Set the monitor control pilot at a value, at which the shut-off relay must close the shut-off valve
(set value monitor control = closing pressure shut-off valve).
-
Turn the spindle on the shut-off relay to the left, until the shut-off valve closes. The red button
underneath the transparent cap on the shut-off relay, will then "spring" up.
-
Place the protective cap over the shut-off relay's spring casing.
-
Decrease the outlet pressure by opening the needle valve.
-
Turn the spindle on the monitor control pilot to the left.
-
Press the reset button on the shut-off relay in.
-
Set, with the monitor control pilot, a value at which the monitor control must start to operate.
-
Tighten the locking nut on the monitor control pilot's spindle, without turning the spindle.
-
Turn the spindle on the regulator pilot to the left, until the pressure gauge shows the required
reduced pressure.
-
Tighten the locking nut on the regulator pilot's spindle, without turning the spindle.
-
Close the needle valve.
-
Close the valve attached in the supply pipe, located within 5 meters of the station.
-
Close the ball valve DN50 in supply pipe, by turning the ball valve's handle a quarter of a turn
to the right.
-
Close the butterfly valve DN150 in the discharge pipe, by turning it a quarter of a turn to the
left
-
Close the casing cover.
Now you can start operating the cartridge; see paragraph 4.6.4 on page 23.
4.9 Replacing parts
The following paragraphs describe the replacement of a number of parts in the cartridge. The
following parts can be replaced on site, by the operator.
-
The two upper seal rings between the cartridge and casing (paragraph 4.9.1);
-
The two lower seal rings between the cartridge and casing (paragraph 4.9.2);
-
Dust filter (paragraph 4.9.3).
The remaining parts must be replaced by a qualified maintenance engineer in the service workshop.