
Input
Max. Input Power (W)
13,500
13,500
Max. Input Voltage (V)
600
600
MPPT Operating Voltage Range (V)
80~550
80~550
MPPT Voltage Range at Nominal Power
(V)
250~500
280~500
Start-up Voltage (V)
80
80
Nominal Input Voltage (V)
360
360
Max. Input Current per MPPT (A)
16
16
Max. Short Circuit Current per MPPT (A)
20
20
Max. Backfeed Current to The Array (A)
0
0
Number of MPP Trackers
3
3
Number of Strings per MPPT
1
1
Output
Nominal Output Power (W)
8500
10000
Nominal Output Apparent Power (VA)
8500
10000
Max. AC Active Power (W)
*1
9350
10000
Max. AC Apparent Power (VA)
*2
9350
10000
Nominal Power at 40℃ (W) (Only for
Brazil)
8500
10000
Max Power at 40℃ (Including AC
Overload) (W) (Only for Brazil)
9350
10000
Nominal Output Voltage (V)
220/230/240
220/230/240
Output Voltage Range (V)
180~265
180~265
Nominal AC Grid Frequency (Hz)
50/60
50/60
AC Grid Frequency Range (Hz)
45~55 / 55~65
45~55 / 55~65